General description:
The BTV Range of Trace Heating Units is of the parallel circuit self-regulating type, rated at 230 V
with power output up to 29W/m. the units have a maximum self-limiting temperature of 85°C.
Each trace heating units comprises:
- The active heating cable
- An end seal for terminating the remote end of the unit
- A cable gland for connecting the powered end of the unit to a suitable terminal enclosure , or alternative integrated power connection systems.
The active heating cable comprises two stranded copper conductors around which is extruded a semi-conductive core material. This core material increases in resistance with increasing temperature and gives the cable its self-limiting property. The core is covered with an extruded layer of modified polyolefin insulation before being overbraided with tinned copper. A further layer of polyolefin or fluoropolymer is extruded over the braid.
The declared maximum withstand temperature for the range is 85°C and the minimum installation temperature is -60°C.
Cable Accessories:
END SEALS
The end seals for terminating the remote end of the unit may be the following types:
-Type E-100-L or E-100, which are mechanical end seals incorporating an end cap which is filled with silicone grease sealant
-Type E-03 or E-06, which comprises heat shrink sleeves lined with hot melt adhesive
-Type E-150 mechanical end seals
SPLICES AND JOINT
The following splicing and jointing arrangement are provided
- A Raychem Type S-19 heat shrink splice kit for connecting lengths of active heating cable.
- A Raychem T-100 three connection system
- Type S-150 mechanical splice kit
POWER CONNECTION
Power connection may be achieved by the following means:
-Types C25-21 and C16-19, incorporating type GHG 960 923 P … plastic cable glands. The kits may use a molded silicone rubber core seal to insulate the bus wires with silicone grease in a molded cavity to seal the end of the heating cable.
In this arrangement the kits are Types C25-100 and C16-100
-Type C3 / 4-100- Metal or C25-100-Metal, which incorporate a type E8XF metallic cable gland
-Type C-150 power connector
-Type JBS-100 power connection system for a single heater cable
-Type JBM-100 power connection system for multiple heater cables
-Type JBU-100 power connection system
-Type CCON connection kit
TYPE APPROVAL CERTIFICATE
No. ELE052224XG/003
Enclosure - Page 2 of 2
BTV Series
Special Conditions for Safe Use:
The temperature of E-03 and S-19, and seal and splice shall not exceed 85°C
The end seal, splices and power connections have the following associated minimum ambient temperatures:
-55°C for the E-03, E-06 , S-19 and CCON ;
-50°C for the E-100, E-100-L, , E-150, S-150, C-150, JBS-100, JBU-100 and JBM-100 _
-40°C for the JBS-100-L, JBM-100-L, T100, JBU-100-L, E-100-L
-55°C for the GHG 960 923 P… cable gland with silicon rubber seals
-60°C for the type E8XF cable gland
Minimum bending radius is 35 mm for the type BTV units.
Thermal output rating: 9 to 29 W/m at 10° C
Reference documents:
- ATEX Certificate
Certification Authority: SGS Fimko Oy, Takomotie 8, FI-00380 Helsinki, Finland
ATEX Certificates: SGS20ATEX0048X - Issue 3
Marking:
II 2 GD Ex 60079-30-1 eb IIC T6 Gb Ex 60079-30-1 eb mb IIC T6 Gb Tmin -60° C or
II 2 GD Ex 60079-30-1 tb IIIC T80°C DB or Ex 60079-30-1 mb tb IIIC T80°C Db
Safety Standard:
EN60079-0: 2018 ; EN60079-7:2015+A1:2018; EN60079-18:2015+A1:2017 ; EN60079-30-1:2017
EN 60079-31:2014
- Data sheet: Raychem-DS-EU1380-BTV-EN
Remarks:
The Information listed in the present certificate are partial information based on the Baseefa Certificates.
The component listed in this Certificate are to be used / installed according to the manufacturer instructions:
Special conditions for safe use and installation to be in accordance with the above referenced ATEX Certificates.
The certificate supersedes previous RINA certificate No. ELE065119XG/003. |
|