MED381326CS!008ENG- -  -  N- MD9901 Smoke and Heat detector, including short circuit isolator,MD9901-EX Smoke and heat detector (I.S.) -N- S- S- -21/06/2026- Marine Equipment- - SN- S- - N-  - 840,487B2bisMarine EquipmentNumero Pratica,Direttiva,Norma,Schema,Richiesta,Validità,EmailR- MED381326CS/008- N-Jun 21, 2031840487
 
Form
  Marine Equipment(TO)
Certification N. MED381326CS/008 - (ENG)
Certificate date 21/06/2026
Type Protezione antincendio
Product Fixed fire detection and fire alarm systems components for control stations, service spaces, accommodation spaces, cabin balconies, machinery spaces and unattended machinery spaces: (d) Smoke detectors: Point detectors using scattered light, transmitted light or ionization
Item Nº MED/3.51d

Model
Items/Sizes
MD9901 Smoke and Heat detector, including short circuit isolator,MD9901-EX Smoke and heat detector (I.S.)
Applicant MICRODATA DUE - SOCIETA' A RESPONSABILITA' LIMITATA
Place of requester VIA GRETI DEL VARA 9  %  19020 Follo (SP)  % ITALY
Tel. N.,Fax, Email 0187 599101, 0187 558983, d.dido@microdatasrl.it
Directive (EU) 2025/1533
Standard EN 54-7:2018,IEC 60092-504:2016,IEC 60533:2015
Reference Documents SOLAS 74 Reg. II-2/7,SOLAS 74 Reg. X/3,IMO Res. MSC.36(63)-(1994 HSC Code) 7,IMO Res. MSC.97(73)-(2000 HSC code) 7,IMO Res. MSC.98(73)-(FSS Code) 9,IMO Res. MSC391(95)-(IGF Code) 11,IMO MSC.1/Circ 1242,RINA Rules for the certification of Marine Equipment
Validity 21/06/2031
EC TYPE-EXAMINATION (MODULE B) ENG
Vuoto Querysave
Chiara Boscolo S

EC TYPE EXAMINATION (MODULE B)
No. MED381326CS/008

This is to certify that RINA Services S.p.A. (Notified Body No. 0474) did undertake the relevant type approval procedures for the equipment identified below, which was found to be in compliance with the Fire Protection requirements of Marine Equipment Directive (MED) 2014/90/EU, including the requirements and testing standards of Regulation (EU) 2025/1533.
MED Item Nº MED/3.51d
Description Fixed fire detection and fire alarm systems components for control stations, service spaces, accommodation spaces, cabin balconies, machinery spaces and unattended machinery spaces: (d) Smoke detectors: Point detectors using scattered light, transmitted light or ionization
Type MD9901 Smoke and Heat detector, including short circuit isolator MD9901-EX Smoke and heat detector (I.S.)
Applicant MICRODATA DUE - SOCIETA' A RESPONSABILITA' LIMITATA
VIA GRETI DEL VARA 9,19020 Follo (SP),ITALY
Testing standards applied EN 54-7:2018,IEC 60092-504:2016,IEC 60533:2015
Regulations specified and reference documents SOLAS 74 Reg. II-2/7; SOLAS 74 Reg. X/3; IMO Res. MSC.36(63)-(1994 HSC Code) 7; IMO Res. MSC.97(73)-(2000 HSC code) 7; IMO Res. MSC.98(73)-(FSS Code) 9; IMO Res. MSC391(95)-(IGF Code) 11; IMO MSC.1/Circ 1242; RINA Rules for the certification of Marine Equipment
Issued in Genoa on
This Certificate is valid until
June 21, 2026
June 21, 2031
This Certificate consists of this sheet plus an attachment

________________________________________
Luigi Benedetti
RINA Services S.p.A.
**** NOTICE: This is NOT an official certificate ****

ATTACHMENT TO
No.  MED381326CS/008
Page 1 of 4
Products description:

MD 9901 Combined Smoke and Heat Detector
Analogue, Addressable microprocessor based photoelectric Smoke detector including separate Heat sensors.
A further sensor is exclusively used for analog measurement of temperature .
MD 9901 detector responds to para. 4.1 C) of CEA 4021 : July 2003 requirements
Temperature sensor complies with Class A1, B and C as defined on EN 54-5:2017 incl. A1:2018 requirements.

Reference documents
Microdata Due ST24736 Rev. B ELET/44885 Technical specification
Microdata Due D24735 Rev. 0 ELET/44888 Software description
Microdata Due D24731 Rev. H ELET/44886 Data sheet
Microdata Due D36689 Rev. 0 ELET/44887 Risk Assessment
Microdata Due D36647 Rev. 0 ELET/44889 Comparing Lexan 920 and Lexan 923 resin

Test Reports
BRE Testing Laboratory Test Report:

No. TE220771-A (RINA Id ELET/44793): Technical Evaluation of the the Microdata Due Model MD9901 analogue
addressable optical heat detector to the requirements of EN 54-7:2000, EN 54-5: 2000; Date 06/2005
No. TE220771SW (RINA Id. ELET/44794): Software evaluation of the Microdata Due Model MD9901 analogue addressable optical heat detector to EN 54-5 & EN 54-7:2000, Clause 4.11 Additional requirements for software controlled detectors. Date 04/2005.

Istituto Giordano Laboratory:

No. 213254 (RINA Id. ELET/44817): Enclosure Protection (IP 32 with detector bases MD9900-BC and MD9900-BCI and IP 65 with detector bases MD9900-BS and MD9900-BSI); Date 06/2006.

TesLab Laboratory:
No. 08C189F-3 (RINA Id. ELET/44792): Sensor Base with buzzer MD9900BBZ (EN 54-2 and EN 54-3); Date 02/2009
No 214123E (RINA Id. ELET/44815): Alarm system EMC (EN 50130-4:2011+A1:2014); 04/2021
No. 17B302E-b (RINA ELET/44795): Radiated Emission and Electromagnetic Field (EN 60092-504); Date: 01/2018

Microdata Due
No. IS-25793 (RINA Id. ELET/44796) and Report No. 1058: Collaudo Rivelatori Incendio modello MD9901 con centrale MD9800 (witnessed by Rina)













ATTACHMENT TO
CERTIFICATE No. MED381326CS/008
Page 3 of 4


MD9901-EX IS Combined Smoke and Heat Detector

Analogue , Addressable Intrinsically Safe multicriteria fire detector, model MD9901-EX
MD9901-EX may be installed in potentially explosive atmosphere, with the use of additional Zener Barrier, contained in Module MD9850.
Module MD9850 allows the galvanic isolation between the detection Loop and the EX detector line.
MD9850 Max ambient temperature Operating Condition: -5°C to +60°C

Reference documents
Microdata Due ST28999 Rev. B ELET/44891 Technical Specification
Microdata Due D29009 Rev. G ELET/44892 Data sheet
Microdata Due D24735 Rev. 0 ELET/44888 Software description
Microdata Due D36689 Rev.0 ELET/44887 Risk Assessment

Safety references:
Certificate: IMQ 09 ATEX 025 X (2015-11-13)
Marking: II 2GD Ex ia IIC T5 Ga ; Ex ia IIIC T100°C Da
Safety Standard: EN60079-0:2012+A11:2013; EN60079-11:2012
Certification Authority: IMQ S.p.A
Type approval certificate RINA ELE037623CS005 (for the zener barrier)

Test reports:
BRE Testing Laboratory Test Report:

No. TE255351 (RINA Id ELET/44797): Technical Evaluation of the the Microdata Due Model MD9901-Ex instrinsically safe analogue addressable optical heat detector to the requirements of EN 54-7:2000, EN 54-5: 2000; Date 06/2005
No. TE220771SW (RINA Id. ELET/44794): Software evaluation of the Microdata Due Model MD9901 analogue addressable optical heat detector to EN 54-5 & EN 54-7:2000, Clause 4.11 Additional requirements for software controlled detectors. Date 04/2005.

Istituto Giordano Laboratory:

No. 213254 (RINA Id. ELET/44817): Enclosure Protection (IP 32 with detector bases MD9900-BC and MD9900-BCI and IP 65 with detector bases MD9900-BS and MD9900-BSI); Date 06/2006.

TesLab Laboratory Test Report:
No. 17B302E-c (RINA Id. ELET/44798): Radiated Emission and Electromagnetic Field (EN 60092-504); Date: 01/2018.
No 214123E (RINA Id. ELET/44815): Alarm system EMC (EN 50130-4:2011+A1:2014); 04/2021




ATTACHMENT TO
No. MED381326CS/008
Pages 4 of 4
The mark of conformity may only be affixed to the above type approved equipment and a Manufacturer's Declaration of Conformity issued when the production control phase module (D, E or F) of Annex II of the Directive is fully complied with a written inspection agreement with a Notified Body
XXXX/YY
"WHEELMARK FORMAT"

XXXX
Notified Body number undertaking surveillance module
YY
Last two digits of year mark affixed
     
______________________________________________
General conditions for the approval
a) The initial conditions verified by RINA at the time of the approval are to be maintained
b) Any changes to the initial conditions are to be promptly communicated to RINA, which reserves the right to repeat the relevant assessment
c) This certificate will no be valid if the manufacturer makes any changes or modifications to the approved equipment, which have not been notified to, and agreed with RINA
d) RINA personnel are to be allowed to witness during the performances of activities, upon their request
e) The activities are to be carried out in compliance with the RINA Rules and/or other applicable Rules

f) Should the specified regulations or standards be amended during the validity of this certificate, the product is to be reapproved prior to it being placed on board vessels to which the amended regulations or standards apply. 


__________________________________________
Luigi Benedetti
**** NOTICE: This is NOT an official certificate ****