Products description:
MD 9901 Combined Smoke and Heat Detector
Analogue, Addressable microprocessor based photoelectric Smoke detector including separate Heat sensors.
A further sensor is exclusively used for analog measurement of temperature .
MD 9901 detector responds to para. 4.1 C) of CEA 4021 : July 2003 requirements
Temperature sensor complies with Class A1, B and C as defined on EN 54-5:2017 incl. A1:2018 requirements.
Reference documents
Microdata Due ST24736 Rev. B ELET/44885 Technical specification
Microdata Due D24735 Rev. 0 ELET/44888 Software description
Microdata Due D24731 Rev. H ELET/44886 Data sheet
Microdata Due D36689 Rev. 0 ELET/44887 Risk Assessment
Microdata Due D36647 Rev. 0 ELET/44889 Comparing Lexan 920 and Lexan 923 resin
Test Reports
BRE Testing Laboratory Test Report:
No. TE220771-A (RINA Id ELET/44793): Technical Evaluation of the the Microdata Due Model MD9901 analogue
addressable optical heat detector to the requirements of EN 54-7:2000, EN 54-5: 2000; Date 06/2005
No. TE220771SW (RINA Id. ELET/44794): Software evaluation of the Microdata Due Model MD9901 analogue addressable optical heat detector to EN 54-5 & EN 54-7:2000, Clause 4.11 Additional requirements for software controlled detectors. Date 04/2005.
Istituto Giordano Laboratory:
No. 213254 (RINA Id. ELET/44817): Enclosure Protection (IP 32 with detector bases MD9900-BC and MD9900-BCI and IP 65 with detector bases MD9900-BS and MD9900-BSI); Date 06/2006.
TesLab Laboratory:
No. 08C189F-3 (RINA Id. ELET/44792): Sensor Base with buzzer MD9900BBZ (EN 54-2 and EN 54-3); Date 02/2009
No 214123E (RINA Id. ELET/44815): Alarm system EMC (EN 50130-4:2011+A1:2014); 04/2021
No. 17B302E-b (RINA ELET/44795): Radiated Emission and Electromagnetic Field (EN 60092-504); Date: 01/2018
Microdata Due
No. IS-25793 (RINA Id. ELET/44796) and Report No. 1058: Collaudo Rivelatori Incendio modello MD9901 con centrale MD9800 (witnessed by Rina)
ATTACHMENT TO
CERTIFICATE No. MED381326CS/008
Page 3 of 4
MD9901-EX IS Combined Smoke and Heat Detector
Analogue , Addressable Intrinsically Safe multicriteria fire detector, model MD9901-EX
MD9901-EX may be installed in potentially explosive atmosphere, with the use of additional Zener Barrier, contained in Module MD9850.
Module MD9850 allows the galvanic isolation between the detection Loop and the EX detector line.
MD9850 Max ambient temperature Operating Condition: -5°C to +60°C
Reference documents
Microdata Due ST28999 Rev. B ELET/44891 Technical Specification
Microdata Due D29009 Rev. G ELET/44892 Data sheet
Microdata Due D24735 Rev. 0 ELET/44888 Software description
Microdata Due D36689 Rev.0 ELET/44887 Risk Assessment
Safety references:
Certificate: IMQ 09 ATEX 025 X (2015-11-13)
Marking: II 2GD Ex ia IIC T5 Ga ; Ex ia IIIC T100°C Da
Safety Standard: EN60079-0:2012+A11:2013; EN60079-11:2012
Certification Authority: IMQ S.p.A
Type approval certificate RINA ELE037623CS005 (for the zener barrier)
Test reports:
BRE Testing Laboratory Test Report:
No. TE255351 (RINA Id ELET/44797): Technical Evaluation of the the Microdata Due Model MD9901-Ex instrinsically safe analogue addressable optical heat detector to the requirements of EN 54-7:2000, EN 54-5: 2000; Date 06/2005
No. TE220771SW (RINA Id. ELET/44794): Software evaluation of the Microdata Due Model MD9901 analogue addressable optical heat detector to EN 54-5 & EN 54-7:2000, Clause 4.11 Additional requirements for software controlled detectors. Date 04/2005.
Istituto Giordano Laboratory:
No. 213254 (RINA Id. ELET/44817): Enclosure Protection (IP 32 with detector bases MD9900-BC and MD9900-BCI and IP 65 with detector bases MD9900-BS and MD9900-BSI); Date 06/2006.
TesLab Laboratory Test Report:
No. 17B302E-c (RINA Id. ELET/44798): Radiated Emission and Electromagnetic Field (EN 60092-504); Date: 01/2018.
No 214123E (RINA Id. ELET/44815): Alarm system EMC (EN 50130-4:2011+A1:2014); 04/2021