MED063325WSENGD- -  -  N- RGSJ-H,RGSJ-L -N- S- S- -10/06/2025- Marine Equipment- - SN- S- - N-  - 1,241,906B2bisMarine EquipmentNumero Pratica,Direttiva,Norma,Schema,Richiesta,Validità,EmailR- MED063325WS- N-Jun 9, 20301241906
 
Form
  Marine Equipment(TO)
Certification N. MED063325WS - (ENG)
Certificate date 10/06/2025
Type Protezione antincendio
Product Fixed water based local application fire fighting systems components for use in category "A" machinery spaces (Nozzles and performance tests)
Item Nº MED/3.48

Model or Denomin.
Items
RGSJ-H,RGSJ-L
Applicant Guangzhou Ruigang Fire-Fighting Equipment Co., Ltd.
Place of requester No.2, Zhongwei Road, Dongyong Town, Nansha District Guangzhou (Guangdong)  % CHINA
Tel. N.,Fax, Email 020-34855108, ---, ship119gdruigang@126.com
Directive (EU) 2024/1975
Standards IMO MSC.1/Circ.1387
Reference Documents SOLAS 74 Reg.II-2/10, IMO Res.MSC.36(63)-(1994 HSC Code) 7, IMO Res.MSC.97(73)-(2000 HSC Code) 7.
Request 02/20/2025
Expire date 09/06/2030
Responsible Office SHANGHAI
EC TYPE-EXAMINATION (MODULE B) ENG
Vuoto Querysave
Qiang Sun S

EC TYPE EXAMINATION (MODULE B)
CERTIFICATE No. MED063325WS

This is to certify that RINA Services S.p.A. (Notified Body No. 0474) did undertake the relevant type approval procedures for the equipment identified below, which was found to be in compliance with the Fire Protection requirements of Marine Equipment Directive (MED) 2014/90/EU, including the requirements and testing standards of Regulation (EU) 2024/1975.
MED Item Nº MED/3.48
Description Fixed water based local application fire fighting systems components for use in category "A" machinery spaces (Nozzles and performance tests)
Type RGSJ-H; RGSJ-L
Applicant Guangzhou Ruigang Fire-Fighting Equipment Co., Ltd.
No.2, Zhongwei Road, Dongyong Town, Nansha District Guangzhou (Guangdong),CHINA
Testing standards IMO MSC.1/Circ.1387
Reference standards SOLAS 74 Reg.II-2/10, IMO Res.MSC.36(63)-(1994 HSC Code) 7, IMO Res.MSC.97(73)-(2000 HSC Code) 7.
Issued in SHANGHAI on
This Certificate is valid until
June 10, 2025
June 9, 2030
This Certificate consists of this sheet plus an attachment

________________________________________
Qiang Sun
RINA Services S.p.A.
**** NOTICE: This is NOT an official certificate ****

ATTACHMENT TO
CERTIFICATE No.  MED063325WS
Page 1 of 3

Product Description


The system(Type:RGSJ-H & RGSJ-L) is a water mist system for use in protection of Machinery Spaces of Category A or similar fire risk areas, composed of nozzles (spray heads), steel piping, manual or automatic section valves, test valves, control panel and water supply pump(s).

The system is to be designed according to principal requirements for the system, SOLAS '74 Reg.II-2/10.5.6 and IMO MSC.1/Circ.1387.

Only the nozzles are with the scope of this MED certificate. Pumps, pipes, valves, couplings and other systems components are subject to case-by-case approval.

The open type nozzles (Type: XSWT1.6/3 & XSWT6/0.8) are made of Copper Alloy(QAL9-2) with the following characteristics:

Fixed Water-based Local Application Fire-fighting System
Product Model
RGSJ-H
RGSJ-L
Working Pressure
3.0~15.0 Mpa
0.8~1.6 Mpa
Nozzle Details
Type
XSWT1.6/3
XSWT6/0.8
K-factor
1.6
6.0
Flow (using Q = K • (10p)1/2)
8.76 L/min at min.p = 3.0 Mpa
16.97 L/min at min.p = 0.8 Mpa

The open type nozzles (Type: XSWT1.6/3 & XSWT6/0.8) are to be installed above the protected objects according to the following specifications:
Type
XSWT1.6/3
XSWT6/0.8
Max. horizontal spacing of nozzles
3.0 m
2.5 m
3.0 m
2.5 m
Height Range above the Project Objects
2.5 m ~ 12.0 m *
0.5 m ~ 2.5 m *
2.5 m ~ 12.0 m *
0.5 m ~ 2.5 m *
Minimum pressure
p = 3.0 Mpa (at spray heads)
p = 0.8 Mpa (at spray heads)
Nozzle Arrangement Form **
1x1, 2x2, 1x3
1x1, 2x2, 1x3
* Nozzles are to be installed out to a position being at the periphery of the protected objects (see IMO MSC/Circ.1387, annex 3.4.2.2), the nozzles are to be installed in a pendant (downward) position.
** Nozzles in single rows are accepted when half spacing is used, the outer nozzle should be placed at least at the edge of the protected area.

ATTACHMENT TO
CERTIFICATE No. MED063325WS
Page 2 of 3
Field of Application/Limitation

The nozzles are approved for use in a fixed water-based local application fire-extinguishing system for protection of Machinery Spaces of Category A or similar fire risk areas.

Reference Documents

Typical Technical Documentation, edited by Guangzhou Ruigang Fire-Fighting Equipment Co., Ltd., and approved by RINA with No.: SHFP-31841.

Tests Carried Out

The nozzles were tested according to IMO MSC/Circ.1165 and IMO MSC.1/Circ.1387 as per below:
- Extinguishing Fire Tests Report (Ref. No.: RGSJ-0903) for nozzles were carried out by Guangzhou Ruigang Fire-Fighting Equipment Co., Ltd. dated on September 03, 2024 ~ September 05, 2024, and filed by RINA with No.: SHFP-31832;
- Evaluation and Test Report (Ref. No.: NX2024092907) for Nozzles were carried out by Nanjing Fire Laboratory Technology Co., Ltd. dated on November 11, 2024, and filed by RINA with No.: SHFP-31835;
- Vibration Test Report (Ref. No.: PG018-240316) for nozzles according to para. 4.15 of MSC.1-Circ.1165 were carried out by Shanghai Jianke Technical Assessment of Construction Co., Ltd. (under RINA Narrative Report on Lab Assessment) dated on October 31, 2024, and filed by RINA with No.: SHFP-31837.

Installation Testing

The installation tests of the system as following:
- At least one section should be tested with full flow through the nozzles.
- Test of manual and remote release of all section valves and start of pumps.
- Testing of alarms (SOLAS Ch. II-2, Reg.10.5.6.4).
- Testing of automatic start of system (in case of unattended machinery spaces).
- Pressure testing of water pipe system.
- System to be cleaned in accordance with routines outlined in makers installation manual.
- Other tests as required by RINA Rules (pressure testing of piping, etc.) and according to maker's manual shall be carried out.

Remarks

1. Installation of the system, spacing of nozzles and components used shall be in accordance with the type examination documentation.
2. Prior to fitting the system on board, the following details shall be submitted to class for approval for each separated case, as minimum:
.1 System arrangement plans including location of nozzles, sections valves, release stations and pump-unit (including water supply);
.2 Documentation of power supply and control system;
.3 Specification of pipes, electrical motor, valves, pumps and associated components;
.4 Pressure drop calculations and water mist capacity calculations;
.5 Arrangement of interface to fire detection and alarm system (where applicable);
.6 Manual with design, installation, operation, test and maintenance instructions.
3. The nozzle shall be marked as para.5 of MSC/Circ.1165 and the Mark of Conformity as per Annex I of 2014/90/EU.




ATTACHMENT TO
CERTIFICATE No. MED063325WS
Pages 3 of 3
The mark of conformity may only be affixed to the above type approved equipment and a Manufacturer's Declaration of Conformity issued when the production control phase module (D, E or F) of Annex II of the Directive is fully complied with a written inspection agreement with a Notified Body
XXXX/YY
"WHEELMARK FORMAT"

XXXX
Notified Body number undertaking surveillance module
YY
Last two digits of year mark affixed
     
______________________________________________
General conditions for the approval
a) The initial conditions verified by RINA at the time of the approval are to be maintained
b) Any changes to the initial conditions are to be promptly communicated to RINA, which reserves the right to repeat the relevant assessment
c) This certificate will no be valid if the manufacturer makes any changes or modifications to the approved equipment, which have not been notified to, and agreed with RINA
d) RINA personnel are to be allowed to witness during the performances of activities, upon their request
e) The activities are to be carried out in compliance with the RINA Rules and/or other applicable Rules

f) Should the specified regulations or standards be amended during the validity of this certificate, the product is to be reapproved prior to it being placed on board vessels to which the amended regulations or standards apply. 


__________________________________________
Qiang Sun
**** NOTICE: This is NOT an official certificate ****