Place of Manufacturer:
NCT S.a.r.l
Lot n. 108, Rue Sfax-Zone Industrielle Mghira 2-2082 Fouchana Ben Arous
TUNISIA
E90/50 Series Fuse Holder/Disconnectors - Main features:
Rated Voltage Ue: 690 Vac (Fuse system F); Rated Current Ith: 50A ac;
Rated frequency: 50/60 Hz, Rated conditional short circuit Icc: 120 kA
Rated Insulation Voltage Ui: 800V; Rated impulse withstand voltage Uimp: 6kV
Suitability for isolation: yes; utilization category: AC-20B; Degree of protection:IP20
Max rated power dissipation of fuse-link 5W (gG type) @25°C Tamb; Fuses size: 14x51 mm
Pollution degree:3
| Type | Poles | Signal LED | Neutral |
| E91/50 | 1P | No | -- |
| E91N/50 | 1P+N | No | Right |
| E92/50 | 2P | No | -- |
| E93/50 | 3P | No | -- |
| E93N/50 | 3P+N | No | Right |
| E91/50s | 1P | Yes | -- |
| E91N/50s | 1P+N | Yes | Right |
| E92/50s | 2P | Yes | -- |
| E93/50s | 3P | Yes | -- |
| E93N/50s | 3P+N | Yes | Right |
| E91N/50 | 1P+N | No | Left |
| E93N/50 | 3P+N | No | Left |
| E91N/50s | 1P+N | Yes | Left |
| E93N/50s | 3P+N | Yes | Left |
E90/125 Series Fuse Holder/Disconnectors - Main features:
Rated Voltage Ue: 690 Vac (Fuse system F); Rated Current Ith: 100A ac;
Rated frequency: 50/60 Hz, Rated conditional short circuit Icc: 120 kA
Rated Insulation Voltage Ui: 800V; Rated impulse withstand voltage Uimp: 6kV
Suitability for isolation: yes; utilization category: AC-20B; Degree of protection:IP20
Max rated power dissipation of fuse-link 9.5W (gG type) @25°C Tamb; Fuses size: 22x58 mm
Pollution degree:3
| Type | Poles | Signal LED | Neutral |
| E91/125 | 1P | No | -- |
| E91N/125 | 1P+N | No | Right |
| E92/125 | 2P | No | -- |
| E93/125 | 3P | No | -- |
| E93N/125 | 3P+N | No | Right |
| E91/125s | 1P | Yes | -- |
| E91N/125s | 1P+N | Yes | Right |
| E92/125s | 2P | Yes | -- |
| E93/125s | 3P | Yes | -- |
| E93N/125s | 3P+N | Yes | Right |
| E91N/125 | 1P+N | No | Left |
| E93N/125 | 3P+N | No | Left |
| E91N/125s | 1P+N | Yes | Left |
| E93N/125s | 3P+N | Yes | Left |
ISO 9001:2015 Certificate No. 2021/95429.2 (valid until 10/2027); Production Site: NCT S.a.r.l; QA system certifying body: AFNOR
ABB ISO 9001:2015 Certificate No. 9105.ELTR (valid until 06/2026); QA system certifying body: IMQ
Test Report:
CB Test Certificate No. IT-IMQ-25826; Date: 2025-07-17; Type Ref. E90 series; Reference Standard IEC 60947-3:2020 in conjunction with IEC 60947-1:2020.
IMQ Test Report: PB25-0114406-01-00 and from PB25-0114406-01-01 to PB25-0114406-01-10; Date: 2025-06-30
CB Test Certificate No. IT-IMQ-25811; Date: 2025-07-14; Type Ref. E90 series; Reference Standard IEC 60269-1:2006, IEC 60269-1:2006/AMD1:2009, IEC 60269-1:2006/AMD2:2014, IEC 60269-2:2013, IEC 60269-2:2013/AMD1:2016.
IMQ Test Report: PB18-0023628-02/00 and from PB18-0023628-02/01 to PB18-0023628-02/10, PB18-0023628-02/00A and from PB18-0023628-02/01A to PB18-0023628-02/10A, PB25-0114391-01 and PB25-0114391-02; Date: 2025-06-30
ABB Test Report No. 2CE02168_04; Type Ref.: E90/50 series; Tests: Humidity, Insulation resistance, Dry Heat, High Voltage, Vibration; Date: 2008-01-30
ABB Test Report No. 2CE02168_03; Type Ref.: E90/125 series; Tests: Humidity, Insulation resistance, Dry Heat, High Voltage, Vibration; Date: 2014-12-9
General Remarks:
Admissible max. rated current to be evaluated considering 45°C ambient temperature.
This Certificate annuls and replaces the previous No. ELE147318CS.
Offer No. 2024/31041 - Job: RS/2024/CS/01/5051
Initial Audit carried out at the production site: NCT S.a.r.l.; date: 21/11/2025; Job: RS/2026/CS/01/156
The documents above mentioned have been archived in the Leonardo Draw Plus portal under the project:
https://leodrawplus.rina.org/projects/122312/detail.
Validity of this certificate is subject to satisfactory outcome of yearly audit as per RINA "Rules for Testing and Certification of Marine Materials and Equipment"
|
|