Product description
Glazed single leaf hinged door adjacent to a fixed glazed panel. Leaf maximum dimensions are 1092x1952 mm (WxH) and maximum clear opening is 1000x1910 mm(WxH). The glass panes, having clear opening size of 922x1780 mm (door) and 842x1900 mm (fixed panel), are composed, moving from the exposed side, of a glass type PYRAN S (manufacturer Schott AG - Germany) fitted with or without deposited metallic oxides and having thickness of 6 mm, a void space, 9 mm thick and a toughened pane having thickness of 8 mm, with or without deposited metallic oxides, manufactured by Soglass. The door frame, the fixed panel frame and the glass retaining frame are composed of hollow stainless steel profiles having thickness of 1.5 mm bolted by means of M10 screws, on the side not exposed to the fire, to steel flats having dimensions of 60x6 mm (lower part) and to L shaped carbon steel profiles having dimensions of 60x40x6 mm (upper part) and 60x60x6 mm (other sides). On the upper side U shaped steel profiles having thickness of 4 mm and dimensions of 50x59 mm are fitted between the frame and L shaped profiles and bolted to the same. Between the glass faces, the frame and the glass retaining frames, gaskets of KERAFIX FLEXLIT type, are fitted. Between the glass edges and the frame, on lower side, also spacers of calcium silicate having dimensions of 25x15x6 mm, are fitted. Between door frame and glass frame intumescing strips type SEALBIFIRE S BLACK, are fitted. The glass panes are sealed by means of sylicone type PENSIL 300. The door may be fitted with door check.
|
ATTACHMENT TO
CERTIFICATE Nr. MED093122CS/004
Page 2 of 3 |
Field of application
Fire resistant A-0 single leaf hinged glazed door adjacent to a fixed glazed panel with fire hazard on side fitted with the toughened pane having thickness of 6 mm. Fire resistant A-0 Class single leaf hinged door in compliance with IMO MSC.1/Circ. 1319 dated 11 June 2009. In this case the dimensions relevant to the height and with of the door may be increased of 15% provided that the surface area is not increased of more than 10%.
Reference documents
SOMEC MARINE drawing No. SDM-34 dated 8 March 2012 approved on 15 March 2012 with endorsement No. LABS-648.
Tests carried out
Tests as per RINA Test Laboratory Report No. 2012CS01712/5 issued on 15 March 2012 according to IMO Res. A. 754(18) and to IMO MSC.1/Circ. 1319 dated 11 June 2009. |