MC-6a/9a/12a/18a/9b/12b/18b/22b/32a/40a/50a/65a/75a/85a/100a
Product Description
- METASOL type contactor applicable to the marine environment with following rating:
1. Frame Size 18AF
Type | Rated Freq. [Hz] | Rated
Insulation
Voltage | Ambient
Temp. [C] | Rated Thermal Current
Ith [A] | Rated Operational Voltage Ue[V] | Rated
operational current Ie[A] | Utilization
Category |
MC-6a | 50/60 | 690 | 45 | 25 | 200/240
380/440
500/550
690 | 9
7
6
4 | AC-3 |
MC-9a | 50/60 | 690 | 45 | 25 | 200/240
380/440
500/550
690 | 11
9
7
5 | AC-3 |
MC-12a | 50/60 | 690 | 45 | 25 | 200/240
380/440
500/550
690 | 13
12
12
9 | AC-3 |
MC-18a | 50/60 | 690 | 45 | 32 | 200/240
380/440
500/550
690 | 18
18
13
9 | AC-3 |
2. Frame Size 22AF
Type | Rated Freq. [Hz] | Rated Insulation Voltage | Ambient
Temp. [C] | Rated Thermal Current
Ith [A] | Rated Operational Voltage Ue[V] | Rated
operational current Ie[A] | Utilization
Category |
MC-9b | 50/60 | 690 | 45 | 25 | 200/240
380/440
500/550
690 | 11
9
7
6 | AC-3 |
MC-12b | 50/60 | 690 | 45 | 27 | 200/240
380/440
500/550
690 | 13
12
12
9 | AC-3 |
MC-18b | 50/60 | 690 | 45 | 40 | 200/240
380/440
500/550
690 | 18
18
13
9 | AC-3 |
MC-22b | 50/60 | 690 | 45 | 45 | 200/240
380/440
500/550
690 | 22
22
20
18 | AC-3 |
3. Frame Size 40AF
Type | Rated Freq. [Hz] | Rated Insulation Voltage | Ambient
Temp. [C] | Rated Thermal Current
Ith [A] | Rated Operational Voltage Ue[V] | Rated
operational current Ie[A] | Utilization
Category |
MC-32a | 50/60 | 1000 | 45 | 55 | 200/240
380/440
500/550
690 | 32
32
28
20 | AC-3 |
MC-40a | 50/60 | 1000 | 45 | 60 | 200/240
380/440
500/550
690 | 40
40
32
23 | AC-3 |
4. Frame Size 65AF
Type | Rated Freq. [Hz] | Rated Insulation Voltage | Ambient
Temp. [C] | Rated Thermal Current
Ith [A] | Rated Operational Voltage Ue[V] | Rated
operational current Ie[A] | Utilization
Category |
MC-50a | 50/60 | 1000 | 45 | 100 | 200/240
380/440
500/550
690 | 55
50
43
28 | AC-3 |
MC-65a | 50/60 | 1000 | 45 | 115 | 200/240
380/440
500/550
690 | 65
65
60
35 | AC-3 |
5. Frame Size 100AF
Type | Rated Freq. [Hz] | Rated Insulation Voltage | Ambient
Temp. [C] | Rated Thermal Current
Ith [A] | Rated Operational Voltage Ue[V] | Rated
operational current Ie[A] | Utilization
Category |
MC-75a | 50/60 | 1000 | 45 | 125 | 200/240
380/440
500/550
690 | 75
75
64
42 | AC-3 |
MC-85a | 50/60 | 1000 | 45 | 135 | 200/240
380/440
500/550
690 | 85
85
75
45 | AC-3 |
MC-100a | 50/60 | 1000 | 45 | 160 | 200/240
380/440
500/550
690 | 105
105
85
65 | AC-3 |
Reference Documents
KEMA Test Certificate No. NL-9848/M2 dated 17 December 2008, Test Report No. NL-13534 dated 05 November 2007
KEMA Test Certificate No. NL-14734 dated 26 August 2008, Underwriters Lab. Ref. No. DK-15348 dated 13 March 2009
KEMA Test Certificate No. NL-31652/A1 dated 26 June 2014
DEMKO UL CB scheme Test Certificate No. DK-100615-UL, Test Report No. DK-10517-D25~38-CB-1
LSIS PT&T Test Report No. R426-0502 dated 09 April 2025
Asbestos free declaration: LS ELECTRIC’s letter dated 09 July 2026
Note/Remark
l The product is subject to the compliance with RINA Rules and other Standards mentioned on certificate.
l Type Approval certifies that a representative sample of the product has been found to meet the applicable design criteria.
l Any modification or change shall not be valid until approval is granted by RINA as a result of due assessment.
l Validity of this Type Approval Certificate is subject to the maintenance of a Production Quality Assurance certificate by RINA, covering the production of the type approved products.
Renewal/Revision
l 30/10/2010: initial certification. Certificate No ELE028310PU/001
l 30/10/2015: renewed without design change. New certificate No. ELE207015PU/001 revokes previous certificate
l 15/01/2021: renewed without design change. New certificate revokes previous certificate No. ELE207015PU/001
l 09/07/2026: renewed without design change. New certificate revokes previous certificate No. ELE103120PU/001