MED293826CSENGD- -  -  N- AQUATECH WMA 101 -N- S- S- -25/06/2026- Marine Equipment- - SN- S- - N-  - 151,598B2bisMarine EquipmentNumero Pratica,Direttiva,Norma,Schema,Richiesta,Validità,EmailR- MED293826CS- N-Jun 24, 2031151598
 
Form
  Marine Equipment(TO)
Certification N. MED293826CS - (ENG)
Certificate date 25/06/2026
Type Protezione antincendio
Product Sprinkler systems components for accomodation spaces, service spaces and control stations equivalent to that referred to in SOLAS 74 Regulation II-2/12 (limited to nozzles and their performance)
Item Nº MED/3.9

Model or Denomin.
Items
AQUATECH WMA 101
Applicant TEMA SISTEMI SPA
Place of requester VIA LUCIANO ROMAGNOLI N. 4  %  48026 Russi (RA)  % ITALY
Tel. N.,Fax, Email 099 4724607, 099 4724640, amm@temasistemi.com
Directive (EU) 2025/1533
Standards IMO Res A.800(19) as amended
Reference Documents Reg II-2/7, Reg II-2/9, Reg II-2/10 of SOLAS 74 as amended, IMO Res.MSC 98 (73)-(FSS Code),   IMO Res.MSC.36 (63)-(1994 HSC Code) 7, IMO Res.MSC.44 (65), IMO Res.MSC.97 (73)-(2000 HSC Code) 7,   IMO Res.MSC.98 (73) - (FSS Code) 8, IMO MSC/Circ.912, IMO MSC/Circ. 1556
Request 10/02/2026
Expire date 24/06/2031
EC TYPE-EXAMINATION (MODULE B) ENG
Vuoto Querysave
Davide Campora S

EC TYPE EXAMINATION (MODULE B)
CERTIFICATE No. MED293826CS

This is to certify that RINA Services S.p.A. (Notified Body No. 0474) did undertake the relevant type approval procedures for the equipment identified below, which was found to be in compliance with the Fire Protection requirements of Marine Equipment Directive (MED) 2014/90/EU, including the requirements and testing standards of Regulation (EU) 2025/1533.
MED Item Nº MED/3.9
Description Sprinkler systems components for accomodation spaces, service spaces and control stations equivalent to that referred to in SOLAS 74 Regulation II-2/12 (limited to nozzles and their performance)
Type AQUATECH WMA 101
Applicant TEMA SISTEMI SPA
VIA LUCIANO ROMAGNOLI N. 4,48026 Russi (RA),ITALY
Testing standards IMO Res A.800(19) as amended
Reference standards Reg II-2/7, Reg II-2/9, Reg II-2/10 of SOLAS 74 as amended, IMO Res.MSC 98 (73)-(FSS Code),   IMO Res.MSC.36 (63)-(1994 HSC Code) 7, IMO Res.MSC.44 (65), IMO Res.MSC.97 (73)-(2000 HSC Code) 7,   IMO Res.MSC.98 (73) - (FSS Code) 8, IMO MSC/Circ.912, IMO MSC/Circ. 1556
Issued in Genoa on
This Certificate is valid until
June 25, 2026
June 24, 2031
This Certificate consists of this sheet plus an attachment

________________________________________
Fabio Morbioni
RINA Services S.p.A.
**** NOTICE: This is NOT an official certificate ****

ATTACHMENT TO
CERTIFICATE No.  MED293826CS
Page 1 of 3

System Components


The water mist system is composed of stand-by pump, high pressure pumps, dedicated fresh water tank, stainless steel piping, section valves, filters, check valves, shut-off valves, control and monitoring system and AQUATECH WMA 101 nozzles as described in the System manual. Nozzles are also available in nickel coated version. Only the nozzles are type approved by this certificate. Other components are to be approved and/or certified on a case by case basis, as requested by the applicable rules.

Technical characteristics

The AQUATECH WMA 101 nozzles are made of a brass body and stainless steel components, e.g. filter, with a fast response frangible glass bulb type with nominal release temperature of 57°C (orange). The nozzle is also available in coated version with nichel coating. Bulbs with temperature ratings above 57° C, but not more than 30° C above ambient temperature are to be approved on a case by case basis.
Flow constant K

Average water flow
(lpm)
Working pressure
(bar)
1.0 at 100 bar
10
100 (nominal)
90-110 (min-max)
Acceptance conditions
Nozzles are to be installed in a pendant position in accordance with table 1, appendix 2 of IMO Res. MSC.265(84).
Application
Max spacing
Max distance from bulkheads
Cabins up to 12 m²
2 m(c)
1.5 m
Corridor (a)
3 m
centred
Public space
(ceiling up to 2.5 m)
2 m
1 m
Public space (b)
(ceiling up to 5.0 m)
2 m
1 m
Shopping and storage areas
1.5 m
0.75 m
Note:
a) Maximum width of corridor: 1.5 m
b) Ceiling height of more than 5 m is to be evaluated on a case by case basis
c) In case of 2 or more nozzles installed.
ATTACHMENT TO
CERTIFICATE Nr. MED293826CS
Page 2 of 3


Field of application

Accommodation spaces, public spaces, and other service areas, including control stations, corridors and staircases, shopping and storage areas of conventional ships and high speed craft.


Reference documents
  • Aquatech WMA 101 Nozzle is represented on Tema Sistemi drawing "TSG WMA 101 rev.4" approved with no. CSST-26434.
  • Tema Sistemi system manual and typical installation diagram are filed with no. CSST-9186 and CSST-9187.
Tests carried out
  • Fire tests as per Tema Sistemi test reports TS/WMA101/01/06, TS/WMA101/02/07, TS/WMA101/03/07 and TS/WMA101/03/07-1 filed with no. CSST-9188, CSST-9189, CSST-9190 and CSST-9191.
  • Functional and mechanical tests as per Tesi test report 189/C filed with no. CSST-9192.
  • Vibration test as per test report 2010TA28 filed with no. CSST-9193.
  • Droplet size test as per test report 2010MI0195 filed with no. CSST-9194.
  • Fire tests as per Tema Sistemi test reports TS/WMA101/01/15 filed with no. CSST-13960
  • Test Report n° TS/WM/01/21 issued by Brand technology filed with n° CSST 19035.
  • Test Report n° TS/WMA101/26 issued by Brand technology filed with n° CSST 26439.




ATTACHMENT TO
CERTIFICATE No. MED293826CS
Pages 3 of 3
The mark of conformity may only be affixed to the above type approved equipment and a Manufacturer's Declaration of Conformity issued when the production control phase module (D, E or F) of Annex II of the Directive is fully complied with a written inspection agreement with a Notified Body
XXXX/YY
"WHEELMARK FORMAT"

XXXX
Notified Body number undertaking surveillance module
YY
Last two digits of year mark affixed
     
______________________________________________
General conditions for the approval
a) The initial conditions verified by RINA at the time of the approval are to be maintained
b) Any changes to the initial conditions are to be promptly communicated to RINA, which reserves the right to repeat the relevant assessment
c) This certificate will no be valid if the manufacturer makes any changes or modifications to the approved equipment, which have not been notified to, and agreed with RINA
d) RINA personnel are to be allowed to witness during the performances of activities, upon their request
e) The activities are to be carried out in compliance with the RINA Rules and/or other applicable Rules

f) Should the specified regulations or standards be amended during the validity of this certificate, the product is to be reapproved prior to it being placed on board vessels to which the amended regulations or standards apply. 


__________________________________________
Fabio Morbioni
**** NOTICE: This is NOT an official certificate ****