The water mist system is composed of stand-by pump, high pressure pumps, dedicated fresh water tank, stainless steel piping, section valves, filters, check valves, shut-off valves, control and monitoring system and AQUATECH WMA 101 nozzles as described in the System manual. Nozzles are also available in nickel coated version. Only the nozzles are type approved by this certificate. Other components are to be approved and/or certified on a case by case basis, as requested by the applicable rules.
Technical characteristics
The AQUATECH WMA 101 nozzles are made of a brass body and stainless steel components, e.g. filter, with a fast response frangible glass bulb type with nominal release temperature of 57°C (orange). The nozzle is also available in coated version with nichel coating. Bulbs with temperature ratings above 57° C, but not more than 30° C above ambient temperature are to be approved on a case by case basis.
Flow constant K

| Average water flow
(lpm) | Working pressure
(bar) |
1.0 at 100 bar | 10 | 100 (nominal)
90-110 (min-max) |
Acceptance conditions |
Nozzles are to be installed in a pendant position in accordance with table 1, appendix 2 of IMO Res. MSC.265(84).
Application | Max spacing | Max distance from bulkheads |
Cabins up to 12 m² | 2 m(c) | 1.5 m |
Corridor (a) | 3 m | centred |
Public space
(ceiling up to 2.5 m) | 2 m | 1 m |
Public space (b)
(ceiling up to 5.0 m) | 2 m | 1 m |
Shopping and storage areas | 1.5 m | 0.75 m |
Note:
a) Maximum width of corridor: 1.5 m
b) Ceiling height of more than 5 m is to be evaluated on a case by case basis
c) In case of 2 or more nozzles installed. |
|

ATTACHMENT TO
CERTIFICATE Nr. MED293826CS
Page 2 of 3
Field of application
Accommodation spaces, public spaces, and other service areas, including control stations, corridors and staircases, shopping and storage areas of conventional ships and high speed craft.
Reference documents
- Aquatech WMA 101 Nozzle is represented on Tema Sistemi drawing "TSG WMA 101 rev.4" approved with no. CSST-26434.
- Tema Sistemi system manual and typical installation diagram are filed with no. CSST-9186 and CSST-9187.
Tests carried out
- Fire tests as per Tema Sistemi test reports TS/WMA101/01/06, TS/WMA101/02/07, TS/WMA101/03/07 and TS/WMA101/03/07-1 filed with no. CSST-9188, CSST-9189, CSST-9190 and CSST-9191.
- Functional and mechanical tests as per Tesi test report 189/C filed with no. CSST-9192.
- Vibration test as per test report 2010TA28 filed with no. CSST-9193.
- Droplet size test as per test report 2010MI0195 filed with no. CSST-9194.
- Fire tests as per Tema Sistemi test reports TS/WMA101/01/15 filed with no. CSST-13960
- Test Report n° TS/WM/01/21 issued by Brand technology filed with n° CSST 19035.