Round and rectangular fire dampers fixed to the coaming, welded to a deck and to a bulkhead, by a flange with M8 mm diameter steel bolts and 20 mm thick ceramic fiber was padded. The fire dumper frame is composed of steel plate whereas the blades are composed of an hollow profile made by a carbon steel plate on both sides; the blades are filled with ceramic fiber with a density of 96 kg/m3 (certified non-combustible in compliance with IMO FTP Code). The dumpers named CF and CFD are fitted with a set of manual actuator; the dumpers named CFE and CFED are fitted with a set of electric actuator; the dumpers named CFP and CFPD are fitted with a set of pneumatic actuator. See following table for details.
The coaming, the damper installed on the bulkhead (including the actuator) are insulated with two layers of ceramic fiber having density of 96 kg/m3 and thickness of 20 mm, (certified non-combustible in compliance with IMO FTP Code); the coaming, the dumper installed on the deck (including the actuator) are installed with three layers of ceramic fiber having density of 96 kg/m3 and thickness of 20 mm, (certified non-combustible in compliance with IMO FTP Code). The ceramic fiber, fixed by means of steel pins and washers, is applied up to 50 mm away from the unexposed side end of the coaming.
Field of application Fire resistant A-15 Class fire dampers fitted on decks and bulkheads as per the following table:
DECK |
Item | Max Dim. mm | Max
Vent. Size
mm | Frame -
Flange thick mm | Blade height
mm | Blade Composition
mm | Actuator
Type |
CFD DN400 | D: 500 | D: 400 | 5 - 5 mm | 161-166 | 5+23+2 | Manual |
BULKHEAD |
Item | Max Dim. mm | Max
Vent. Size
mm | Frame -
Flange thick mm | Blade height
mm | Blade Composition
mm | Actuator
Type |
CFE DN400 | D:500 | D:400 | 5 - 5 mm | 394 | 5+23+2 | Electric |
|
ATTACHMENT TO
CERTIFICATE Nr. MED416425CS
Page 2 of 4 |
Fire resistant A-30 Class fire dampers fitted on decks and bulkheads as per the following table:
DECK |
Item | Max Dim. mm | Max
Vent. Size
mm | Frame -
Flange thick mm | Blade height
mm | Blade Composition
mm | Actuator
Type |
CF 250x120 | 330x200 | 250x120 | 4 - 4 mm | 117 | 1+22+1 | Manual |
CFE 250x480 | 330x560 | 250x480 | 5 - 5 mm | 240 | 1+22+1 | Electric |
CFP 250x1120 | 350x1200 | 250x1120 | 6 - 6 mm | 240 | 1+22+1 | Pneumatic |
CFED 300x930 | 380x1100 | 300x930 | 6 - 6 mm | 150 | 1+22+1 | Electric |
CFD 1650x1600 | 1750x1700 | 1650x1600 | 8 - 8 mm | 177-197 | 1+22+1 | Manual |
CFPD DN1600 | D:1760 | D:1600 | 12 - 12 mm | 223-219 | 5+23+2 | Pneumatic |
BULKHEAD |
Item | Max Dim. mm | Max
Vent. Size
mm | Frame -
Flange thick mm | Blade height
mm | Blade Composition
mm | Actuator
Type |
CF 250x120 | 330x200 | 250x120 | 4 - 4 mm | 117 | 1+22+1 | Manual |
CFD 200x650 | 730x280 | 650x200 | 6 - 6 mm | 197 | 1+22+1 | Manual |
CFPD 1650x1200 | 1750x1300 | 1650x1200 | 8 - 8 mm | 182-202 | 1+22+1 | Pneumatic |
CFED DN600 | D:700 | D:600 | 8 - 8 mm | 227-232 | 5+23+2 | Electric |
Fire resistant A-60 Class fire dampers fitted on decks and bulkheads as per the following table:
DECK |
Item | Max Dim. mm | Max
Vent. Size
mm | Frame -
Flange thick mm | Blade height
mm | Blade Composition
mm | Actuator
Type |
CFPD 1650x1200 | 1750x1300 | 1650x1200 | 8 - 8 mm | 182-202 | 1+22+1 | Pneumatic |
CF DN200 | D:280 | D:200 | 4 - 4 mm | 194 | 5+23+2 | Manual |
CFE DN400 | D:500 | D:400 | 5 - 5 mm | 394 | 5+23+2 | Electric |
CFP DN450 | D:550 | D:450 | 6 - 6 mm | 444 | 5+23+2 | Pneumatic |
CFED DN800 | D:900 | D:800 | 8 - 8 mm | 195-200 | 5+23+2 | Electric |
|
ATTACHMENT TO
CERTIFICATE Nr. MED416425CS
Page 3 of 4 |
BULKHEAD |
Item | Max Dim. mm | Max
Vent. Size
mm | Frame -
Flange thick mm | Blade height
mm | Blade Composition
mm | Actuator
Type |
CFE 250x480 | 330x560 | 250x480 | 5 - 5 mm | 240 | 1+22+1 | Electric |
CFP 250x1120 | 350x1200 | 250x1120 | 6 - 6 mm | 240 | 1+22+1 | Pneumatic |
CFED 300x930 | 380x1010 | 300x930 | 6 - 6 mm | 150 | 1+22+1 | Electric |
CF DN200 | D:280 | D:200 | 4 - 4 mm | 194 | 5+23+2 | Manual |
CFD DN400 | D:500 | D:400 | 5 - 5 mm | 161-166 | 5+23+2 | Manual |
CFP DN450 | D:550 | D:450 | 6 - 6 mm | 444 | 5+23+2 | Pneumatic |
CFPD DN800 | D:900 | D:800 | 8 - 8 mm | 195-200 | 5+23+2 | Pneumatic |
Reference documents Drawings enclosed to FEFTC, Far East Fire Testing Centre, Report No. FT19013 dated 25 February 2019, Report No. FT19014 dated 25 February 2019, Report No. FT19015 dated 12 March 2019, Report No. FT19016 dated 3 March 2019, Report No. FT19017 dated 14 March 2019, Report No. FT19018 dated 25 February 2019,
Tests carried out Tests as per FEFTC, Far East Fire Testing Centre, Report No. FT19013 dated 25 February 2019, Report No. FT19014 dated 25 February 2019, Report No. FT19015 dated 12 March 2019, Report No. FT19016 dated 3 March 2019, Report No. FT19017 dated 14 March 2019, Report No. FT19018 dated 25 February 2019, according to IMO 2010 FTP Code Part. 3 - Annex 1. |