General description:
The HTV Range of Trace Heating Units is of the parallel circuit self-regulating type, rated at 190 up to 277 V
with power output up to 88W/m. The units have a maximum self-limiting temperature of 260°C.
Each trace heating units comprises:
- The active heating cable
- An end seal for terminating the remote end of the unit
- A cable gland for connecting the powered end of the unit to a suitable terminal enclosure , or alternative integrated power connection system.
The active heating cable comprises two stranded copper conductors around which is extruded a semi-conductive core material. This core material increases in resistance with increasing temperature and gives the cable its self-limiting property. The core is covered with an extruded layer of modified polyolefin insulation before being overbraided with tinned copper. A further layer of polyolefin or fluoropolymer is extruded over the braid.
The declared maximum withstand temperature for the range is 260°C and the minimum installation temperature is -60°C.
Cable Accessories:
END SEALS
The end seals for terminating the remote end of the unit may be the following types:
-Type E-100-L-x or E-100-x, which are mechanical end seal incorporating an end cap which is filled with silicone grease sealant
-Type E-40, which comprises heat shrink sleeves lined with hot melt adhesive
-Type E-150 mechanical end seals
SPLICES AND JOINT
The following splicing and jointing arrangement are provided
- A Raychem Type S-40 heat shrink splice kit for connecting lengths of active heating cable.
- A Raychem T-100 tee connection system
- Type S-150 mechanical splice kit
POWER CONNECTION
Power connection may be achieved by the following means:
-Types C25-21. The kits may use a molded silicone rubber core seal to insulate the bus wires with silicone grease in a molded cavity to seal the end of the heating cable. In this arrangement the kit Type C25-100
-C25-100-Metal-NP, C25-100-Metal-SS, C3/4-100-Metal, C3/4-100-Metal-NP, C3/4-100-Metal-SS and C75-100-A, which incorporate a type E8XF metallic cable gland
-Type C-150 power connector
-Type JBS-100 power connection system for a single heater cable
-Type JBM-100 power connection system for multiple heater cables
-Type JBU-100 power connection system
-Type CCON connection kit
TYPE APPROVAL CERTIFICATE
No. ELE052224XG/002
Enclosure - Page 2 of 2
HTV
Special Conditions for Safe Use:
The following limiting temperatures for the end seals , splices and power connections shall not be exceeded:
250°C for JBU-100 ; 200°C for E-40 and S-40 ; 151°C for the E-100-x, E-100-L-x and JBS-100;
155°C for the JBM-100 and T100; 110°C for the GHG 960 923 P … cable glands and CCON
180° for the type E8XF cable gland; 150°C for the E-150, S-150 and C-150 ;
The E-100-x, E-100-L-x, JBM-100, JBS-100 and T-100 have limiting temperatures based on internal component in these accessories. When located on pipe or other work piece surface, a maximum pipe temperature of 215°C will not cause the limiting temperatures of 151°C or 155°C to be exceeded.
The end seal, splices and power connections have the following associated minimum ambient temperatures:
-60°C for the E-40, S-40 and CCON ;
-50°C for the E-100, E-150, S-150, C-150, JBS-100, JBU-100 and JBM-100 _
-40°C for the JBS-100-L, JBM-100-L, T100, JBU-100-L, E-100-L
-55°C for the C25-100, C25-21 and CCON
-60°C for the C25-100-Metal, C25-100-Metal-NP, C25-100-Metal-SS, C3/4-100-Metal, C3/4-100-Metal-NP, C3/4-100-Metal-SS
Minimum bending radius is 12,7 mm for the type HTV units.
Thermal output rating: 9 to 90 W/m at 10° C and 230 V.
Reference documents:
- ATEX Certificate
Certification Authority: PTB, Bundesallee 100, 38116 Braunschweig, Germany
Certificates: PTB 21 ATEX 1003 X, Issue: 3
Marking:
II 2 G Ex eb mb 60079-30-1 IIC T6...T2 Gb or
II 2 D Ex tb 60079-30-1 IIIC T85° C...T215° C Db
Safety Standard:
EN60079-0: 2018 ; EN60079-7:2015+A1:2018 ; EN60079-18:2015+Cor.2018 ; EN60079-30-1:2017
EN60079-21:2014
- Data sheet: EN – Raychem-DS-EU1750+HTV-EN
Remarks:
The Information listed in the present certificate are partial information based on the Baseefa Certificates.
The component listed in this Certificate are to be used / installed according to the manufacturer instructions:
Special conditions for safe use and installation to be in accordance with the above referenced ATEX Certificates.
The certificate supersedes previous RINA certificate No. ELE065119XG/002 |
|