MD9908 Automatic, Addressable, Analogue heat detector :
Main features:
MD 9908 detector consists of two parts:
- The sensor, (IP67) to be installed in the room to be monitored
- The Loop Interface Box, (IP 66) also includes short circuit isolator and LED Fire signaling
(to be mounted outside of the monitored space)
Sensors and Interface box are connected each other with a 30 meters maximum length cable
- Fire alarm for high temperature
- Monitoring of the temperature inside the room where it is installed
- Send to the Central Unit the temperature analogue values
- Short circuit isolator functionality
MD9908 IP66 Loop interface and IP 67 Heat detector F Class; Alarm threshold: 129°C to +145°C
The detector continuously monitors the thermistor component and is able to provide a fault signalization in case of sensor failure.
The communication through the loop with Central Unit is performed by control cards, which provide to the detectors
the 24Vdc power supply on which a serial transmission signal using MD2 protocol is modulated
If an alarm is detected an optical signalization (red LED) on the Interface Box housing flashes.
Microdata Due specifications:
Technical Specification: ELET/44862 ST36605 rev. B
Datasheet: ELET/44863 D35545 rev. D
Software description: ELET/44837 SDD36634 rev. 0
Risk Assessment: ELET/44865 D36691 rev. 0
Test Reports:
BRE GLOBAL Ltd Test Report n. TE-P103830-1001 rev. 02 (RINA Id. ELET/44799)
TesLab No:
- 166117E-d (05/09/2016 - RINA Id. ELET/44805) (RINA Rules – Pt C, Ch 3, Sec 8)
- 17B302E-b RINA Id. ELET/44795 - EMC _ EN60092-504: 2016
Note: Technical equivalence with EN 54-5:2017+A1:2018 is considered demonstrated based on the original EN 54-5:2000+A1:2002 test reports and supplementary EMC testing performed according to the updated requirements reported in the Test Report TesLab No. 17B302E-b.