'FK 5-1-12 Fixed fire suppression system' is used for equivalent fixed gas fire extinguishing systems components (extinguishing medium, head valves and nozzles) for machinery spaces and cargo pump rooms.
Extinguishing agent:
| Trade name | Noah® 5112 |
| Designation | FK-5-1-12 - CF₃CF₂C(O)CF(CF₃)₂ |
| Manufacturer | Zhejiang Noah Fluorochemical Co., Ltd |
| Minimum design concentration | 6.64 % |
| NOAEL | 10.0 % |
| LOAEL | >10.0 % |
| Cylinder capacity | 140 L |
| Storage pressure | 42 bars at 21°C |
| Assembly cylinder position | Vertical only |
Discharge nozzle:
| Material | Bronze |
| Size | 40 A (360°) |
| Min. pressure | 4.0 bar |
| Weight | 0.62 kg |
Cylinder valve:
| Material | Forged Brass, Ni-Coated |
| Cylinder connection | 2 - 1/2 - 8 NPT |
| Working pressure | 7.0 MPa |
| Weight | Approx. 4.2 kg |
 | ATTACHMENT TO
CERTIFICATE No. MED188925PU
Page 2 of 3 |
Technical Documentation
- Technical drawings and Manual, filed by RINA listed on Letter No. PUFP/2025/491/YK008.
Tests Carried out
- Test report of Fire & Full capacity discharge test (Ref. No. NK-FK-001), witnessed by RINA dated on 21-11-2025, filed by RINA with No. PUFP-8029.
- Test report of Fire test (Ref. No. R2024-0451 & R2024-0451R1), issued by Fire Insurers Laboratories of Korea dated from 02-09-2024 to 05-09-2024, witnessed by DNV, filed by RINA with No. PUFP-8030.
- Test report of Fire test (Ref. No. 2025-0142), issued by Fire Insurers Laboratories of Korea dated from 31-03-2025 to 01-04-2025, witnessed by DNV, filed by RINA with No. PUFP-8031.
- Test report of Gas sampling (Ref. No. TBK-2025-014745), issued by Korea Testing & Research Institute dated on 05-12-2025, filed by RINA with No. PUFP-8032.
Application/Limitation
- Instruction for installation, use and maintenance are to be available in the ship's official languages.
- The onboard arrangements, installation of this equipment and other system components are to be evaluated in each case, to the satisfaction of the classification society on board or the flag administration.
- The system should be suitably designed to withstand ambient temperature changes, vibration, humidity, shock, impact, clogging, and corrosion normally encountered in machinery spaces or cargo pump rooms in ships.
- The extinguishing system should be installed according to the manufacturer's design and installation instructions. The maximum vertical distance should be limited to 5 m.
Note
|