Product Description
Manual Motor Starter type MS132-0.16/-0.25/-0.4/-0.63/-1/-1.6/-2.5/-4/-6.3/-10/-12/-16/-20/-25/-32 (optional followed by K) with
thermal and magnetic overcurrent protection and type MO132-0.16/-0.25/-0.4/-0.63/-1/-1.6/-2.5/-4/-6.3/-10/-16/-20/-25/-32 with
magnetic overcurrent protection only and auxiliary contacts.
Technical Data
- Number of poles: 3.
- Rated frequency: 50/60 Hz.
- Rated operational voltage (Ue):230V up to 690V.
- Rated insulation voltage (Ui): 690V.
- Rated current (In): 0.1A up to 32A.
- Utilization Category according to IEC 60947-2: A.
- Utilization Category according to IEC 60947-4-1: AC-3.
- Rated short-circuit capacity:
Rated service short circuit breaking capacity (Ics)
Rated ultimate short circuit breaking capacity (Icu)
Rated short circuit making capacity (Icm) (**)
Ue (V) | In | Ics (kA) | Icu (kA) |
230 | 0.1A-10A
8A-25A
25A-32A | 100
50
25 | 100
50
25 |
400 | 0.1A -10A
8A-25A
25A-32A | 100
50
25 | 100
50
25 |
440 | 0.1A-2.5A
2.5A-32A | 100
3 | 100
3 |
500 | 0.1A-2.5A
2.5A-32A | 100
3 | 100
3 |
690 | 0.1A-2.5A
2.5A-32A | 100
3 | 100
3 |
(**) Icm (kA) according to Standard IEC 60947-2, Tab. 2.
TYPE APPROVAL CERTIFICATE |
No. ELE410625XG |
Enclosure - Page 2 of 3 |
MS132; MO132
|
Auxiliary contacts
- UA1 Undervoltage release
- AA1 Shunt release
- HKF1-11, HKF1-11K, HKF1-20, HKF1-20K Auxiliary switch for front mounting:
Rated insulation voltage (Ui): 250V.
Rated impulse withstand voltage (Uimp): 6kV.
Conventional free air thermal current (Ith): 5A.
Utilization Category: AC-15 & DC-13.
HKF1-xx(K)
Ue (V) | AC-15 | DC-13 |
24 | 3A | 1A |
120 | 3A |
|
125 |
| 0.27A |
240 | 1.5A |
|
250 |
| 0.15A |
- HK.-.. Auxiliary switches for lateral mounting (at right)
HK1-11(K)
HK1-20(K)
HK1-20L (with lead contacts)
HK1-02(K)
- SK.-..Signaling contacts for lateral mounting
SK1-11(K)
SK1-20(K)
SK1-02(K)
- CK.-. Short-circuit signaling contacts for lateral mounting
CK1-11
CK1-20
CK1-02
- Rated insulation voltage (Ui): 690V.
- Rated impulse withstand voltage (Uimp): 6kV.
- Conventional free air thermal current (Ith): 6A.
- Utilization Category: AC-15 & DC-13.
HK1-xx(K); HK1-20L; SK1-xx(K); CK1-xx
Ue (V) | AC-15 | DC-13 |
24 | 6A | 2A |
120 | 6A |
|
125 |
| 0.55A |
240 | 4A |
|
250 |
| 0.27A |
400 | 3A |
|
600 |
| 0.15A |
690 | 1A |
|
TYPE APPROVAL CERTIFICATE |
No. ELE410625XG |
Enclosure - Page 3 of 3 |
MS132; MO132
|
Additional Place of Manufacture
ABB Xinhui Low Voltage Switchgear Co., Ltd.
Jinguzhou Industrial Development Zone
Xinhui district, Jiangmen City
Guangdong Province, China
Documents
- CB Test Certificate n° BE-2013 issued on 15.07.2009 (KEMA Test Reports from n° 58495802/00 up to 58495802/12 issued on 13.07.2009).
- CB Test Certificate n° BE-2012 issued on 15.07.2009 (KEMA Test Reports from n° 58495801/00 up to 58495801/15 issued on13.07.2009).
- CB Test Certificate n° NL-16564-A1 issued on 10.08.2009 (KEMA Test Report n° 2122927.53 issued on 20.07.2009).
- CB Test Certificate n° NL-16563-A1 issued on 10.08.2009 (KEMA Test Report n° 2122927.52 issued on 20.07.2009).
- PACONSULT Test Report n° 09-2475A issued on 27.05.2009.
- LOVAG Test Report n° AN 07/2002 issued on 14.02.2002.
- Data Sheet for Manual Motor Starter MS 132: Document number 2CDC 131 021 D0202 (08.2014)
Remarks
The product is subject to the compliance with Tab.1 of RINA Rules for the Classification of Ships Pt.C, Ch.3, Sec.8, where applicable,
and with the Standards mentioned on the Certificate.
This certificate annuls and replaces the previous one n° ELE121819XG/001. |
|