ELE381326CS!004ENG- -  -  N- MD9908 -N- S- S- -21/06/2026- Prodotti Elettrici- - SN- N- - N-  - 840,487BbisProdotti ElettriciNumero Pratica,NumDich,Norma,NumBusta,Richiesta,Validità- ELE381326CS/004- N-Jun 21, 2031840487
 
Form
  Prodotti Elettrici(TO)
Certification N. ELE381326CS/004 - (ENG)
Certificate date 21/06/2026
Type Impianti di Automazione
Product Fixed fire detection and fire alarm systems : Heat detector including Short circuit isolator

Model or Denomin.
Items
MD9908
Applicant MICRODATA DUE SRL
Place of requester Via Greti Del Vara 9 , 19020 Follo, La Spezia % ITALY
Tel. N.,Fax, Email 0187 599101, 0187 558983, C.RUFFINI@MICRODATASRL.IT
Standards RINA Rules for the Classification of Ships - Part C- Machinery, Systems and Fire Protection - Ch.3 , Sect. 8, Table 1
Envelope N. 9090 H
Expire date 21/06/2031
Interrut.senza Dettaglio ENG
Vuoto Querysave
S
TYPE APPROVAL CERTIFICATE
No. ELE381326CS004              
This is to certify that the product below is found to be in compliance with the applicable requirement of the RINA type approval system.

Description
Type MD9908
Applicant MICRODATA DUE SRL
Via Greti Del Vara 9 , 19020 Follo, La Spezia
ITALY
Reference standards Rules for the Classification of Ships Part C - Machinery Systems and Fire Protection,Ch. 3, Sec. 8, Table 1, EN 54-5:2017 incl. A1:2018, EN 54-17 (2005) including AC(2007), IEC 60092-504:2016,IEC 60533:(2015)
  

 
 
   .   This Certificate is valid until June 21, 2031
_________________________________
RINA Services S.p.A.
Sumit Kumar Paul
This certificate consists of this page and 1 enclosure
**** NOTICE: This is NOT an official certificate ****

TYPE APPROVAL CERTIFICATE
No. ELE381326CS004              
Enclosure - Page 1 of 2
MD9908
Products description:
Series MD9908 Automatic, Addressable, Analogue heat detector:

Main features:
MD 9908 detector consists of two parts:
- The sensor, (IP67) to be installed in the room to be monitored
- The Loop Interface Box, (IP 66) also includes short circuit isolator and LED Fire signaling (to be mounted outside of the monitored space) Sensors and Interface box are connected each other with a 30 meters maximum length cable
- Fire alarm for high temperature
- Monitoring of the temperature inside the room where it is installed
- Send to the Central Unit the temperature analogue values
- Short circuit isolator functionality

MD9908 IP66 Loop interface and IP 67 Heat detector F Class; Alarm threshold: 129°C to +145°C
The detector continuously monitors the thermistor component and is able to provide a fault signalization in case of sensor failure.
The communication through the loop with Central Unit is performed by control cards, which provide to the detectors
the 24Vdc power supply on which a serial transmission signal using MD2 protocol is modulated
If an alarm is detected an optical signalization (red LED) on the Interface Box housing flashes.

Microdata Due specifications:
Technical Specification: ELET/44862 ST36605 rev. B
Datasheet: ELET/44863 D35545 rev. D
Software description: ELET/44837 SDD36634 rev. 0
Risk Assessment: ELET/44865 D36691 rev. 0

Test Reports:
BRE GLOBAL Ltd Test Report n. TE-P103830-1001 rev. 02 (RINA Id. ELET/44799)

TesLab No:
- 166117E-d (05/09/2016 - RINA Id. ELET/44805) (RINA Rules – Pt C, Ch 3, Sec 8)
- 17B302E-b RINA Id. ELET/44795 - EMC _ EN60092-504: 2016

Note: Technical equivalence with EN 54-5:2017+A1:2018 is considered demonstrated based on the original EN 54-5:2000+A1:2002 test reports and supplementary EMC testing performed according to the updated requirements reported in the Test Report TesLab No. 17B302E-b.


Flame addressable interface board p.n. FD-PP

The FD-PP board is a gateway designed to interface Microdata Due MD99xx-series detector with the Consilium system. It communicates with the Microdata detector using the same physical layer and protocol as Microdata systems, then converts and makes this information available to the Consilium system using the appropriate physical layer and Consilium protocol.
The FD-PP board PN 28063 is an interface board that included a short circuit isolator.
The FD-PP board will be used in conjunction with the heat detectors made by Microdata Due model MD9907-A1/B/ C – PN 29261-A1 /B/C




TYPE APPROVAL CERTIFICATE
No. ELE381326CS004
Enclosure - Page 2 of 2
MD9908




Microdata Due specifications:
Technical Specification: ELET/44862 ST36605 rev. B
Datasheet: ELET/44863 D35545 rev. D
Software description: ELET/44837 SDD36634 rev. 0
FD-PP Software Assessment ELET/45068 D37779 Rev. 0
Risk Assessment: ELET/44865 D36691 rev. 0
FD-PP-B Board dwg. ELET/45063 AS-28063-20001
FD-PP Board Assembly dwg. ELET/45064 AS-28063-20002
FD-PP Part List ELET/45065 AS-28063-20003
FD-PP Board PCB dimension ELET/45066 PC-28064-10015
FD-PP Board Label ELET/45067 ME-29035


Test Reports:

BRE GLOBAL Ltd Test Report n. TE-P103830-1001 rev. 02 (RINA Id. ELET/44799)

TesLab No:

- 166117E-d (05/09/2016 - RINA Id. ELET/44805) (RINA Rules – Pt C, Ch 3, Sec 8)
- 17B302E-b RINA Id. ELET/44795 - EMC _ EN60092-504: 2016 2
- 172048F-a (22/08/2017 - RINA Id. ELET/45070); FD-PP; UNI-EN 54-17
- 17B295E (22/11/2017 - RINA Id. ELET/45071); FD-PP; EN 60092-504 EMC


Remarks:

Offer No. 2026/22430 - Job: RS/2026/CS/01/3813
Validity of this certificate is subject to satisfactory outcome of yearly audit as per RINA "Rules for Testing and Certification of Marine Materials and Equipment".
Initial Audit carried out at the production site; Date: 25/09/2026
The documents above mentioned have been archived in the Leonardo Draw Plus portal under the project:
https://leodrawplus.rina.org/projects/80469/detail


Genoa June 21, 2026
**** NOTICE: This is NOT an official certificate ****