Technical Characteristics
FOAM CONCENTRATE SF-2%HEF |
Type of Foam Concentrate | Concentrate for fixed high expansion foam fire extinguishing system
for machinery spaces and cargo pump rooms |
Mixing Ratio | 2 : 98 |
Density (Volume Mass) at 20 ºC | 1.00 ~ 1.20 g/cm3 |
pH at 20ºC | 6.0 ~ 9.5 |
Kinematic Viscosity at 20 ºC | ≤ 200 mm2/s |
Max. Continuous Storage Temperature | 50 ºC |
Lowest Use Temperature | - 7 ºC |
Sedimentation | ≤ 0.25% |
Pour Point | - 12 ºC |
Expansion Ratio at 20 ºC | ≥ 600 *
662 ** |
*) Data from Technical Specification.
**) Data from Initial Test, when tested with seawater and IMO MSC/Circ.670 test apparatus. |
Field of Application
Foam concentrate SF-2%HEF is with no intentionally added PFOS (perfluorooctane sulfonic acid).
This approval does not address the foam generating equipment, only the foam concentrate for fixed high expansion foam fire extinguishing systems for machinery spaces and cargo pump rooms, and for mobile fire extinguishing systems, according to IMO MSC/Circ.670.
Technical Documentation
Technical Specification (SF-2%HEF) approved by RINA with No.: SHFP-10280.
 | ATTACHMENT TO
CERTIFICATE No. MED393526WS
Page 2 of 3 |
Tests Carried Out
According to IMO MSC/Circ.670 - "Guidelines for The Performance and Testing Criteria and Surveys of High-expansion Foam Concentrates for Fixed Fire-extinguishing Systems", Test Report (Ref No.: SL-2016-1213) issued by Jiangsu Suolong Fire Science and Technology Co.,Ltd, witnessed and filed by RINA with No.: SHFP-10277.
Routing Test Report (Ref. No.: ZY-11680/11682) issued by Jiangsu Suolong Fire Science and Technology Co.,Ltd, witnessed and filed by RINA with No.: SHFP-19942;
Test Report (PFOS) (Ref. No.:TAOEC25004136801) issued by SGS-CSTC Standards Technical Services (Qingdao) Co., Ltd, and filed by RINA with No.: SHFP-37567.
Remarks
The storage facilities and piping arrangement onboard the vessel are to be designed and constructed with regard to seawater exposure (where applicable), and the minimum allowed temperature for the foam liquid.
Each product is to be supplied with its manual for installation, use and maintenance. This shall include requirements for transport and storage, material of foam tank, coating (if applicable) and cleaning procedures.
Periodical controls of foam concentrates stored on board:
The foam liquid is to be delivered with a declaration of the main characteristics (sedimentation, pH-value, expansion ratio, drainage time, volumetric mass and date of production. The declaration will be the basis for the annual condition test (each year after 3 years).
Notes
Renewal of Previous EC Type Examination (Module B) Certificate No.: MED057422WS/001 dated 04/24/2022.
As declared, the initial conditions at the time of the approval are maintained.