MED345024CS!003ENGD- -  -  N- CF II-Q-J/D -N- S- S- -26/07/2024- Marine Equipment- - SN- S- - N-  - 1,082,438B2bisMarine EquipmentNumero Pratica,Direttiva,Norma,Schema,Richiesta,Validità,EmailR- MED345024CS/003- N-Jul 25, 20291082438
 
Form
  Marine Equipment(TO)
MED365024WS/003
Certification N. MED345024CS/003 - (ENG)
Certificate date 26/07/2024
Type Protezione antincendio
Product Sbarramenti antincendio
Item Nº MED/3.22
USCG Category N° 164.139

Model
Items/Sizes
CF II-Q-J/D
Applicant TAIXING TRAFFIC MACHINERY FACILITIES FACTORY
Place of requester No. 166, Gensi West Road, City District Industrial Park, Taixing City  Jiangsu Province Taixing (Jiangsu)  % CHINA
Tel. N.,Fax, Email 13951172142, 0523-87593309, 13951172142@139.com
Directive (EU) 2023/1667
Standard IMO Res. MSC.307(88)-(2010 FTP Code)
Reference Documents Chap. II-2 of SOLAS 74 Convention, as amended, RINA Rules for the certification of Marine Equipment
Request 28/06/2024
Validity 25/07/2029
EC TYPE-EXAMINATION (MODULE B) ENG
Vuoto Querysave
Enrico Cabella S

EC TYPE EXAMINATION (MODULE B)
CERTIFICATE No. MED345024CS/003

This is to certify that RINA Services S.p.A. (Notified Body No. 0474) did undertake the relevant type approval procedures for the equipment identified below, which was found to be in compliance with the Fire Protection requirements of Marine Equipment Directive (MED) 2014/90/EU, including the requirements and testing standards of Regulation (EU) 2023/1667.
MED Item Nº MED/3.22
USCG Category Nº 164.139
Description Fire dampers
Type CF II-Q-J/D
Applicant TAIXING TRAFFIC MACHINERY FACILITIES FACTORY
No. 166, Gensi West Road, City District Industrial Park, Taixing City Jiangsu Province Taixing (Jiangsu),CHINA
Testing standards IMO Res. MSC.307(88)-(2010 FTP Code)
Reference standards Chap. II-2 of SOLAS 74 Convention, as amended, RINA Rules for the certification of Marine Equipment
Issued in Genoa on
This Certificate is valid until
July 26, 2024
July 25, 2029
This Certificate consists of this sheet plus an attachment

________________________________________
Enrico Cabella
RINA Services S.p.A.
**** NOTICE: This is NOT an official certificate ****

ATTACHMENT TO
CERTIFICATE No.  MED345024CS/003
Page 1 of 2

Product description

Rectangular pneumatic fire dampers named CF II-Q-J/D fixed to the coaming, welded to a deck and to a bulkhead, by a flange with M12 mm diameter steel bolts and 5 mm thick ceramic fiber was padded. The fire dumper frame is composed of 8 mm thick steel plate whereas the blades, having width of 43 mm, are composed of an hollow profile made by a carbon steel sheet on both sides, 1.5 mm tick. The blades are filled with 40 mm of a polycrystalline wool, named DJS, with a density of 120 kg/m3. The dumper is fitted with a set of pneumatic actuator A-125SR produced by WUXI ST.HANS CONTROLS CO., LTD; the coaming, the damper (including the actuator) are insulated with two layers of ceramic fiber having density of 170 kg/m3 and thickness of 20 mm, (certified non-combustible in compliance with IMO FTP Code). The ceramic fiber, fixed by means of steel pins and washers, is applied on the coaming, for a minimum length of 445 mm.
Field of application
Fire resistant A-60 Class fire dampers fitted on decks and bulkheads as per the following table:

DECK
Item
Max Dim. mm
Max
Vent. Size
mm
Frame -
Flange thick mm
Blade height
mm
Blade Composition
mm
Actuator
Type
CFII-Q-J/D
1300x1900
1200x1800
8 - 5 mm
235
1.5+40+1.5
Pneumatic
BULKHEAD
Item
Max Dim. mm
Max
Vent. Size
mm
Frame -
Flange thick mm
Blade height
mm
Blade Composition
mm
Actuator
Type
CFII-Q-J/D
1300x1900
1200x1800
8 - 5 mm
235
1.5+40+1.5
Pneumatic

Reference documents

Drawings enclosed to FEFTC, Far East Fire Testing Centre, Report No. FT18199 dated 18 September 2018, Report No. FT18202 dated 17 September 2018.
Tests carried out
Tests as per FEFTC, Far East Fire Testing Centre, Report No. FT18199 dated 18 September 2018, Report No. FT18202 dated 17 September 2018. according to IMO 2010 FTP Code Part. 3 - Annex 1.




ATTACHMENT TO
CERTIFICATE No. MED345024CS/003
Pages 2 of 2
The mark of conformity may only be affixed to the above type approved equipment and a Manufacturer's Declaration of Conformity issued when the production control phase module (D, E or F) of Annex II of the Directive is fully complied with a written inspection agreement with a Notified Body
XXXX/YY
"WHEELMARK FORMAT"

XXXX
Notified Body number undertaking surveillance module
YY
Last two digits of year mark affixed
     
______________________________________________
General conditions for the approval
a) The initial conditions verified by RINA at the time of the approval are to be maintained
b) Any changes to the initial conditions are to be promptly communicated to RINA, which reserves the right to repeat the relevant assessment
c) This certificate will no be valid if the manufacturer makes any changes or modifications to the approved equipment, which have not been notified to, and agreed with RINA
d) RINA personnel are to be allowed to witness during the performances of activities, upon their request
e) The activities are to be carried out in compliance with the RINA Rules and/or other applicable Rules

f) Should the specified regulations or standards be amended during the validity of this certificate, the product is to be reapproved prior to it being placed on board vessels to which the amended regulations or standards apply. 


__________________________________________
Enrico Cabella
**** NOTICE: This is NOT an official certificate ****