General Description:
The water- or air- cooled COBRA Battery System comprises a switch unit and up to eight battery modules utilizing Lithium Ferrophosphate battery cells (LFP). The system is scalable up to sixteen compact battery racks per control cabinet. Battery LFP be mounted either into the battery rack or mounting frame. Equal to a rack arrangement, each string of mounting frames is connected to a single boxed switch unit. All interfaces (HV, cooling, gassing) are accessible through the mounting frame same as in the rack arrangement.
Ratings:
|
| Cell Configuration |
|
| 35S1P* | 33S1P* |
Cell Level | Rated Capacity [Ah]: | 100 - 105 | 100 - 105 |
Nominal Voltage [V]: | 3.2 |
max Voltage [V]: | 3.65 |
min Voltage [V]: | 2.5 |
Module Level | Nominal Voltage [V]: | 112 | 105.6 |
Voltage Range [V]: | 88 - 125 | 82.9 - 117.8 |
Capacity [Ah]: | 100 - 105 | 100 - 105 |
Rack Level | Voltage Range [V]: | 248 - 1000 |
Modules in series | 3 - 8 |
System lever | Racks | 1 - 16 |
Energy [kWh]: | 89.6 - 1504 | 84.5 - 1434 |
| * The System is not limited to proposed configuration. |
Software:
COBRASense42-Master: V01
COBRASense42-Slave: V09B
Battery Management System (BMS): ID:203
Control System PLC: 2.03.00
Switch Unit (SU)
Max Current: fuse value 125 A default (60 A - 250 A)
Degree of protection: IP44 (rack version), IP66 (mounting frame)
Control Cabinet (CC)
Power supply: 24 V DC
Power consumption: 88 - 730 W (1 Rack - 16 Racks)
Connected racks: up to 16
Degree of protection: IP55
TYPE APPROVAL CERTIFICATE
No. ELE053123XG
Enclosure - Page 2 of 3
Battery System
Battery Management System (BMS) and system overview
The BMS and independent safety system consits of BMS Master, BMS Slave (Cell monitoring), COBRASense42 Master and COBRASense42 Slave.
BMS Cell Monitoring Unit (CMU)
The Slave-BMS comprises of three single board, located in the battery modules. Their purpose is to measure the status of LFP and submit the data to the BMS-Master. Each slave board can measure the voltage of up to twelve cells and records four temperatures. Each board has twelve balancing resistors, which can be individually activated by the master to achieve SOC balance on cell level.
COBRASense42 Master (CS42M)
This unit is installed in the switch box. It communicates with the COBRASense42 Slave and monitors the pilot line. Additionally, it controls the module heating.
COBRASense42 Slave (CS42S)
This unit is part of the battery module and is designed for independent safety functionality. The function of the board is to detect cell venting, redundant temperature monitoring and the module cooling liquid leakage detection. A safety line trips the main breaker in case of detected fault.
Switch Unit (SU)
The unit comprises the BMS Master, COBRASense42 Master, two power fuses and two circuit breakers.
BMS Maser Control Unit (MCU)
It creates the interface between BMS and PLC.
Control Cabinet (CC)
Each battery system (comprising of 1 to 16 racks) is connected to one control cabinet, which manages the basic system functions. Also is it the interface to the ship's system.
Remarks:
- Each particular application and installation such as electric propulsion and essential services, or for the charging/discharging of battery systems of a capacity of 50 kWh or above are to be specifically approved.
- Batteries are to be subject to functional and safety tests according to IEC Publication 62620 or in accordance with other equivalent national or international standards recognized by RINA.
- Performance tests (Factory Acceptance Test) are to be carried out on the battery system (BMS and Battery Cells) according to a test program and which is to include functional tests (alarm system, safety system, control system, etc.) and further tests resulting from the Risk Assessment at the presence of a RINA Surveyor.
- The battery system is to be used in connection with an appropriate PMS able to shut down the battery pack in case of an identified failure.
- Installation of the battery system is to be in accordance with RINA Rules for the Certification, Installation and Testing of Lithium Based Storage Batteries.
- The battery system is not to be installed on the bridge or deck zone.
- This Type Approval Certificate does not cover any Flag Administration requirements.
TYPE APPROVAL CERTIFICATE
No. ELE053123XG
Enclosure - Page 3 of 3
Battery System
Documents:
01 COBRA System Description Rev 03; 02 COBRA Functional Description Rev 03; 03 COBRA Specification Rev 05; 04 COBRA Operating and Maintenance Manual Rev 06; 05 COBRA Safety Description Rev 04; 06 COBRA Circuit Diagrams Rev 04,compl; 07 COBRA Testing Rev 03; 08 COBRA Software Change Handling Rev 05; 09 COBRA List of Hardware versions Rev 04; 20220725 COBRA Test Procedure at Manufacturer;
Test Reports:
20222807 COBRA Test,Protocols,for TA,v07; 214-22,V1U TREO IACS Tests; 269-22,V1U; 50296284 001 IEC 62619,CB,report LF105; BU-202200196-B1; DNV Propagation test, Test protocol, LFP System,Becker Marine Systems 07072022; LF105 UL1642 test report; LF105 UL9540A REPORT; MSDS LF105; 073068.227.21,Report,BMS,COBRA Battery System,V1.0; Protokoll Charge cap ret and rec 2022 fertig; Protokoll Discharge Peformance at 25C 2022 fertig; Test Procedure Endurance in Cycles 2022 fertig; Test Procedure Endurance in Storage 2022 fertig; Test Procedure Overcharge Current 62619 823,with results,rev02; Test Procedure Overcharge Voltage 62619 822,with results,rev02; Test Procedure Overheating Control 62619 824,with results,rev02; Test Protocol External Shortcircuit UN38.3 T5,v03; Test,Protocol,DC Resistance Ramp-up EVE Cell Rev-; |
|