Switch disconnectors : E2.2/ML, E4.2/ML, E6.2/ML
E2.2/ML Switch-disconnectors main features:
Method of operation: independent manual operation; independent power operation
Suitability for isolation: suitable
Number of poles: 3P, 4P
Kind of current: AC
Rated frequency: 50/60 Hz
Rated insulation voltage Ui(V): 1000V
Rated impulse withstand voltage Uimp (kV): 12 kV
Utilization category: AC-23A
Pollution degree: 3
| Models |
| E 2.2 N / MS | E 2.2 H / MS |
| Rated operational Voltage Ue | V | 440/690 |
| Conventional free air thermal Ith | A | 800,1250.1600, 2000, 2500 |
| Rated operational current Ie | A |
| Rated short-time withstand current Icw | kA | 66 kA/1s | 85 kA/1s |
| Rated short-time making capacity Icm | kA | 145 kA | 187 kA |
| Models |
| E 4.2 N / MS | E 4.2 H / MS | E 2.2 V / MS |
| Rated operational Voltage Ue | V | 440/690 |
| Conventional free air thermal Ith | A | 3200, 4000 | 2000, 2500, 3200, 4000 |
| Rated operational current Ie | A |
| Rated short-time withstand current Icw | kA | 66 kA/1s | 85 kA/1s | 100 kA/1s |
| Rated short-time making capacity Icm | kA | 145 kA | 187 kA | 220 kA |
| Models |
| E 6.2 H/MS
E 6.2 H/f/MS | E 6.2 X/MS
E 6.2 H/f/MS |
| Rated operational Voltage Ue | V | 440/690 |
| Conventional free air thermal Ith | A | 4000, 5000, 6300 |
| Rated operational current Ie | A |
| Rated short-time withstand current Icw | kA | 100 kA/1s | 120 kA/1s |
| Rated short-time making capacity Icm | kA | 220 kA | 264 kA |
Technical specifications: 1SDC007910D0201 (02-2022)
Test Reports: STIE doc. n. 00901-CB2019CQC-090388-M3 (2022-02-23)
STIE doc. n. 00901-CB2019CQC-088018 (2020-01-09)
STIE doc. n. 00901-CB2014CQC-064199 (2015-04-13)
CB Test Certificate _ China Quality certification center:
CN56272 (24/03/2022)
CN34014-A1/M1 (2016-01-22)
CN34016A1/M1 (2015-0702)
CN34040 (2015-05-08)
Reference document:
TAO-APP dated 08.11.2022
Offer n. 2022/23831 dated 16.11.2022
TAC n. ELE413117CS |
|