TS1000N/TS1000H/TS1000L/TS1250N/TS1250H/TS1600N/TS1600H
Product Description
- Moulded case circuit breaker applicable to the marine environment with following rating (amb. temp. 40℃):
Type | Rated Freq.
[Hz] | Rated Current at 45℃
In[A] | Rated Oper. Volt.
Ue[V]
50/60Hz | Service Short-circuit Breaking Capacity Ics[kA] | Ultimate
Short-circuit
Breaking Capacity
Icu[kA] | Rated
Short-circuit
Making Capacity
Icm[kA] | Rated
Short-time
Withstand
Current
Icw[kA] | Util.
Cate-gory |
TS1000N | 50/60 | 630,
800, 1000 | 660/690
480/500
440/460
380/415
220/240 | 100% Icu | 35
40
50
50
55 | 73.5
84
105
105
121 | 25 (1s) | B |
TS1000H | 50/60 | 630,
800, 1000 | 660/690
480/500
440/460
380/415
220/240 | 75% Icu | 45
50
65
70
75 | 94.5
105
143
154
165 | 25 (1s) | B |
TS1000L | 50/60 | 630,
800, 1000 | 660/690
480/500
440/460
380/415
220/240 | 100% Icu | --
100
130
150
200 | --
220
286
330
440 |
| A |
TS1250N | 50/60 | 1250 | 660/690
480/500
440/460
380/415
220/240 | 100% Icu | 35
40
50
50
55 | 73.5
84
105
105
121 | 25 (1s) | B |
TS1250H | 50/60 | 1250 | 660/690
480/500
440/460
380/415
220/240 | 75% Icu | 45
50
65
70
75 | 94.5
105
143
154
165 | 25 (1s) | B |
TS1600N | 50/60 | 1600 | 660/690
480/500
440/460
380/415
220/240 | 100% Icu | 35
40
50
50
55 | 73.5
84
105
105
121 | 25 (1s) | B |
TS1600H | 50/60 | 1600 | 660/690
480/500
440/460
380/415
220/240 | 75% Icu | 45
50
65
70
75 | 94.5
105
143
154
165 | 25 (1s) | B |
*Note : OCR – electronic type overcurrent trip unit, Pole – 3P (327H x 210W x 152.5D), 4P (327H x 280W x 152.5D)
Reference Documents
DEKRA CB scheme Test Report No. 2168756.70 dated 26 January 2015, No. 2168756.71 dated 26 January 2015,
No. 2131728.51 dated 19 April 2011, No. NL-20335/A1 dated 28 January 2015
ENV & EMC Test: PT&T Test Report No. R415-2504 and No. R415-2506 dated 21 December 2015, No. R415-2505 and No. R415-2507 dated 16 December 2015, Chungbuk Technopark Test Report No. CBTP-15C-0037 and No. CBTP-15C-0038 dated 22 December 2015
Renewal Test (Visual Inspection & Function Test): PT&T Report No. R426-0257 dated 08 April 2026
Asbestos-free Declaration (SOLAS II-1/reg.3-5): LSIS letter dated 09 July 2026
Note/Remark
l The product is subject to the compliance with RINA Rules and other Standards mentioned on certificate.
l Type Approval certifies that a representative sample of the product has been found to meet the applicable design criteria.
l Any modification or change shall not be valid until approval is granted by RINA as a result of due assessment.
l Each Circuit Breakers with nominal current greater than 100A are subject to Final Inspection/Final Test of the Society
l Validity of this Type Approval Certificate is subject to the maintenance of a Production Quality Assurance certificate by RINA, covering the production of the type approved products.
Renewal/Revision
l 31/12/2015: initial certification. Certificate No. ELE241115PU
l 30/12/2020: renewal certification without design change.
l 09/07/2026: renewed without design change. New certificate revokes previous certificate No. ELE148520PU