Form
  Marine Equipment(TO)
MED201025XG
Certification N. MED201025XG - (ENG)
Certificate date 08/10/2025
Type Protezione antincendio
Product Equivalent fixed gas fire extinguishing systems components (extinguishing medium, head valves and nozzles) for machinery spaces and cargo pump rooms
Item Nº MED/3.45

Model or Denomin.
Items
FIREBOY- XINTEX FES FK-5-1-12
Applicant FIREBOY-XINTEX UK Operations Ltd
Place of requester 10 HOLTON ROAD, HOLTON HEATH  %  BH16 6LT Poole  % UNITED KINGDOM
Tel. N.,Fax, Email 00448453899462, 00441202625376, raldous@fireboy-xintex.com
Directive (EU) 2025/1533
Standards IMO MSC/Circ.848 ,IMO MSC.1/Circ.1267 as amended
Reference Documents SOLAS 74 Reg. II-2/10, IMO Res. MSC.36(63)-(1994 HSC Code) 7, IMO Res. MSC.97(73)-(2000 HSC Code) 7, IMO Res.MSC.98(73)-(FSS Code) 5. IMO MSC/Circ.848, IMO MSC.1/Circ.1313.
Expire date 07/10/2030
Head Office Hamburg
EC TYPE-EXAMINATION (MODULE B) ENG
Vuoto Querysave
Kagan Alaybasi S

EC TYPE EXAMINATION (MODULE B)
CERTIFICATE No. MED201025XG

This is to certify that RINA Services S.p.A. (Notified Body No. 0474) did undertake the relevant type approval procedures for the equipment identified below, which was found to be in compliance with the Fire Protection requirements of Marine Equipment Directive (MED) 2014/90/EU, including the requirements and testing standards of Regulation (EU) 2025/1533.
MED Item Nº MED/3.45
Description Equivalent fixed gas fire extinguishing systems components (extinguishing medium, head valves and nozzles) for machinery spaces and cargo pump rooms
Type FIREBOY- XINTEX FES FK-5-1-12
Applicant FIREBOY-XINTEX UK Operations Ltd
10 HOLTON ROAD, HOLTON HEATH,BH16 6LT Poole,UNITED KINGDOM
Testing standards IMO MSC/Circ.848 ,IMO MSC.1/Circ.1267 as amended
Reference standards SOLAS 74 Reg. II-2/10, IMO Res. MSC.36(63)-(1994 HSC Code) 7, IMO Res. MSC.97(73)-(2000 HSC Code) 7, IMO Res.MSC.98(73)-(FSS Code) 5. IMO MSC/Circ.848, IMO MSC.1/Circ.1313.
Issued in Hamburg on
This Certificate is valid until
October 8, 2025
October 7, 2030
This Certificate consists of this sheet plus an attachment

________________________________________
Giuseppe Russo
RINA Services S.p.A.
**** NOTICE: This is NOT an official certificate ****

ATTACHMENT TO
CERTIFICATE No.  MED201025XG
Page 1 of 2

Product description


Extinguishing Agent:
Trade name FK-5-1-12 - CF3CH2C(O)CF(CF3)2
Manufacturer Any Company with UL or FM FK-5-1-12 approval
Minimum design concentration 5.85 %
NOAEL (% volume) 10.0
LOAEL (% volume) >10.0
Cylinder capacity 20, 50, 90, 140, 280, 390, 450, 850 lb or equivalent liters capacity
Storage pressure 25 bars at 21° C (360 Psi at 70° F)
Operating temperature -18° to 55° C (0° to 130° F)
Assembly cylinder position Vertical only
Discharge nozzle: brass nozzle size (1/2" ÷ 2") 16 Port 360°/ 7 Port 180°- Minimum pressure: 4.87 bar;

Container valves: 1" BSPT/ 2" BSPT /3" Flare - Material: brass CZ122 or UNS36000; Max working pressure: 33.4 bar.


Field of application

Fixed gas fire-extinguishing systems for use in machinery spaces of category A and cargo pump-rooms equivalent to fire-extinguishing systems required by SOLAS Ch II-2, Reg 10.5 and by para 2.2 of Chapter 5 of Fire Safety System Code.

Reference documents

- Marine Novec 1230 System - Design, Installation, Recharge and Maintenance Manual issued on January 30, 2006 by Fireboy-Xintex Marine Safety Systems and filed by RINA with n° CSST 6052.
- Discharge nozzle, size 15÷50mm - Datasheet n° DS01830, issued by Fireboy-Xintex and approved by RINA with n° CSST 12999;
- Container Valve Assembly, 25mm / 50mm / 80mm, datasheet n° DS01102, DS01122 and DS01125 issued by Fireboy-Xintex and approved by RINA with n° CSST 13000, CSST 13001 and CSST 13002.

Test report
Fire Test report n° EX6263 issued by Underwriters Laboratories Inc. on September 23, 2002 and filed by RINA with n° CSST 6053.
Remarks

- In case of design concentrations above the NOAEL concentrations, controls as required by para 2.2.2.1 and 2.2.2.2 of Chapter 5 of Fire Safety System Code are to be provided;
- System using only one bottle located inside the protected space, can not be accepted. Such systems shall be designed with the bottle located outside the protected space.




ATTACHMENT TO
CERTIFICATE No. MED201025XG
Pages 2 of 2
The mark of conformity may only be affixed to the above type approved equipment and a Manufacturer's Declaration of Conformity issued when the production control phase module (D, E or F) of Annex II of the Directive is fully complied with a written inspection agreement with a Notified Body
XXXX/YY
"WHEELMARK FORMAT"

XXXX
Notified Body number undertaking surveillance module
YY
Last two digits of year mark affixed
     
______________________________________________
General conditions for the approval
a) The initial conditions verified by RINA at the time of the approval are to be maintained
b) Any changes to the initial conditions are to be promptly communicated to RINA, which reserves the right to repeat the relevant assessment
c) This certificate will no be valid if the manufacturer makes any changes or modifications to the approved equipment, which have not been notified to, and agreed with RINA
d) RINA personnel are to be allowed to witness during the performances of activities, upon their request
e) The activities are to be carried out in compliance with the RINA Rules and/or other applicable Rules

f) Should the specified regulations or standards be amended during the validity of this certificate, the product is to be reapproved prior to it being placed on board vessels to which the amended regulations or standards apply. 