Materials/Components
Power and control cables, armoured and unarmoured, low smoke, halogen free, flame retardant, fire resistant (+ mechanical shocks + water spray), for ships and offshore units.
Rated voltage: 0,6/1 kV
Type: FIREBAR® XI (unarmoured) & XAI (armoured)
Maximum conductor temperature: 95°C
Marking: CCI FIREBAR® XI (or XAI) 0.6/1 kV n X s mm2 IEC 60092-353 IEC 60332-3-22 Cat A BS 7846:2000 Cat F3 meter marking Year QA n°
Construction:
conductor:: plain or tinned annealed copper conductor (according to IEC 60228, Class 2 or Class 5)
Mica glass tape on the conductor
insulation: S95
fillers: fibreglass ropes, silicon sheathed
FIREBAR® protection:
- fibreglass tapes overlapped 50%
- Cu-PET tapes
- fibreglass tapes overlapped 50%
inner sheath: HF LSOH compound
armour: plain or tinned copper wires braid (XAI type only)
outher sheath: SHF2 or SHF1
Other Standards:
In accordance with IEC 60228; IEC 60092-350; IEC 60092-353; IEC 60092-360; IEC 60332-1-2; IEC 60331-1 /2; EN 50200 Annex E (De ≤ 20 mm); IEC 60332-3-22 Cat.A; IEC 60754-1; IEC 60754-2; IEC 61034-1; IEC 61034-2; RINA Rules; RINAMIL Rules; RINA Rules for FSRU; RINAMIL for FREMM; RINA Rules for FPV.
Fire Resistance with Mechanichal Shocks and Water Spray according to Standards BS 7846:2000 F3.
Cold Bend and Impact Test at Low Temperature (-40C°) according to Standards CSA C 22.2 N. 22.2 N. 0.3-01 & N. 38-05.
Technichal Specification:
CCI Data Sheet N. FBRI/IEC716-2 Rev.0 dated 05/07/16.
Test Reports/ Documents:
CCI:
Test Report N. 21154, dated 02 Aug.2013
Test Report N. 21064, dated 23 Sep. 2013
Test Report N. 19671, dated 31 Oct.. 2012
Test Report N. 25068, dated 30 Sep. 2015
Test Report N. 21177, dated 08 Oct. 2013.
Test Report N. 21065, dated 23 Sep. 2013
Test Report N. KCABP/R/W/10/11/2-1, dated 15 Dec. 2010
Test Report N. BP/COP/11-11, dated 09 Nov. 2011
Test Report N. LRFB/IEC0806-1&2, dated 09 Jul. 2006
Wtnessed Fire Resistant Tests Report, dated 19 feb. 2010
Witnessed IEC 60092-360 Tests Report dated 01 Mar. 2016.
Document N. FBRI/IEC716-2/DC - Rev.0, dated 29 Aug. 2016
TYPE APPROVAL CERTIFICATE
ELE197118CS/002
Enclosure - Page 2 of 2
FIREBAR® XI & XAI serie, 0.6/1 kV
Test Reports/ Documents:
Warringtonfire:
Test Report N. 159382, dated 04 Jan. 2007
IMQ:
Test Report N. 01SK00153, dated 15 Jul. 2010
Test Report N. 01SG00256, dated 20 Dec. 2006
Test Report N. 01SJ00113 rev.1, dated 01 Feb. 2010
Test Report N. 01SJ00113-332, dated 10 Mar. 2010
Components for electric plants to be used according to the instructions given by the manufacturer.
The product is subject to the compliance with RINA Rules and Standards mentioned on the certificates
Type Approval certifies that a rappresentative sample of the products has been found to meet the applicable design criteria
Any modification of change shall not be valid until approval is granted by RINA as a result of due assessment.
|
|