Product:
S200C Compact MCBs series: S202C and S202C M.
Production Description:
Miniature Circuit – breakers for overcurrent protection.
Environmental Category:
- EC3b3
- EC41
according to RINA Rules Part C, Ch.2, Sec 3
Rating and principal characteristics:
S202C:
Number of poles | 2P |
Number of modules | 1M |
Tripping Characteristic | B, C |
Rated Current In [A] | 2, 4, 6, 10, 13, 15, 16, 20 A |
Rated operational voltage Ue [V] | 240 |
Rated insulation voltage Ui [V] | 500 V AC |
Rated frequency f [Hz] | 50/60 |
Min operation voltage [V] | 12 |
Max operation voltage [V] | 253 |
Rated short-circuit capacity Icn [A] | 6000 |
Rated impulse withstand voltage (1.2/50us) Uimp [kV] | 4 |
Dielectric test voltage at ind. freq. for 1 min [kV] | 2.5 kV (50/60Hz, 1 min) |
Ambient temperature (with daily average +35°C) | -25…+55 |
S202C M:
Number of poles | 2P |
Number of modules | 1M |
Tripping Characteristic | B, C |
Rated Current In [A] | 2, 4, 6, 10, 13, 15, 16, 20 A |
Rated operational voltage Ue [V] | 240 |
Rated insulation voltage Ui [V] | 500 V AC |
Rated frequency f [Hz] | 50/60 |
Min operation voltage [V] | 12 |
Max operation voltage [V] | 253 |
Rated short-circuit capacity Icn [A] | 10000 |
Rated impulse withstand voltage (1.2/50us) Uimp [kV] | 4 |
Dielectric test voltage at ind. freq. for 1 min [kV] | 2.5 kV (50/60Hz, 1 min) |
Ambient temperature (with daily average +35°C) | -25…+55 |
Type reference of the circuit – breakers S200C series and related ratings:
Model | Rated short – circuit capacity In | Curve | Rated current [A] | Type reference |
S202C | 6000 A | B | 2 | 2CSS252420R0025 |
4 | 2CSS252420R0045 |
6 | 2CSS252420R0065 |
10 | 2CSS252420R0105 |
13 | 2CSS252420R0135 |
16 | 2CSS252420R0165 |
20 | 2CSS252420R0205 |
C | 2 | 2CSS252420R0024 |
4 | 2CSS252420R0044 |
6 | 2CSS252420R0064 |
10 | 2CSS252420R0104 |
13 | 2CSS252420R0134 |
15 | 2CSS252420R0154 |
16 | 2CSS252420R0164 |
20 | 2CSS252420R0204 |
S202C M | 10000 A | B | 2 | 2CSS272420R0025 |
4 | 2CSS272420R0045 |
6 | 2CSS272420R0065 |
10 | 2CSS272420R0105 |
13 | 2CSS272420R0135 |
16 | 2CSS272420R0165 |
20 | 2CSS272420R0205 |
C | 2 | 2CSS272420R0024 |
4 | 2CSS272420R0044 |
6 | 2CSS272420R0064 |
10 | 2CSS272420R0104 |
13 | 2CSS272420R0134 |
15 | 2CSS272420R0154 |
16 | 2CSS272420R0164 |
20 | 2CSS272420R0204 |
Data sheet:
ABB Catalogue A_ELSB_Cat_2025_01_MCBs_S200C No. 9AKK107991A8329
Reference Documents:
ISO 9001:2015 Certificate No. 9105.ELTR (IMQ, expiry date: 2026/06/29)
Test Report:
IMQ Test Report according to IEC 60898-1 (17/04/2025):
Model | In[A] | Curve | Rated current [A] | Test Report Reference No. | Date (s) of performance of tests: |
S202C | 6000 | C | 20 | PB24-0112624-02-16 | From 2024/09/13 to 2025/04/01 |
6 | PB24-0112624-02-17 |
2 | PB24-0112624-02-18 |
S202C M | 10000 | B | 20 | PB24-0112624-02-09 |
16 | PB24-0112624-02-10 |
13 | PB24-0112624-02-11 |
10 | PB24-0112624-02-12 |
6 | PB24-0112624-02-13 |
4 | PB24-0112624-02-14 |
2 | PB24-0112624-02-15 |
C | 20 | PB24-0112624-02-01 |
16 | PB24-0112624-02-02 |
15 | PB24-0112624-02-03 |
13 | PB24-0112624-02-04 |
10 | PB24-0112624-02-05 |
6 | PB24-0112624-02-06 |
4 | PB24-0112624-02-07 |
2 | PB24-0112624-02-08 |
IMQ CB Test Certificate No. IT-IMQ-25701 (2025/06/03).
IMQ Cenelec Certification Agreement (CCA)
ABB Test Report:
Test Report No. 2CE06454-000-00 (Test execution date from 24/06/2025 to 04/07/2025).
Remarks:
Validity of this certificate is subject to satisfactory outcome of yearly audit as per RINA " Rules for Testing and Certification of Marine Materials and Equipment".