High pressure water mist system composed of water pumps, stainless steel pipes, strainer, section valves, open nozzles, control and monitoring systems designed in accordance with the "Principal requirements of the System", IMO MSC/Circ.1165, as amended.
Nozzles characteristics and installation requirements
Machinery space installation
1. Volume up to 1260 m³
Uniform grid pattern of nozzles type EI -FOG2IXX0.815 (*)
K-factor [lpm /(bar)½] | 0.88 |
Max ceiling height [m] | 8.4 |
Max nozzle spacing [m] | 5 |
Max distance from bulkhead [m] | 2.5 |
Minimum working pressure [bar] | 100 |
2. Volume up to 3000 m³
Uniform grid pattern of nozzles type EI SECURIPLEX RNZ-16434-00 (*)
K-factor [lpm /(bar)½] | 2.1 |
Max ceiling height [m] | 8.0 |
Max nozzle spacing [m] | 2.5 |
Max distance from bulkhead [m] | 2.5 |
Minimum working pressure [bar] | 53 |
(*): according to MSC.1/Circ.1385 " Scientific methods on scaling of test volume for fire tests on water-mist fire -extinguishing systems" and based on the fire test concucted, the maximum protected net volume can be scaled as following:
- System using nozzles EI -FOG2IXX0.815: up to and including 2520 m³
- System using nozzles EI SECURIPLEX RNZ-16434-00: up to and including 5250 m³
ATTACHMENT TO
CERTIFICATE Nr. MED129322CS/003
Page 2 of 3
Bilge area installation
The protection can be achieved with either water based or foam making systems:
Water nozzles: type EI SECURIPLEX RNZ-16434-00
| K-factor [lpm /(bar)½] | 2.1 |
| Bilge height [m] | 0.75 |
| Max nozzle spacing [m] | 2.0 |
| Minimum working pressure [bar] | 53 |
| Location | bilge plate |
| Projection | 30° downward |
Foam nozzles: type EI -FOG BETE WL-20 (*)(**)
| Nozzle connection | 3/4" | 1" |
K-factor [lpm /(bar)½] | 30 | 45.9 |
Bilge height [m] | 0.75 |
Nozzle spacing [m] | 5.0 x 4.0 |
Minimum working pressure [bar] | 0.5 | 0.2 |
| Location | bilge plate |
Projection | horizontal |
(*): foam obtained with fresh water and low expansion foam concentrate, mixing ratio 3%
(**): nozzle material brass and/or naval brass
Reference documents
- Use and Maintenance Manual “Fixed Pressure Water Spraying Fire Extinguishing System for Machinery Spaces ”edited by EUSEBI IMPIANTI and filed by RINA with n° CSST 9419.
- P&I Diagram for watermist system according to MSC/Circ.1165, n° 7754MA27, filed by RINA with n° CSST 9420
- Mechanical Datasheet “Fixed Pressure Water Spraying Fire Extinguishing System for Machinery Spaces" edit by EUSEBI IMPIANTI and filed by RINA with n° CSST 9421.
- Datasheet of total flooding nozzles, approved by RINA with n° CSST 10409.
- Nozzles Heads Type EI-FOG 2Ixx0.815 and RNZ-16434-00 issued by Eusebi Impianti and approved by Rina with n°CSST14712.
Tests carried out
- Clogging test of nozzle RNZ-16434-00, report n° 3024766 edit by FM Approvals and filed by RINA with n° CSST-9422.
- Testing of Fire-Scope 5000 Water Mist Nozzle EI SECURIPLEX RNZ-16434-00 - Final Report n° 01.15472.01.001 edit by Southwest Research Institute and filed by RINA with n° CSST-9423.
- Approval Report n° 3011043 - Mechanical component test nozzle RNZ-16434-00, edit by FM Approvals and filed by RINA with n° CSST-9435.
- Test Report n° 213/c edit by TE.S.I. Laboratory and filed by RINA with n° CSS- 9424.
- Component performance test of Eusebi Model 2IXX1.615, report n° E246487, edit by UL Laboratories and filed by RINA with n° CSST-9397.
- Clogging Test report n° 3033662, nozzle 2IXX1.615, issued by FM Approvals Laboratory and filed by RINA with n° CSST-2906.
- Fire Test Report nozzle 2IXX1.615, n° P603476, issued by SP Swedish National and Research Institute and filed by RINA with n° CSST-2907.
- Component performance test of nozzle EI-FOG BETE WL-20, report n° 204/C and n° 217/C, issued by TE.S.I. Laboratory and filed by RINA with n° CSST-9436 and n° CSST-10410.