MED129322CS!003ENGD- -  -  N- EI-MIST FIXED PRESSURE-WATER SPRAYING FIRE EXTINGUISHING SYSTEMS FOR MACHINERY SPACES AND CARGO PUMP ROOMS -N- S- S- -31/03/2022- Marine Equipment- - SN- S- - N-  - 491,066B2bisMarine EquipmentNumero Pratica,Direttiva,Norma,Schema,Richiesta,Validità,EmailR- MED129322CS/003- N-Mar 30, 2027491066
 
Form
  Marine Equipment(TO)
Certification N. MED129322CS/003 - (ENG)
Certificate date 31/03/2022
Type Protezione antincendio
Product Ugelli per impianti fissi ad acqua spruzzata per locali apparato motore Cat. A e locali pompe del carico.
Item Nº MED/3.39

Model or Denomin.
Items
EI-MIST FIXED PRESSURE-WATER SPRAYING FIRE EXTINGUISHING SYSTEMS FOR MACHINERY SPACES AND CARGO PUMP ROOMS
Applicant VALVITALIA S.P.A. - BUSINESS UNIT FIRE FIGHTING
Place of requester VIA MARIO NATALUCCI 6  %  60131 Ancona (AN)  % ITALY
Tel. N.,Fax, Email 3453666651, +39 071 2865099, fabrizio.raffaelli@valvitalia-fire.com
Directive (EU) 2021/1158
Standards IMO MSC/Circ. 1165, as amended.
Reference Documents Reg. II-2/10, IMO Res. MSC.36(63)-(1994 HSC Code) 7, IMO Res. MSC.97(73)-(2000 HSC Code) 7, IMO Res. MSC.98(73)-(FSS Code) 7, IMO MSC.1/Circ.1313, IMO MSC.1/Circ.1458.
Request 20/02/2017
Expire date 30/03/2027
EC TYPE-EXAMINATION (MODULE B) ENG
Vuoto Querysave
Giovanni Carratino S

EC TYPE EXAMINATION (MODULE B)
CERTIFICATE No. MED129322CS/003

This is to certify that RINA Services S.p.A. (Notified Body No. 0474) did undertake the relevant type approval procedures for the equipment identified below, which was found to be in compliance with the Fire Protection requirements of Marine Equipment Directive (MED) 2014/90/EU, including the requirements and testing standards of Regulation (EU) 2021/1158.
MED Item Nº MED/3.39
Description Nozzles for equivalent water-mist fire extinguishing systems for machinery spaces and cargo pump rooms
Type EI-MIST FIXED PRESSURE-WATER SPRAYING FIRE EXTINGUISHING SYSTEMS FOR MACHINERY SPACES AND CARGO PUMP ROOMS
Applicant VALVITALIA S.P.A. - BUSINESS UNIT FIRE FIGHTING
VIA MARIO NATALUCCI 6,60131 Ancona (AN),ITALY
Testing standards IMO MSC/Circ. 1165, as amended.
Reference standards Reg. II-2/10, IMO Res. MSC.36(63)-(1994 HSC Code) 7, IMO Res. MSC.97(73)-(2000 HSC Code) 7, IMO Res. MSC.98(73)-(FSS Code) 7, IMO MSC.1/Circ.1313, IMO MSC.1/Circ.1458.
Issued in Genoa on
This Certificate is valid until
March 31, 2022
March 30, 2027
This Certificate consists of this sheet plus an attachment

________________________________________
Giovanni Carratino
RINA Services S.p.A.
**** NOTICE: This is NOT an official certificate ****

ATTACHMENT TO
CERTIFICATE No.  MED129322CS/003
Page 1 of 3

Product description

High pressure water mist system composed of water pumps, stainless steel pipes, strainer, section valves, open nozzles, control and monitoring systems designed in accordance with the "Principal requirements of the System", IMO MSC/Circ.1165, as amended.
Nozzles characteristics and installation requirements

Machinery space installation


1. Volume up to 1260 m³

Uniform grid pattern of nozzles type EI -FOG2IXX0.815 (*)

K-factor [lpm /(bar)½]
0.88
Max ceiling height [m]
8.4
Max nozzle spacing [m]
5
Max distance from bulkhead [m]
2.5
Minimum working pressure [bar]
100

2. Volume up to 3000 m³

Uniform grid pattern of nozzles type EI SECURIPLEX RNZ-16434-00 (*)

K-factor [lpm /(bar)½]
2.1
Max ceiling height [m]
8.0
Max nozzle spacing [m]
2.5
Max distance from bulkhead [m]
2.5
Minimum working pressure [bar]
53

(*): according to MSC.1/Circ.1385 " Scientific methods on scaling of test volume for fire tests on water-mist fire -extinguishing systems" and based on the fire test concucted, the maximum protected net volume can be scaled as following:
  • System using nozzles EI -FOG2IXX0.815: up to and including 2520 m³
  • System using nozzles EI SECURIPLEX RNZ-16434-00: up to and including 5250 m³


ATTACHMENT TO
CERTIFICATE Nr. MED129322CS/003
Page 2 of 3

Bilge area installation

The protection can be achieved with either water based or foam making systems:

Water nozzles: type EI SECURIPLEX RNZ-16434-00

K-factor [lpm /(bar)½]
2.1
Bilge height [m]
0.75
Max nozzle spacing [m]
2.0
Minimum working pressure [bar]
53
Location
bilge plate
Projection
30° downward
Foam nozzles: type EI -FOG BETE WL-20 (*)(**)
Nozzle connection 3/4"
1"
K-factor [lpm /(bar)½]
30
45.9
Bilge height [m]
0.75
Nozzle spacing [m]
5.0 x 4.0
Minimum working pressure [bar]
0.5
0.2
Location
bilge plate
Projection
horizontal
(*): foam obtained with fresh water and low expansion foam concentrate, mixing ratio 3%
(**): nozzle material brass and/or naval brass
Reference documents
  1. Use and Maintenance Manual “Fixed Pressure Water Spraying Fire Extinguishing System for Machinery Spaces ”edited by EUSEBI IMPIANTI and filed by RINA with n° CSST 9419.
  2. P&I Diagram for watermist system according to MSC/Circ.1165, n° 7754MA27, filed by RINA with n° CSST 9420
  3. Mechanical Datasheet “Fixed Pressure Water Spraying Fire Extinguishing System for Machinery Spaces" edit by EUSEBI IMPIANTI and filed by RINA with n° CSST 9421.
  4. Datasheet of total flooding nozzles, approved by RINA with n° CSST 10409.
  5. Nozzles Heads Type EI-FOG 2Ixx0.815 and RNZ-16434-00 issued by Eusebi Impianti and approved by Rina with n°CSST14712.

Tests carried out
  • Clogging test of nozzle RNZ-16434-00, report n° 3024766 edit by FM Approvals and filed by RINA with n° CSST-9422.
  • Testing of Fire-Scope 5000 Water Mist Nozzle EI SECURIPLEX RNZ-16434-00 - Final Report n° 01.15472.01.001 edit by Southwest Research Institute and filed by RINA with n° CSST-9423.
  • Approval Report n° 3011043 - Mechanical component test nozzle RNZ-16434-00, edit by FM Approvals and filed by RINA with n° CSST-9435.
  • Test Report n° 213/c edit by TE.S.I. Laboratory and filed by RINA with n° CSS- 9424.
  • Component performance test of Eusebi Model 2IXX1.615, report n° E246487, edit by UL Laboratories and filed by RINA with n° CSST-9397.
  • Clogging Test report n° 3033662, nozzle 2IXX1.615, issued by FM Approvals Laboratory and filed by RINA with n° CSST-2906.
  • Fire Test Report nozzle 2IXX1.615, n° P603476, issued by SP Swedish National and Research Institute and filed by RINA with n° CSST-2907.
  • Component performance test of nozzle EI-FOG BETE WL-20, report n° 204/C and n° 217/C, issued by TE.S.I. Laboratory and filed by RINA with n° CSST-9436 and n° CSST-10410.




ATTACHMENT TO
CERTIFICATE No. MED129322CS/003
Pages 3 of 3
The mark of conformity may only be affixed to the above type approved equipment and a Manufacturer's Declaration of Conformity issued when the production control phase module (D, E or F) of Annex II of the Directive is fully complied with a written inspection agreement with a Notified Body
XXXX/YY
"WHEELMARK FORMAT"

XXXX
Notified Body number undertaking surveillance module
YY
Last two digits of year mark affixed
     
______________________________________________
General conditions for the approval
a) The initial conditions verified by RINA at the time of the approval are to be maintained
b) Any changes to the initial conditions are to be promptly communicated to RINA, which reserves the right to repeat the relevant assessment
c) This certificate will no be valid if the manufacturer makes any changes or modifications to the approved equipment, which have not been notified to, and agreed with RINA
d) RINA personnel are to be allowed to witness during the performances of activities, upon their request
e) The activities are to be carried out in compliance with the RINA Rules and/or other applicable Rules

f) Should the specified regulations or standards be amended during the validity of this certificate, the product is to be reapproved prior to it being placed on board vessels to which the amended regulations or standards apply. 