Technical Characteristics
DESIGNATION | CONC. | EXPANSION
RATIO | VISCOSITY
(mm²/s) | PH | DENSITY
(g/cm³) | DRAINAGE
TIME (25%/50%) | FIRE RATING |
GX-FUOCO
High Expansion Foam | 1% | 549 | 4.23 | 8.82 | 1.04 | 3min40s
4min50s | Extinction time
< 2 min |
2% | 602 | 6.37 | 8.88 | 1.02 | 2min50s
4min45s |
3% | 666 | 4.49 | 8.58 | 1.01 | 3min4s
5min2s |
Field of Application
This approval does not address the foam generating equipment, only the foam concentrate for fixed high expansion
foam fire extinguishing systems for extinguishing fires in machinery spaces and cargo pump rooms referred to in
SOLAS regulation II-2/9.
Tests Carried Out
The analysis product report and fire test report were witnessed by RINA and issued according to IMO MSC.1/Circ.670
- 'Guidelines for The Performance and Testing Criteria and Surveys of High-Expansion Foam Concentrates for Fixed
Fire-Extinguishing Systems'.
| ATTACHMENT TO
CERTIFICATE No. MED098924X3
Page 2 of 3 |
Technical Documentation
- Technical Data Sheet reviewed and filed by RINA with Dwg. No. PUFP-6565
- Material Safety Data Sheet reviewed and filed by RINA with Dwg. No. PUFP-6564
- Analysis Product for High Expansion Foam reviewed and filed by RINA with Dwg. No. PUFP-6562
- Fire Test Report for High Expansion Foam reviewed and filed by RINA with Dwg. No. PUFP-6563
DESIGNATION | CONC | Dwg. No. PUFP-6562 | Dwg. No. PUFP-6563 |
<Test for Product Analysis> | <Fire Test> |
GX-FUOCO
High Expansion
Foam | 1% | No. 4892 dated 09/04/24, 25/04/24 | GSP/WSFT/1/HE dated 16/05/24 |
2% | No. 4893 dated 09/04/24, 25/04/24 | GSP/WSFT/2/HE dated 16/05/24 |
3% | No. 4894 dated 09/04/24, 25/04/24 | GSP/WSFT/3/HE dated 16/05/24 |