MED236824CS!001ENGD- -  -  N- Fanflex 20F-SV/3 Mod. -N- S- S- -02/08/2024- Marine Equipment- - SN- S- - N-  - 692,947B2bisMarine EquipmentNumero Pratica,Direttiva,Norma,Schema,Richiesta,Validità,EmailR- MED236824CS/001- N-Aug 1, 2029692947
 
Form
  Marine Equipment(TO)
MED070424MI/001
Certification N. MED236824CS/001 - (ENG)
Certificate date 02/08/2024
Type Protezione antincendio
Product Penetrations through "A" Class divisions: (b) pipe, duct, trunk, etc. penetrations
Item Nº MED/3.26b
USCG Category N° 164.138

Model or Denomin.
Items
Fanflex 20F-SV/3 Mod.
Applicant BBV TECH SRL
Place of requester VIA PAPA GIOVANNI XXIII, 56  %  20090 Rodano (MI)  % ITALY
Tel. N.,Fax, Email +39 0295328118, 0295328316, ---
Directive (EU) 2023/1667
Standards IMO Res. MSC.307(88)-(2010 FTP Code)
Reference Documents Chap. II-2 of SOLAS 74 Convention, as amended, RINA Rules for the certification of Marine Equipment
Request 13/05/2024
Expire date 01/08/2029
EC TYPE-EXAMINATION (MODULE B) ENG
Vuoto Querysave
Enrico Cabella S

EC TYPE EXAMINATION (MODULE B)
CERTIFICATE No. MED236824CS/001

This is to certify that RINA Services S.p.A. (Notified Body No. 0474) did undertake the relevant type approval procedures for the equipment identified below, which was found to be in compliance with the Fire Protection requirements of Marine Equipment Directive (MED) 2014/90/EU, including the requirements and testing standards of Regulation (EU) 2023/1667.
MED Item Nº MED/3.26b
USCG Category Nº 164.138
Description Penetrations through "A" Class divisions: (b) pipe, duct, trunk, etc. penetrations
Type Fanflex 20F-SV/3 Mod.
Applicant BBV TECH SRL
VIA PAPA GIOVANNI XXIII, 56,20090 Rodano (MI),ITALY
Testing standards IMO Res. MSC.307(88)-(2010 FTP Code)
Reference standards Chap. II-2 of SOLAS 74 Convention, as amended, RINA Rules for the certification of Marine Equipment
Issued in Genoa on
This Certificate is valid until
August 2, 2024
August 1, 2029
This Certificate consists of this sheet plus an attachment

________________________________________
Enrico Cabella
RINA Services S.p.A.
**** NOTICE: This is NOT an official certificate ****

ATTACHMENT TO
CERTIFICATE No.  MED236824CS/001
Page 1 of 2

Product description


The pipe penetration is carried out by a steel cylinder min. Ø280 mm, max Ø 1020 mm, height 450 mm and thickness 5 mm welded on the unexposed side of the bulkhead. A steel pipe min. DN50, thickness 3.18 mm, max. DN800, thickness 5 mm, pass inside the cylinder. On the pipe is welded a steel flange having “L”, Ø external min. 420 mm, max 1160 mm, height 40 mm and thickness 5 mm. The gap between flange and penetration cylinder is 30 mm. Outside the penetration, on the unexposed side, a steel cylinder having Ø min. 420 mm, max. 1160 mm, height 340 mm and thickness 5 mm, is welded on the bulkhead. Externally to this cylinder, for a height of 290 mm, it is installed 1 layer of mineral wool having thickness 40 mm (#) and density of 100 kg/m³, named Rockwool PROROX WM 960 with metallic net, secured by steel wire. Inside the penetration on the exposed side, the pipe is insulated for a height of 885 mm from the welded flange on the pipe, by 2 layers of mineral wool having thickness 40 mm and density of 100 kg/m³, named Rockwool PROROX WM 960 with metallic net, secured by steel wire. On the exposed side, externally to the up described insulation, for a height of 400 mm starting from the bulkhead, are applied 4 layer of mineral wool thickness 40 mm and density of 100 kg/m³, named Rockwool PROROX WM 960 with metallic net, secured by steel wire. At 100 mm from the bulkhead, these insulations are fixed to the pipe using two (#) rows of steel pins 200 mm (#) apart, positioned every min. 60°, max. 120°. On the unexposed side, externally to the cylinder penetration, for a height of 480 mm from the bulkhead, are applied 2 layers of mineral wool having thickness 40 mm (#) and density 100 kg/m³, named Rockwool PROROX WM 960 with metallic net. On the unexposed side, externally to the pipe, for the entire height, from the welded flange, are applied 3 layers of mineral wool having thickness 40 mm (#) and density 100 kg/m³ named Rockwool PROROX WM 960 with metallic net, secured by steel wire, overlapped of min. 200 mm (#). From the flange welded on the pipe and the cylinder welded on the bulkhead, using inox clamps, are installed a gasket made of HT silicone named BBV Tech srl EVV051501, thickness, thickness 3 mm, density 1300 kg/m³ and one layer of glass fiber cover named rex thermoglas Gewebe 200 - 1300 kg/m².

Field of application

Fire resistant A-60 Class metal pipes penetration through bulkhead as per above table.

Reference documents

BBV-Tech drawing no. 1C-9354 dated 17/06/2024.

BBV-Tech drawing no. 1C-9341 dated 06/05/2024.


Tests carried out

RINA Test Report No. 2024CS012368/1 and 2024CS012368/3 issued on 20/06/2024 according to IMO 2010 FTP Code.

Pressure Test Certificate (test pressure 0.3 bar) No. CPI-Type Approval-02 (RINA 2024/MI/01/544) issued on the 16/07/2024 at BBV Tech S.r.l.





ATTACHMENT TO
CERTIFICATE No. MED236824CS/001
Pages 2 of 2
The mark of conformity may only be affixed to the above type approved equipment and a Manufacturer's Declaration of Conformity issued when the production control phase module (D, E or F) of Annex II of the Directive is fully complied with a written inspection agreement with a Notified Body
XXXX/YY
"WHEELMARK FORMAT"

XXXX
Notified Body number undertaking surveillance module
YY
Last two digits of year mark affixed
     
______________________________________________
General conditions for the approval
a) The initial conditions verified by RINA at the time of the approval are to be maintained
b) Any changes to the initial conditions are to be promptly communicated to RINA, which reserves the right to repeat the relevant assessment
c) This certificate will no be valid if the manufacturer makes any changes or modifications to the approved equipment, which have not been notified to, and agreed with RINA
d) RINA personnel are to be allowed to witness during the performances of activities, upon their request
e) The activities are to be carried out in compliance with the RINA Rules and/or other applicable Rules

f) Should the specified regulations or standards be amended during the validity of this certificate, the product is to be reapproved prior to it being placed on board vessels to which the amended regulations or standards apply. 


__________________________________________
Enrico Cabella
**** NOTICE: This is NOT an official certificate ****