1. Product Description
The SCS-GDS is a Gas Detection System designed to monitoring the leakage of combustible/toxic gas on board. covers the following components:
1.1 Gas Alarm Controller:
Power supply: AC90V~264V,50/60HZ
Model: FXK-GD6064
Structure: Wall mounting type
Main Compositions: Touch screen, Control unit, Communication convert card
IP degree: IP 66
1.2 Detectors:
GTYQ-WRS81 : Catalytic combustion type/Point-type infrared, Combustible gas, Certified by MED274525WS/001,Ex db IIC T6 Gb; Ex tb IIIC T80°C Db
GTYQ-WRS91 : Catalytic combustion type/Point-type infrared, Combustible gas, Certified by MED274525WS/001,Ex db IIC T6 Gb; Ex tb IIIC T80°C Db
GQ-WRS81 : Electrochemical, O2, Certified by MED274525WS/001,Ex db IIC T6 Gb; Ex tb IIIC T80°C Db
GQ-WRS91 : Electrochemical, O2, Certified by MED274525WS/001,Ex db IIC T6 Gb; Ex tb IIIC T80°C Db
This certificate covers detectors' model: GTYQ-WRS81/82 and GQ-WRS91/92.
 | ATTACHMENT TO
CERTIFICATE No. MED274525WS/002
Page 2 of 3 |
2. Application/Limitation
The gas detection system designed to detects and monitors the combustible gas at the hazardous area, pump room, water ballast tank, engine room, accommodation area, cargo motor room and BOG pip duct in ships.
This certificate only covers hardware listed under product description. All changes in software are to be recorded as long as he system is used on board. Documentation of major changers is to be forwarded to us for evaluation before implemented on board.
Note: Toxic gases not covered by present certificate.
Ex certification is not covered by this certificate, Applications in hazardous areas are to be approved in each case according to the Rules and Conditions for Safe Use specified in a valid Ex-Certificate issued by a Notified or Recognized Certification Body.
3. Design Assessment
The design assessment is based on SOLAS 74 Reg. II-2/4, IMO Res. MSC.98(73)-(FSS Code) 16, IMO MSC.1/Circ.1370, IMO MSC.1/Circ.1527.
4. Tests Carried Out
The test report, including environment test, EMC test and performance test, complies with EN 50104:2019, EN IEC 60079-0:2018 incl. AC:2020, EN 60079-29-1:2016, IEC 60092-504:2016, and IEC 60533:2015. For combined O2/HC systems,additionally: IMO MSC.1/Circ. 1370. Tests were conducted in authorized laboratory and comply with these standards. Reports are filed by RINA with drawing No.: SHEL-28794.
Inspection report (Date on 2025, July 25) edit by "WAROM TECHNOLOGY INCORPORATED COMPANY" and witnessed by RINA Surveyor. Filed by RINA with drawing No.:SHEL-29130.
5. Reference DocumentsAnalysis and assessment of risk, Filed by RINA with drawing No. SHEL-28799.
European Representative Authorization Letter. Filed by RINA with drawing No.SHEL-28797.
Asbestos-free Declaration: Filed by RINA with drawing No. SHEL-28800.
Technical drawings and manuals approved and filed by RINA listed on Approval letter No.: SHEL/2026/297/JY001 and SHEL/2026/345/JY001.
6. Marking of Product
The product is to be indelibly marked with name and address of the manufacturer, type designation, batch or serial number or other elements allowing their identification and the MED Mark of Conformity. |