Transits of electric cables, having diameter ranging from 9 mm up to 39 mm, installed in A-Class aluminium bulkheads and decks. The transits are composed of an aluminium frame, having thickness of 10 mm and depth of 60 mm, fillet welded, on both sides, to the bulkhead or deck plate. The transits type WRFF AL are fitted, on one side, with a flange welded to the deck or bulkhead plate, whereas the transits type WRF AL, without flange, are welded in the middle to the bulkhead or deck plate. The transits are filled with EPDM modules and, on the upper part, one module fitted with a screw expander is installed. The interstices between the cables and the modules and between the modules, are lubricated by means of product named WallMax Lubricant. The transits are insulated, on both sides, with three layers of mineral wool type SeaRox SL 620, having density of 100 kg/m3 and thickness of 40 mm (first layer fitted around the transit) and 60 mm each (the other two layers); the mineral wool panels, having dimensions of 400 mm in width and 600 mm in length, are fixed to the bulkhead or deck plate by means of bi-metallic pins and washers welded with pitch ranging from 120 up to 200 mm. The certification is valid also for transit type WRFO, fitted without flange, and composed of a three-side frame with the fourth side welded afterwards.
|
ATTACHMENT TO
CERTIFICATE Nr. MED296826CS/002
Page 2 of 4 |
Field of application Fire resistant A-60 Class cable transits through aluminium bulkheads and decks as per following tables:
WRFF / WRFF EX - AL TYPE - BULKHEAD
Transit dimensions (mm) | Flange dimensions (mm) | Minimum fill
% | Maximum fill
% | Cables - Maximum diameter (mm) |
298 x 140 | 418 x 260 | 7.5 | 7.5 | 39 |
118 x 140 | 238 x 260 | 0.5 | 0.5 | 9 |
WRF / WRF EX - AL TYPE - BULKHEAD
Transit dimensions (mm) | Minimum fill
% | Maximum fill
% | Cables - Maximum diameter (mm) |
298 x 140 | 7.5 | 7.5 | 39 |
118 x 140 | 0.5 | 0.5 | 9 |
WRFF / WRFF EX - AL TYPE - DECK
Transit dimensions (mm) | Flange dimensions (mm) | Minimum fill
% | Maximum fill
% | Cables - Maximum diameter (mm) |
298 x 140 | 418 x 260 | 7.5 | 7.5 | 39 |
118 x 140 | 238 x 260 | 0.5 | 0.5 | 9 |
WRF / WRF EX - AL TYPE - DECK
Transit dimensions (mm) | Minimum fill
% | Maximum fill
% | Cables - Maximum diameter (mm) |
298 x 140 | 7.5 | 7.5 | 39 |
118 x 140 | 0.5 | 0.5 | 9 |
|
ATTACHMENT TO
CERTIFICATE Nr. MED296826CS/002
Page 3 of 4 |
Reference documents
WallMax drawing No. WDVpc16A60AIDA01, No. WDVpc16A60AIBHA01 and No. 1112022411 dated 5 February 2016 approved on 4, 5 and 11 May 2016 respectively with endorsement Nos. LABS-1259, LABS-1260 and LABS-1264, "Declaration of product identity" by WallMax Srl dated 14/07/2026.
Tests carried out
Tests as per RINA Test Laboratory Reports No. 2016CS01481/1 dated 4 May 2016 and No. 2016CS01481/2 dated 5 May 2016 issued according to Appendix 1 of IMO 2010 FTPC Part 3 - A.IV Cable Transits. |