MED059422CSENGD- -  -  N-  MW -N- S- S- -23/02/2022- Marine Equipment- - SN- S- - N-  - 31,336B2bisMarine EquipmentNumero Pratica,Direttiva,Norma,Schema,Richiesta,Validità- MED059422CS- N-Feb 22, 202731336
 
Form
  Marine Equipment(TO)
Certification N. MED059422CS - (ENG)
Certificate date 23/02/2022
Type Protezione antincendio
Product Sprinkler systems (limited to sprinkler heads)
Item Nº MED/3.28

Model or Denomin.
Items
MW
Applicant MINIMAX SRL
Place of requester VIA RISTORI 31  %  16151 GENOVA  (GE)  % ITALY
Tel. N.,Fax, Email 010 6450004, 010 6450450, minimax@minimax.it
Directive (EU) 2021/1158
Standards EN 12259-1:2007 including A1 (2001), A2 (2004) and A3 (2006).
Reference Documents Reg II-2/7 of SOLAS 74 as amended, Reg II-2/10 of SOLAS 74 as amended, IMO Res.MSC.36 (63)-(1994 HSC Code) 7, IMO Res.MSC.44 (65), IMO Res.MSC.97 (73)-(2000 HSC Code) 7, IMO Res.MSC.98 (73) - (FSS Code) 8, IMO MSC/Circ.912, IMO MSC/Circ. 1556
Request 02/10/2022
Expire date 22/02/2027
EC TYPE-EXAMINATION (MODULE B) ENG
Vuoto Querysave
Giovanni Carratino S

EC TYPE EXAMINATION (MODULE B)
CERTIFICATE No. MED059422CS

This is to certify that RINA Services S.p.A. (Notified Body No. 0474) did undertake the relevant type approval procedures for the equipment identified below, which was found to be in compliance with the Fire Protection requirements of Marine Equipment Directive (MED) 2014/90/EU, including the requirements and testing standards of Regulation (EU) 2021/1158.
MED Item Nº MED/3.28
Description Sprinkler systems (limited to sprinkler heads)
Type MW
Applicant MINIMAX SRL
VIA RISTORI 31,16151 GENOVA (GE),ITALY
Testing standards EN 12259-1:2007 including A1 (2001), A2 (2004) and A3 (2006).
Reference standards Reg II-2/7 of SOLAS 74 as amended, Reg II-2/10 of SOLAS 74 as amended, IMO Res.MSC.36 (63)-(1994 HSC Code) 7, IMO Res.MSC.44 (65), IMO Res.MSC.97 (73)-(2000 HSC Code) 7, IMO Res.MSC.98 (73) - (FSS Code) 8, IMO MSC/Circ.912, IMO MSC/Circ. 1556
Issued in Genoa on
This Certificate is valid until
February 23, 2022
February 22, 2027
This Certificate consists of this sheet plus an attachment

________________________________________
Giovanni Carratino
RINA Services S.p.A.
**** NOTICE: This is NOT an official certificate ****

ATTACHMENT TO
CERTIFICATE No.  MED059422CS
Page 1 of 3
Reference documents

File No.2005CS014251.

Type approval documentation:
  • "MINIMAX SPRINKLER SYSTEM" booklet edited by MINIMAX s.r.l. filed with n° FPE006820 on July 7th, 2005.
  • CSI test report n° DC03/008F05 dated 24/03/2005, CSI test report n° DC03/001/F05 21/02/2005, CSI test report n° DC03/079F04 dated 22/10/2004.

Materials/Components

Pressure tank, fresh and sea water pumps, piping, section alarm valves, spray nozzles, control and monitoring system as described in the Minimax specification booklet.

Technical characteristics

Minimax nozzle to be used in Minimax sprinkler system, are fast response water spray nozzles, with glass bulb element, having a nominal release temperature of 57°C (orange) 68°C (red) 79°C ( yellow) 93°C (Green) , 141 °C (blue),
Nozzles and relevant components are represented on the drawings contained in Minimax s.r.l. booklet filed with n° FPE0006820 on 7/07/2005.
Nozzle designation
Nozzle type

Minimum working pressure
[bar]
Water flow
[l/min]
K factor
Minimax MW
Pendent
0.65
66.8
82,82



ATTACHMENT TO
CERTIFICATE Nr. MED059422CS
Page 2 of 3

Fields of application

Accommodation, public spaces and service areas, including control stations, corridors and staircases, shopping and storage areas of conventional ships and high-speed crafts.

Acceptance conditions

Maximum spacing 3.50 m

Maximum distance from bulkheads 1.75 m

Minimum working pressure 0.65 bar

Maximum installation height from deck 2.70 m


Tests carried out
  • Nozzle tests according to EN 12259 -1 (1999) carried out at the CSI laboratory in Bollate (Milano), Italy and at the manufacturer "CPF INDUSTRIALE S.p.A." in Gussago (Brescia) Italy at the presence of CSI and RINA surveyors.

Remarks

Drawings of each installation shall be approved prior to fitting the system on board. Drawings shall contain, as minimum, the following details and information:
a) schematic arrangement of the system including size and material of piping and method of pipe jointing;
b) specification of the pump unit;
c) wiring diagrams and cable specifications for automatic release system;
d) hydraulic calculations.




ATTACHMENT TO
CERTIFICATE No. MED059422CS
Pages 3 of 3
The mark of conformity may only be affixed to the above type approved equipment and a Manufacturer's Declaration of Conformity issued when the production control phase module (D, E or F) of Annex II of the Directive is fully complied with a written inspection agreement with a Notified Body
XXXX/YY
"WHEELMARK FORMAT"

XXXX
Notified Body number undertaking surveillance module
YY
Last two digits of year mark affixed
     
______________________________________________
General conditions for the approval
a) The initial conditions verified by RINA at the time of the approval are to be maintained
b) Any changes to the initial conditions are to be promptly communicated to RINA, which reserves the right to repeat the relevant assessment
c) This certificate will no be valid if the manufacturer makes any changes or modifications to the approved equipment, which have not been notified to, and agreed with RINA
d) RINA personnel are to be allowed to witness during the performances of activities, upon their request
e) The activities are to be carried out in compliance with the RINA Rules and/or other applicable Rules

f) Should the specified regulations or standards be amended during the validity of this certificate, the product is to be reapproved prior to it being placed on board vessels to which the amended regulations or standards apply. 


__________________________________________
Giovanni Carratino
**** NOTICE: This is NOT an official certificate ****