Generator Protection Module Type GPM 500
Components
Microprocessor based protection of generators and shipboard mains:
- ZM 432; central module
- DCC 500; DC/DC converter
- NEG 500, NEG 501, power supplies
- NEG 510; power supply extension unit
- ZKG 500; ZKG 501; ZKG 505; central PCB
- GOV 500; governor motor control module
- ISO 500, Analoge Input 8 x AI
- DIO 500; digital I/O PCB
- SLE 500A; SLE 501; SLE 520; current and power acquisition module
- TRV 500; TRV 501; TRV 502; TRV 504; TRV 505; isolation amplifier
- DIF 500; differential current detection device
- USS 500; backup for under voltage coil device
- BAT 500/ 501/ 505/ 520 (EXOR & TOP05-D24557"7 SAM); touch-screen display
Protection Functions for:
- Diesel Generators
- Shaft Generators
- Emergency Generators
- Coupler circuit breakers
- Transformers
- Motors
- Shore connection
- Filters
- High-resistance earthing
Protection functions. ANSI Codes
| Short-circuit Protection. | ANSI code : 50 |
Stator Protection | ANSI code : 50S |
Independent/Dependent Over current-time Protection | ANSI code : 51 |
Current Asymmetry. | ANSI code : 46 |
Differential protection. | ANSI code : 87 |
Under voltage | ANSI code : 27 |
Over voltage. | ANSI code : 59 |
Under frequency. | ANSI code : 81L |
Over frequency | ANSI code : 81H |
Reverse power/directional power. | ANSI code : 32 |
Under Load. | ANSI code : 37 |
Under excitation. | ANSI code : 40 |
Check of synchronism. | ANSI code : 25 |
Phase Failure/Phase Sequence | ANSI code : 47 |
Voltage Displacement | ANSI code : 59N |
Earth-fault Current | ANSI code : 50N, 87N, 67N |
Start Attempts | ANSI code : 66 |
Protective Start Blocking | ANSI code : 50LR |
TYPE APPROVAL CERTIFICATE
ELE128423XG
Enclosure - Page2 of 3
Control and Power Management Functions.
- Blackout start
- Automatic start and synchronizing.
- Frequency control.
- Voltage control.
- Active power control incl..
- Symmetrical load sharing
- Asymmetrical load sharing
- Relieving of the generator priority shutdown
- "Top load function"
- Load monitor function (optional)
- Load-dependent start of DG sets
- Load-dependent stop of DG sets
- Load-dependent start of big consumers
Failure detection.
- Start/stop failure.
- Synchronizing failure.
- Breaker failure
- Diesel engine failure.
- Power supply monitoring.
- Flash checksum.
- Eeprom checksum.
- Module failure.
Diesel Protection Module DPM 500
The DPM 500 consist of a modular designed hardware containing the CPU and I/O boards for the necessary periphery connections.
The DPM 500 is responsible for Diesel Sart / Stop with the following functions:
- Diesel Start and Alarm Start
- Diesel Stop with Normal Start, signal contact Stop, Emergency Stop
- Pre Lubricating
- Fuel Limitation
Inputs:
- Speed (from other devices or pick-up sensors)
- Other Criteria (oil pressure. cooling water temp. a.s.o.)
- Line Break Monitoring
- Stop Suppression except Overspeed
Components:
The DPM 500 protection modules:
- NEG 500 / NEG501/NEG510 power supply
- ZKG 500; ZKG 501; central PCB
- SST 500 start/stop module 8 x DI (therefrom 2 pickup); 4 x DO (line break monitoring)
- DIO 500 (Standard I/O)
BAT 500 (EXOR &TOP05-D24557*7SAM); touch-screen display or other
suitable type approved panel (only necessary by a DPM 500 stand-alone
system)
TYPE APPROVAL CERTIFICATE
No. ELE128423XG
Enclosure - Page 3 of 3
Bus Connections to other Systems
- RS-485 Interface with Modbus Protocol
The GPM500 provides an RS485 Interface for the purpose of communication with external systems
The communication between the GPM 500, DPM 500 and the panel BAT500/ 501/ 505/ 520 is realized by using
a CAN Bus interface.
Reference documents
- Generator Protection Module GPM 500 Project Manual Doc. 271.195 999 BG1 EN
Installation Manual xxxBG2 EN, Parameter Setting Manual xxxBG3 EN
- Diesel Protection Module DPM 500, Installation Manual Doc. no. 271.003 885. G6 EN, Manual doc. no. 271.003 885.BG2, Parameter Description doc. 271.003 885.BG3
- Generator Protection Module GPM500, SLE520 Doc. 271.050 826.BG
- Generator/Diesel Protection Module GPM500/DPM500/ZKG505 Doc. 271.060 281 BG
- Modules Hardware Description doc. 271.195 xxx BG
- Branding T7Am DoC (PROD CERT - 1117928 - 1 - A1) - 1
- Datasheet_T7AM_rev_low
- geaps_inst_man_Kap_02_gb
- geaps_oper_man_Kap_05_gb
- geaps_para_man_Kap_03_gb
- geaps_proj_man_Kap_01_en
- Changes on GEAPAS system since 2011
Test Reports:
- SAM Electronics Performance Test Report 09.09.2004 (GPM 500)
- SAM Electronics Performance Test Report 18.01.2011 (DPM 500)
- RMS Test Report No. 01-12/2010; No. 04-08/2004; No. 04-10/2004
- MessTechnikNord GmbH Test-Report No. 06433.202.10 V1.1, No. 05204.046.06, No. 04853.143.04., No. 072777.237.20 V1.0, No. 073155.177.22 V1.0
- Treo, Test Report 296-22
Remarks
Apparatus to be used according to the instructions given by the manufacturer.
This certificate replace the certificate No.: ELE 124416XG