MED360723CSENG- -  -  N- DOUBLE A60 FIRE DOOR SLIDING HEIGHT 3000 mm -N- S- S- -17/10/2023- Marine Equipment- - SN- S- - N-  - 244,549B2bisMarine EquipmentNumero Pratica,Direttiva,Norma,Schema,Richiesta,Validità,EmailR- MED360723CS- N-Oct 16, 2028244549
 
Form
  Marine Equipment(TO)
Certification N. MED360723CS - (ENG)
Certificate date 17/10/2023
Type Protezione antincendio
Product Porte tagliafuoco
Item Nº MED/3.16
USCG Category N° 164.136

Model or Denomin.
Items
DOUBLE A60 FIRE DOOR SLIDING HEIGHT 3000 mm
Applicant NAVAL SUPPLIERS SRL
Place of requester ZONA INDUSTRIALE 24  %  33049 SAN PIETRO AL NATISONE (UD)  % ITALY
Tel. N.,Fax, Email 0432-727860, 0432-727886, firedoors@navalsuppliers.com
Directive (EU) 2023/1667
Standards IMO Res. MSC.307(88)-(2010 FTP Code)
Reference Documents Chap. II-2 of SOLAS 74 Convention, as amended, RINA Rules for the certification of Marine Equipment
Request 9/10/2023
Expire date 16/10/2028
EC TYPE-EXAMINATION (MODULE B) ENG
Vuoto Querysave
Enrico Cabella S

EC TYPE EXAMINATION (MODULE B)
CERTIFICATE No. MED360723CS

This is to certify that RINA Services S.p.A. (Notified Body No. 0474) did undertake the relevant type approval procedures for the equipment identified below, which was found to be in compliance with the Fire Protection requirements of Marine Equipment Directive (MED) 2014/90/EU, including the requirements and testing standards of Regulation (EU) 2023/1667.
MED Item Nº MED/3.16
USCG Category Nº 164.136
Description Fire doors
Type DOUBLE A60 FIRE DOOR SLIDING HEIGHT 3000 mm
Applicant NAVAL SUPPLIERS SRL
ZONA INDUSTRIALE 24,33049 SAN PIETRO AL NATISONE (UD),ITALY
Testing standards IMO Res. MSC.307(88)-(2010 FTP Code)
Reference standards Chap. II-2 of SOLAS 74 Convention, as amended, RINA Rules for the certification of Marine Equipment
Issued in Genoa on
This Certificate is valid until
October 17, 2023
October 16, 2028
This Certificate consists of this sheet plus an attachment

________________________________________
Enrico Cabella
RINA Services S.p.A.
**** NOTICE: This is NOT an official certificate ****

ATTACHMENT TO
CERTIFICATE No.  MED360723CS
Page 1 of 2

Product description

Double leaf sliding door with maximum clear light of 4000x3000 mm (WxH). The door leaves, having maximum dimensions of 2070x3038 mm (WxH) and 2073x3038 mm (WxH), are composed of two carbon steel sheets, 1.2 mm thick each and, in between, the insulating materials, composed of one composite panel named KNAUF PBE FIRE BOARD M18V, 50 mm thick and having density of 180 kg/m3 and one layer of material named PROMAGLAF GM, having thickness of 12.6 mm and density of 165 kg/m3. The insulating materials are glued together and to the steel sheets by means of 500 g/m2 of adhesive type PROMACOL MARINE. The leaves are fitted, inside, with C shaped steel stiffeners, 1.2 mm thick and having dimensions of 60x20 mm tack welded (pitch of 250 mm) symmetrically to the two steel sheets with pitch of 500 mm. Inside the perimeter of the leaf is fitted, on the upper side and on the vertical side opposite to the lock, with an U shaped steel profile, 6 mm thick and having dimensions of 60x30 mm. Outside the perimeter of the leaf is fitted with a C shaped stainless steel profile having thickness of 1.2 mm and dimensions of 64.8x15 mm. The door frame is composed of steel profiles having thickness of 5 mm. The door may be fitted with a self-closing hose port having maximum dimensions of 160x188 mm.

Field of application
Fire resistant A-60 Class double leaf sliding door.
In case of doors in compliance to the "Agreement between the European Community and the United States of America", the present certificate is valid at the following conditions:
- doors without windows or with total window area no more than 645 cm2 in each door leaf
- maximum door size tested
- door used with a fire tested frame design

Reference documents
Naval Suppliers drawings No. FT-SLA62-242418-R0-LC dated 27 July 2018, No. FT-SLA62-242418-R0-LO dated 12 September 2018 and No. FT-SLA61-242417-RINF dated 7 November 2018 approved on 4 October 2018 and on 8 November 2018 respectively with endorsement Nos. LABS-1728, LABS-1729 and LABS-1754. Naval Suppliers drawing No. FT-SLA62-4000x3000 dated 24 August 2023 and identified with No. 2023CS013607.

Tests carried out
Test as per RINA Test Laboratory reports No. 2018CS012348/2 and No. 2018CS012348/4 dated 4 October 2018, No. 2018CS012701/1 and No. 2018CS012701/2 dated 8 November 2018 issued according to IMO 2010 FTP CODE Part 3. Increased dimensions verified with RINA Technical Reports No. 2023-002-MITHP Rev. 0 dated October 2023.




ATTACHMENT TO
CERTIFICATE No. MED360723CS
Pages 2 of 2
The mark of conformity may only be affixed to the above type approved equipment and a Manufacturer's Declaration of Conformity issued when the production control phase module (D, E or F) of Annex II of the Directive is fully complied with a written inspection agreement with a Notified Body
XXXX/YY
"WHEELMARK FORMAT"

XXXX
Notified Body number undertaking surveillance module
YY
Last two digits of year mark affixed
     
______________________________________________
General conditions for the approval
a) The initial conditions verified by RINA at the time of the approval are to be maintained
b) Any changes to the initial conditions are to be promptly communicated to RINA, which reserves the right to repeat the relevant assessment
c) This certificate will no be valid if the manufacturer makes any changes or modifications to the approved equipment, which have not been notified to, and agreed with RINA
d) RINA personnel are to be allowed to witness during the performances of activities, upon their request
e) The activities are to be carried out in compliance with the RINA Rules and/or other applicable Rules

f) Should the specified regulations or standards be amended during the validity of this certificate, the product is to be reapproved prior to it being placed on board vessels to which the amended regulations or standards apply. 


__________________________________________
Enrico Cabella
**** NOTICE: This is NOT an official certificate ****