1. PRODUCT DESCRIPTION:
Float level controller:
Type | UQK-01-C | UQK-01-C-B | UQK-652-C | UQK-652-C-B |
Rated voltage | A.C. 250V | A.C. 250V | A.C. 250V | A.C. 250V |
Rated current | 10A | 10A | 10A | 10A |
Nominal pressure | 1.0MPa | 1.0MPa | 1.0MPa | 1.0MPa |
Medium temperature | <150℃ | <150℃ | <150℃ | <150℃ |
Control range | 10~30mm | 10~30mm | 20~70mm | 20~70mm |
Ingress of protection | IP68 | IP68 | IP68 | IP68 |
Ex marking | - | Ex ia IIC T4~T6 Ga
Ex db IIC T4~T6 Gb | - | Ex ia IIC T4~T6 Ga
Ex db IIC T4~T6 Gb |
Pressure(liquid level) sensor:
Type | YSZK-01G-C | YSZK-01G-C-B | YSZK-01G-C-E | YSZK-01L-C-E |
Power supply | DC 24V±10% | DC 24V±10% | DC 24V±10% | DC 24V±10% |
Output signal | 4~20mA | 4~20mA | 4~20mA | 4~20mA |
Accuracy | ±0.5%F.S | ±0.5%F.S | ±0.5%F.S | ±0.5%F.S |
Anti-overload | 150% | 150% | 150% | 150% |
Ingress of protection | IP66 | IP66 | IP66 | Sensor IP68
Amplifier IP66 |
Working temperature | -20~80℃ | -20~80℃ | -20~80℃ | Sensor -40~125℃
Amplifier -25~55℃ |
Ex marking | - | Ex db IIC T6 Gb | Ex ia IIC T3~T6 Ga | Ex ia IIC T6 Ga
Ex db IIC T6 Gb |
Temperature sensor:
Type | WZPK-22I-C | WZPK-22I-C-B | WZPK-22I-C-E |
Measurement range | -200~500℃ | -200~500℃ | -200~500℃ |
Accuracy class | ±0.5%F.S. | ±0.5%F.S. | ±0.5%F.S. |
Ingress of protection | IP66 | IP66 | IP66 |
Thermal response time | T0.5≤90s | T0.5≤90s | T0.5≤90s |
Output signal | Pt100/4~20mA | Pt100/4~20mA | Pt100/4~20mA |
Ex marking | - | Ex db IIB T1~T6 Gb | Ex ia IIC T4/T6 Ga |
Pressure controller:
Type | YWK-50-C |
Rated voltage | DC 220V | AC 380V |
Rated current | 2.5A | 3A |
Ambient temperature | -25~55℃ |
Ingress of protection | IP44 |
Control range | 0~4MPa |
TYPE APPROVAL CERTIFICATE
No. ELE606926WS
Enclosure - Page 2 of 2
UQK series, YSZK-01 series, WZPK series, YWK series
2. REFERENCE DOCUMENTS:
+ Drawings and specification: Filed by RINA with drawings No. SHMC50306 and SHMC50307.
+ Asbestos-free Declaration: Filed by RINA with drawing No. SHMC50309.
+ Type test outline: Filed by RINA with drawing No. SHMC50310.
+Test report: Filed by RINA with drawing No. SHMC50311.
+ Routine test report witnessed and signed by attending Surveyor, Filed by RINA with drawing No.: SHMC50313.
+ Narrative report: Filed by RINA with drawing No. SHMC50312.
3. NOTE/REMARK:
+ Sensor installation, mechanical arrangement and filter cleaning devices are not part of this approval; relevant acceptance on board will be granted for each specific delivery, follow on board survey.
+ External piping and Ex-certification are not covered by this Type Approval Certificate. Application in hazardous area to be approved in each case according to the Rules and Ex-Certification/Special Condition for Safe Use listed in valid Ex-certificate issued by a recognized Certification Body.
+ Any modification or change shall not be valid until approval is granted by RINA as a result of due assessment.