Certification N. ELE241522CS - (ENG)
Certificate date 27/12/2022
Type Impianti di Automazione
Product Monitoring and Control System for Fire Doors and Fire Dampers

Model or Denomin.
Items
FDMS3
Applicant Martec Marine S.p.A.
Place of requester Via dell'Industria 1/3  %  20052 Vignate (MI)  % ITALY
Tel. N.,Fax, Email +39 342 300 8200 l.bracco.martecmarine.it
Standards RINA Rules for the Classification of Ships - Part C- Machinery, Systems and Fire Protection - Ch.3 , Sect. 6, Table 1
Expire date 02/08/2027
Interrut.senza Dettaglio ENG
Vuoto Querysave
S
TYPE APPROVAL CERTIFICATE
No. ELE241522CS
This is to certify that the product below is found to be in compliance with the applicable requirement of the RINA type approval system.

Description Monitoring and Control System for Fire Doors and Fire Dampers
Type FDMS3
Applicant Martec Marine S.p.A.
Via dell'Industria 1/3
20052 Vignate (MI)
ITALY
Reference standards RINA Rules for the Classification of Ships - Part C- Machinery, Systems and Fire Protection - Ch.3 , Sect. 6, Table 1
  

 
 
   .   This Certificate is valid until August 2, 2027
_________________________________
RINA Services S.p.A.
Luigi Benedetti
This certificate consists of this page and 1 enclosure
**** NOTICE: This is NOT an official certificate ****

TYPE APPROVAL CERTIFICATE
No. ELE241522CS
Enclosure - Page 1 of 3
FDMS3
FDMS3 is a system developed to control and monitoring the fire doors and dampers.
The infrastructure of the FDMS3 System is based on Martec Power Bus 3 (MPB3)
Through the MPB3 technology the FDMS3 system is able to:
- Provide through two wires, redundant power supply and communication
- Ensure that a single failure will not cause a degradation of performance
- Provides a system which may comply with SRTP passenger Ship Regulations
The system comprises:
MPB3-DCU-D Power bus 3 data collecting Unit
FDU3 Fire Door Unit – Fire Damper Unit
SDU3 Single Door Unit – Single Damper Unit
The TOP system is normally made by the ESD system, which via the Ethernet interface with the MPB3-DCU-D
unit, reads the status feedback and executes the commands to doors/dampers.
In addition, the top system can also perform the function of operator interfaces or alternatively provides
information to another system that runs the function.
The field interface is made through the unit MPB3-DCU-D which provides redundant power and
communication to field units.
The field consists of the FDU3 in different configurations depending on the type of door/damper.
MPB3 Technology
The infrastructure of the FDMS3 system is based on MPB3 technology that is developed to power, control
and monitor the field units.
The FDMS3 system has been developed to ensure that a single failure will not cause a degradation of
performance; in particular, the FDU3 receives a redundant power supply and communication.
System architecture is based on two main components, the MPB3-DCU-D (data Collecting Unit)
and the FDU3 – SDU3 (field unit)
MPB3-DCU-D Power Bus Data Collecting Unit (IP20)
Provides an ac/dc power supply, rated input 2A / 230V and 60 Vdc / 500W output.
The input and output are supervised and current limited, moreover the output is provided with a short-circuit
monitoring.
In addition to providing power to the field, the MPB3-DCU-D handles the communication with the field and
with the top system (ESD)
The communication to the field is realized by the OFDM technology which consists in frequency modulation
on the two power supply wires. The field unit are powered redundantly via two MPB3-DCU-D installed in
separate control cabinets.
MPB3-DCU-D can address and supply up to 99 field control units: real limit depending on the power
consumption of the field.
MPB3-DCU-D
Wide range power supply: 85-265 Vac 47-63Hz
Switching power supply with I/O isolation
Short circuit isolator / monitoring
Display of status indication
Communication to field by power line OFDM technology
Ethernet port 10/ 100 Mbit
Field power supply 48 to 60Vdc up to 500W
Fire Door Unit FDU3-A-15W (IP44)
Units for the control and monitoring of the fire door, the same can also be used as a unit of generic I/Os
The unit is connected to two MPB3-DCU-D from which it receives the power supply and communication
based on OFDM modulation frequency.
On the same branch can be connected up to 64 units, this limit must be checked case by case because it
depends on the consumption of the field, the length of the cable and the cable cross section.

TYPE APPROVAL CERTIFICATE
No. ELE282222CS
Enclosure - Page 2 of 3
FDMS3

FDU3-A-15W
Redundant 60Vdc power supply (bus)
Redundant OFDM communication
Branch short circuit isolator
15 Watt isolated DC/DC for field power supply
2 output for solenoid control, incl. open circuit detection / short circuit protection (15W -24Vdc)
6 supervised input , PNP or switch type (24Vdc)
Display for local status indication
Rotary Switch for local configuration
Fire Damper Unit FDU3-C-15W (IP66) and FDU3-E-15W (IP66)
Units for the control and monitoring of the fire damper. A unit can control 2 fire dampers.
The units are connected to two MPB3-DCU-D from which it receives the power supply and communication
based on OFDM modulation frequency.
On the same branch can be connected up to 64 units, this limit must be checked case by case because it
depends on the consumption of the field, the length of the cable and the cable cross section.
FDU3-C-15W with local release
FDU3-E-15W without local release
Redundant 60Vdc power supply (bus)
Redundant OFDM communication
Branch short circuit isolator
15 Watt isolated DC/DC power supply for field
2 powered digital output with short circuit protection / indication (15W - 24Vdc)
4 supervised digital input, (PNP - 24Vdc / switch contact)
RGB LED for damper feedback position
Display for local status indication
Rotary Switch for local configuration
Fire damper Unit FDU3-D-10F (IP66)
Unit for the indication of the local position of 10 fire damper and for the ESD command
The unit is connected to two MPB3-DCU-D from which it receives the power supply and communication based
on OFDM modulation frequency.
On the same branch can be connected up to 64 units, this limit must be checked case by case because it
depends on the consumption of the field, the length of the cable and the cable cross section.
FDU3-D-10F fire Damper feedback
Redundant 60Vdc power supply
Redundant OFDM communication
Branch short circuit insulator
Membrane keyboard with close activation, reset close activation and lamp test.
10 RGB led for damper position indication
Rotary Switch for local configuration
Display for local status indication
Local release (membrane keyboard)
SDU3-C-10W Single Fire Damper Unit (IP66)
Unit for the control and monitoring of one damper.
The unit is connected to two MPB3-DCU-D from which it receives the power supply and communication based
on OFDM modulation frequency.
On the same branch can be connected up to 64 units, this limit must be checked case by case because it
depends on the consumption of the field, the length of the cable and the cable cross section.





TYPE APPROVAL CERTIFICATE
No. ELE282222CS
Enclosure - Page 3 of 3
FDMS3

SDU3-C-10W with local release
SDU3-E-10W without local release
Redundant 60Vdc Power supply (bus)
Redundant OFDM communication
Branch short circuit isolator
10 Watt isolated DC/DC power supply for field
2 digital input (24Vdc contact switch)
1 digital output with short circuit protection / indication (10W 24Vdc)
RGB LED for damper feedback position
Display for local status indication
Control and monitoring of one damper actuators
Rotary Switch for local configuration
SDU3-B-5W-M Single Fire Door Unit (IP44)
Unit for the control and monitoring of the fire door.
The unit is connected to two MPB3-DCU-D from which it receives the power supply and communication based
on OFDM modulation frequency.
On the same branch can be connected up to 64 units, this limit must be checked case by case because it
depends on the consumption of the field, the length of the cable and the cable cross section.
SDU3-B-5W-M Single Fire Door Unit
Redundant 60Vdc Power supply (bus)
Redundant OFDM communication
Branch short circuit isolator
6 Watt isolated DC/DC power supply for solenoid and feedback
Magnet (24Vdc)
Display for local status indication
Door interface:
Magnet power 2x 2W
Door position feedback PNP proximity 24Vdc with supervision
Local release 2 x free contact
Free digital input PNP proximity 24Vdc with supervision

Technical documents:
60-0213-1-DSH Rev. R1.0 MPB3-DCU
60-0208-10-DSH Rev. R1.0 SDU-3-E-10W
60-0208-9-DSH Rev. R1.1 SDU-3-C-10W
60-0208-7-DSH Rev. R1.1 FDU3-D-10F
60-0208-6 DSH Rev. R1.2 FDU3-E-15W
60-0208-5-DSH Rev. R1.1 FDU3-C-15W
60-0208-4-DSH Rev. R1.1 FDU3-A-15W
60-0208-1-DSH Rev. R1.2 SDU3-B-5W-M
60-0122- FMEA Rev. 0.0
FDMS3 Type Approval Test Specification Rev. 1.1
60-0208-1006-DVR Rev. 1.0

TesLab test reports:
211045A-a; 211045A-b; 211045A-c; 211045A-d; 211045F-a; 211045F-b 2021/03/18

The present certificate annuls and replaces the previous ELE072121CS dated 08/04/2021

Genoa 27/12/2022