ELE052224XG!004ENG- -  -  N- QTVR Series -N- S- S- -03/04/2024- Prodotti Elettrici- - SN- N- Giuseppe Russo- N-  - 1,051,913Giuseppe RussoBbisProdotti ElettriciNumero Pratica,NumDich,Norma,NumBusta,Richiesta,Validità- ELE052224XG/004- N-Apr 2, 20291051913
 
Form
  Prodotti Elettrici(TO)
Certification N. ELE052224XG/004 - (ENG)
Certificate date 03/04/2024
Type Impianti Elettrici
Product ELECTRIC TRACE HEATING SYSTEM

Model or Denomin.
Items
QTVR Series
Applicant nVent Thermal Belgium - nVent Thermal Belgium NV
Place of requester Romeinse straat 14  %  3001 Leuven  % BELGIUM
Tel. N.,Fax, Email ---, ---, Gerry.DeBlick@nVent.com
Standards RINA-Rules for the Classifications of Ships.
Expire date 02/04/2029
Head Office HAMBURG
Interrut.senza Dettaglio ENG
Vuoto Querysave
S
TYPE APPROVAL CERTIFICATE
No. ELE052224XG/004
This is to certify that the product below is found to be in compliance with the applicable requirement of the RINA type approval system.

Description ELECTRIC TRACE HEATING SYSTEM
Type QTVR Series
Applicant nVent Thermal Belgium - nVent Thermal Belgium NV
Romeinse straat 14
3001 Leuven
BELGIUM
Reference standards RINA-Rules for the Classifications of Ships.
  

 
 
   .   This Certificate is valid until April 2, 2029
_________________________________
RINA Services S.p.A.
Giuseppe Russo
This certificate consists of this page and 1 enclosure
**** NOTICE: This is NOT an official certificate ****

TYPE APPROVAL CERTIFICATE
No. ELE052224XG/004
Enclosure - Page 1 of 2
QTVR Series
General description:

The QTVR Range of Trace Heating Units is of the parallel circuit self-regulating type, rated at 230 V
with power output up to 64W/m. The units have a maximum self-limiting temperature of 110°C.

Each trace heating units comprises:
- The active heating cable
- An end seal for terminating the remote end of the unit
- A cable gland for connecting the powered end of the unit to a suitable terminal enclosure , or alternative integrated power connection system.
The active heating cable comprises two stranded copper conductors around which is extruded a semi-conductive core material.
This core material increases in resistance with increasing temperature and gives cable its self-limiting property.
The core is covered with an extruded layer of fluoropolymer insulation before being overbraided with tinned copper.
A further protective, anti-corrosion layer of fluoropolimer is extruded over the braid.

The declared maximum withstand temperature for the range is 110°C and the minimum installation temperature is -60°C.


Cable Accessories:

END SEALS
The end seals for terminating the remote end of the unit may be the following types:
-Type E-100-L-x or E-100-x, which are mechanical end seal incorporating an end cap which is filled with silicone grease sealant
-Type E-20, which comprises heat shrink sleeves lined with hot melt adhesive
-Type E-150 mechanical end seals


SPLICES AND JOINT
The following splicing and jointing arrangement are provided
- A Raychem Type S-20 heat shrink splice kit for connecting lengths of active heating cable.
- A Raychem T-100 tee connection system
- Type S-150 mechanical splice kit


POWER CONNECTION
Power connection may be achieved by the following means:
-Type C25-21. The kits may use a molded silicone rubber core seal to insulate the bus wires with silicone grease in a molded cavity to seal the end of the heating cable.
In this arrangement the kits are Types C25-100 and C16-100
-Type C25-100-Metal, C25-100-Metal-NP, C25-100-Metal-SS, C3/4-100-Metal, C3/4-100-Metal-NP, C3/4-100-Metal-SS, which incorporate a type E8XF metallic cable gland
-Type C-150 power connector
-Type JBS-100 power connection system for a single heater cable
-Type JBM-100 power connection system for multiple heater cables
-Type JBU-100 power connection system
-Type CCON connection kit










TYPE APPROVAL CERTIFICATE
No. ELE052224XG/004
Enclosure - Page 2 of 2
QTVR Series


Special Conditions for Safe Use:

The following limiting temperatures for the end seals , splices and power connections shall not be exceeded:


110°C for the GHG 960 923 p… cable gland S-20, E-20 and CCON


The end seal, splices and power connections have the following associated minimum ambient temperatures:

-55°C for the CCON ;
-50°C for the E-100-x, E-100-L-x , E-150, S-150, C-150, JBS-100, JBU-100 and JBM-100 _
-40°C for the JBS-100-L, JBM-100-L, T100, JBU-100-L,
-55°C for the GHG 960 923 P… cable gland with silicon rubber seals C25-100 and C25-21
-60°C for the type E8XF cable gland, S-20, E-20, C25-100-Metal, C25-100-Metal-NP, C25-100-Metal-SS, C3/4-100-Metal, C3/4-100-Metal-NP, C3/4-100-Metal-SS

Minimum bending radius is 35mm for the type QTVR units.


Thermal output rating: 38 to 64 W/m at 10° C and 230 V


Reference documents:

- ATEX Certificate

Certification Authority: SGS Fimko Oy, Takomotie 8, FI-00380 Helsinki, Finland

Certificates: SGS20ATEX0050X - Isue2

Marking:
II 2 GD Ex 60079-30-1 eb IIC T4 Gb Ex 60079-30-1 eb mb IIC T4 Gb Tmin -60° C or
II 2 GD Ex 60079-30-1 tb IIIC T130°C Ex 60079-30-1 mb tb IIIC T130°C Db

Safety Standard:
EN60079-0: 2018 ; EN60079-7:2015+A1:2018 ; EN60079-18:2015+A1:2017 ; EN60079-30-1:2017
EN60079-31:2014

- Data Sheet: Raychem-DS-EU1381-QTVR-EN


Remarks:
The Information listed in the present certificate are partial information based on the Baseefa Certificates.
The component listed in this Certificate are to be used / installed according to the manufacturer instructions:
Special conditions for safe use and installation to be in accordance with the above referenced ATEX Certificates.

The certificate supersedes previous RINA certificate No. ELE065119XG/004.

HAMBURG April 3, 2024
**** NOTICE: This is NOT an official certificate ****