Mobile Water Monitor is used for Protection of On Deck Container Stacks, in accordance with Reg.II-2/10.7.3.2 of SOLAS '74 as amended.Technical Data
Main Components: Inlet fitting, Monitor waterway, Swivel fittings, Discharge nozzle and a shut-off device, Carrying handle.
Nominal Capacity: 60 m3/h (1000 L/min) @ 0.4 Mpa
Nominal Working Pressure: 0.4 Mpa
Maximum Working Pressure: 1.0 Mpa
Nominal Throw Length: 40 meters @ 0.4 Mpa
Pivoting Area: Horizontal, 270 °; Vertical, 0 ° to 90 °
Weight: ≤ 23 Kg
Nozzle Type: Dual-purpose Spray/Jet
Water Inlet Dimension: DN50
Corrosion Resistant Materials: SS316 & Anti-corrosion Copper AlloyReference Document
The design assessment is based on IMO Resolution MSC.365(93) with following documents:
- Instruction Manual, filed by RINA with No.: SHFP-26942;
- Bill of Material, filed by RINA with No.: SHFP-26944;
- Technical Drawing of Mobile Water Monitor, approved by RINA with No.: SHFP-26945;
- Technical Specification, filed by RINA with No.: SHFP-26946;
- Marking, filed by RINA with No.: SHFP-26947.Production and Tests
The production must be carried out in accordance to the manufacturer quality production system.
Tests has been carried out and witnessed by RINA Surveyor in compliance with IMO MSC.1/Circ.1472 (Guidelines for the design, performance, testing and approval of mobile water monitors used for the protection of on-deck cargo areas of ships designed and constructed to carry five or more tiers of containers on or above the weather deck). Relevant test report has been filed by RINA with No.: SHFP-26949. Remark
Mobile Water Monitors should be equipped with a coupling allowing connection to the ship's fire hydrants by fire hoses. The coupling should be sized so as to ensure that the flow and pressure needed for correct performance will be provided.
The manufacturer's operating guidelines includes information on the safe operation of the monitors to be observed.