MED381326CS!003ENG- -  -  N- MD9908 -N- S- S- -21/06/2026- Marine Equipment- - SN- S- - N-  - 840,487B2bisMarine EquipmentNumero Pratica,Direttiva,Norma,Schema,Richiesta,Validità,EmailR- MED381326CS/003- N-Jun 21, 2031840487
 
Form
  Marine Equipment(TO)
Certification N. MED381326CS/003 - (ENG)
Certificate date 21/06/2026
Type Protezione antincendio
Product Fixed fire detection and fire alarm systems components for control stations, service spaces, accommodation spaces, cabin balconies, machinery spaces and unattended machinery spaces: (g) Short circuit isolators
Item Nº MED/3.51g

Model or Denomin.
Items
MD9908
Applicant MICRODATA DUE - SOCIETA' A RESPONSABILITA' LIMITATA
Place of requester VIA GRETI DEL VARA 9  %  19020 Follo (SP)  % ITALY
Tel. N.,Fax, Email 0187 599101, 0187 558983, d.dido@microdatasrl.it
Directive (EU) 2025/1533
Standards EN 54-17 (2005) including AC(2007),IEC 60092-504:2016,IEC 60533: (2015)
Reference Documents SOLAS 74 Reg.II-2/7, SOLAS 74 Reg.X/3, IMO Res.MSC.36(63)-(1994 HSC Code) 7, IMO Res.MSC.97(73)-(2000 HSC Code) 7, IMO Res.MSC.98(73)-(FSS Code) 9, IMO Res.MSC.391(95)-(IGF Code) 11, IMO MSC/Circ.1242.
Expire date 21/06/2031
EC TYPE-EXAMINATION (MODULE B) ENG
Vuoto Querysave
Chiara Boscolo S

EC TYPE EXAMINATION (MODULE B)
CERTIFICATE No. MED381326CS/003

This is to certify that RINA Services S.p.A. (Notified Body No. 0474) did undertake the relevant type approval procedures for the equipment identified below, which was found to be in compliance with the Fire Protection requirements of Marine Equipment Directive (MED) 2014/90/EU, including the requirements and testing standards of Regulation (EU) 2025/1533.
MED Item Nº MED/3.51g
Description Fixed fire detection and fire alarm systems components for control stations, service spaces, accommodation spaces, cabin balconies, machinery spaces and unattended machinery spaces: (g) Short circuit isolators
Type MD9908
Applicant MICRODATA DUE - SOCIETA' A RESPONSABILITA' LIMITATA
VIA GRETI DEL VARA 9,19020 Follo (SP),ITALY
Testing standards EN 54-17 (2005) including AC(2007),IEC 60092-504:2016,IEC 60533: (2015)
Reference standards SOLAS 74 Reg.II-2/7, SOLAS 74 Reg.X/3, IMO Res.MSC.36(63)-(1994 HSC Code) 7, IMO Res.MSC.97(73)-(2000 HSC Code) 7, IMO Res.MSC.98(73)-(FSS Code) 9, IMO Res.MSC.391(95)-(IGF Code) 11, IMO MSC/Circ.1242.
Issued in Genoa on
This Certificate is valid until
June 21, 2026
June 21, 2031
This Certificate consists of this sheet plus an attachment

________________________________________
Luigi Benedetti
RINA Services S.p.A.
**** NOTICE: This is NOT an official certificate ****

ATTACHMENT TO
CERTIFICATE No.  MED381326CS/003
Page 1 of 2
MD9908 Automatic, Addressable, Analogue heat detector :
Main features:

MD 9908 detector consists of two parts:
- The sensor, (IP67) to be installed in the room to be monitored
- The Loop Interface Box, (IP 66) also includes short circuit isolator and LED Fire signaling
(to be mounted outside of the monitored space)
Sensors and Interface box are connected each other with a 30 meters maximum length cable
- Fire alarm for high temperature
- Monitoring of the temperature inside the room where it is installed
- Send to the Central Unit the temperature analogue values
- Short circuit isolator functionality

MD9908 IP66 Loop interface and IP 67 Heat detector F Class; Alarm threshold: 129°C to +145°C
The detector continuously monitors the thermistor component and is able to provide a fault signalization in case of sensor failure.
The communication through the loop with Central Unit is performed by control cards, which provide to the detectors
the 24Vdc power supply on which a serial transmission signal using MD2 protocol is modulated
If an alarm is detected an optical signalization (red LED) on the Interface Box housing flashes.

Flame addressable interface board p.n. FD-PP
The FD-PP board is a gateway designed to interface Microdata Due MD99xx-series detector with the Consilium system. It communicates with the Microdata detector using the same physical layer and protocol as Microdata systems, then converts and makes this information available to the Consilium system using the appropriate physical layer and Consilium protocol.
The FD-PP board PN 28063 is an interface board that included a short circuit isolator.
The FD-PP board will be used in conjunction with the heat detectors made by Microdata Due model MD9907-A1/B/ C – PN 29261-A1 /B/C

Microdata Due specifications:
Technical Specification: ELET/44862 ST36605 rev. B
Datasheet: ELET/44863 D35545 rev. D
Software description: ELET/44837 SDD36634 rev. 0
FD-PP Software Assessment ELET/45068 D37779 Rev. 0
Risk Assessment: ELET/44865 D36691 rev. 0
FD-PP-B Board dwg. ELET/45063 AS-28063-20001
FD-PP Board Assembly dwg. ELET/45064 AS-28063-20002
FD-PP Part List ELET/45065 AS-28063-20003
FD-PP Board PCB dimension ELET/45066 PC-28064-10015
FD-PP Board Label ELET/45067 ME-29035
Statement: FD-PP board addtion to certificate No. MED381326CS/003 and No. MED381326CS/004 (ELET/45072)

Test Reports:
BRE GLOBAL Ltd Test Report n. TE-P103830-1001 rev. 02 (RINA Id. ELET/44799)
TesLab No:
- 166117E-d (05/09/2016 - RINA Id. ELET/44805) (RINA Rules – Pt C, Ch 3, Sec 8)
- 17B302E-b RINA Id. ELET/44795 - EMC _ EN60092-504: 2016 2
- 172048F-a (22/08/2017 - RINA Id. ELET/45070); FD-PP; UNI-EN 54-17
- 17B295E (22/11/2017 - RINA Id. ELET/45071); FD-PP; EN 60092-504 EMC







ATTACHMENT TO
CERTIFICATE No. MED381326CS/003
Pages 2 of 2
The mark of conformity may only be affixed to the above type approved equipment and a Manufacturer's Declaration of Conformity issued when the production control phase module (D, E or F) of Annex II of the Directive is fully complied with a written inspection agreement with a Notified Body
XXXX/YY
"WHEELMARK FORMAT"

XXXX
Notified Body number undertaking surveillance module
YY
Last two digits of year mark affixed
     
______________________________________________
General conditions for the approval
a) The initial conditions verified by RINA at the time of the approval are to be maintained
b) Any changes to the initial conditions are to be promptly communicated to RINA, which reserves the right to repeat the relevant assessment
c) This certificate will no be valid if the manufacturer makes any changes or modifications to the approved equipment, which have not been notified to, and agreed with RINA
d) RINA personnel are to be allowed to witness during the performances of activities, upon their request
e) The activities are to be carried out in compliance with the RINA Rules and/or other applicable Rules

f) Should the specified regulations or standards be amended during the validity of this certificate, the product is to be reapproved prior to it being placed on board vessels to which the amended regulations or standards apply. 


__________________________________________
Luigi Benedetti
**** NOTICE: This is NOT an official certificate ****