Single leaf sliding door having maximum clear opening size of 5000 mm (W) and 5000 mm (H). The door leaf, having maximum height of 5128 mm and maximum width of 5188 mm, is composed of two parts vertically joined together, by means of a tongue and groove joint which is insulated with strips of PROMATECT H having, each, thickness of 6 mm. The leaf is composed of two steel sheets, 1.5 mm thick each and, in between, the insulating material composed of Neptune sandwich panels having thickness of 47 mm. Such panels consist of three layers of a glass fibre reinforced compound, 2.5 mm thick each, and, in between, two layers of mineral wool which are glued to the steel sheets by means of glue named "Glue K84". The door frame is composed of steel profiles having thickness of 2.5, 3 and 5 mm. The door may be fitted with hose port having maximum dimensions of 220 (W) x 160 (H) mm.
Field of application Fire resistant single leaf A-60 Class sliding door. For doors exceeding 50% in surface area (15 m2) with respect to the tested doors (2585 x 3887 mm), the installation on board has to be submitted, on a case-by-case basis, also to a full analysis based on Solas Regulation II-2/17 (alternative design).
In case of doors in compliance to the "Agreement between the European Community and the United States of America", the present certificate is valid at the following conditions:
- doors without windows;
- maximum door size tested;
- door used with a fire tested frame design.
Reference documents Podszuck drawings enclosed to DANAK Test reports No. PG12278 and No. PG12212 dated respectively 15 November 2010 and 27 August 2010 and drawing No. P-10-1304.002.04 dated 2 October 2013 approved on 2 October 2013 with endorsement No. LABS-827.
Tests carried out Tests as per:
- DANAK Test reports No. PG12278 dated 15 November 2010 and No. PG12212 dated 27 August 2010 issued according to IMO Resolution A.754(18);
- DANAK assessment No. PH13633 dated 28 February 2011;
- RINA Technical Report TR No. 2013/005/TCHD dated 18 September 2013.
This Certificate annuls and replace the previous one No. MED036519CS dated 05/02/2019. |