Transits of electric cables, having maximum diameter of 54 mm, installed in A-Class steel bulkheads. These transits are composed of an “omega” shaped perforated steel sheet frame, 0.9 mm thick, applied on the edges of the bulkhead plating aperture. The frame is filled with one layer of mattress manufactured from alkaline earth silicate fibers THERMAL CERAMICS type Superwool Plus Blanket having density 128 kg/m3 and thickness 25 mm, and one layer of mineral wool ROCKWOOL type SEAROX SL 480 having nominal density of 200 kg/m3 and nominal thickness of 30 mm. The mattress manufactured from alkaline earth silicate fibers is coated by means of a layer of product named NAVYCROSS (density of 600 kg/m3), applied with a thickness of 40 mm, for a width of 40 mm all around the mattress. On the side coated with NAVYCROSS, the electric cables are covered all around, for a length of 80 mm, with a layer of NAVYCROSS having thickness of 15 mm. On the side opposite of the alkaline earth silicate fibers coated by means of a layer of NAVYCROSS, it is installed for a width of 40 mm by pins and washers, on the perimeter of the steel plate aperture, one layer of mineral wool ROCKWOOL type SEAROX SL 620 having thickness of 60 mm and nominal density of 100 kg/m3.
Field of application
Fire resistant A-60 cable transits through steel bulkheads, as per following table:
Transit dimensions (mm) | Minimum fill % | Maximum fill % | Cables - Maximum diameter (mm) |
100x80 | 0.98 | 29.59 | 54 |
from 100x80
up to 450x240 | 0.98 | 12.19 | 54 |
450x240 | 0.09 | 12.19 | 54 |
Reference documents
Marinoni SpA drawings No. Dwg 12-23, Rev. 02, dated 30 October 2024 enclosed to RINA Test Laboratory report No. 2023CS014360/1, No. Dwg 01-24, Rev 02, dated 30 October 2024 enclosed to RINA Test Laboratory report No. 2023CS014360/2 and No. Dwg 02-24, Rev 01, dated 30 October 2024 enclosed to RINA Test Laboratory report No. 2024CS012692.
Tests carried out
Tests as per RINA Test Laboratory Report No. 2023CS014360/1, RINA Test Laboratory Report No. 2023CS014360/2 and RINA Test Laboratory Report No. 2024CS012692 issued on 15 November 2024 according to Appendix 1 of IMO 2010 FTP Code Part 3 - A.IV Cable Transits. |