ELE331621XGENG- -  -  N- Series S200 P -N- S- S- -12/01/2022- Prodotti Elettrici- - SN- N- Giuseppe Russo- N-  - 865,304Giuseppe RussoBbisProdotti ElettriciNumero Pratica,NumDich,Norma,NumBusta,Richiesta,Validità- ELE331621XG- N-Jan 11, 2027865304
 
Form
  Prodotti Elettrici(TO)
Certification N. ELE331621XG - (ENG)
Certificate date 12/01/2022
Type Impianti Elettrici
Product INTERRUTTORI AUTOMATICI

Model or Denomin.
Items
Series S200 P
Applicant ABB STOTZ-KONTAKT GMBH
Place of requester EPPELHEIMER STR. 82 69123 HEIDELBERG - GERMANY
Tel. N.,Fax, Email 0049 6221701501, 0049 6221701449, ---
Standards IEC 60947-2
Expire date 11/01/2027
Head Office HAMBURG
Interrut.senza Dettaglio ENG
Vuoto Querysave
S
TYPE APPROVAL CERTIFICATE
No. ELE331621XG
This is to certify that the product below is found to be in compliance with the applicable requirement of the RINA type approval system.

Description CIRCUIT BREAKERS
Type Series S200 P
Applicant ABB STOTZ-KONTAKT GMBH
EPPELHEIMER STR. 82 69123 HEIDELBERG
GERMANY
Reference standards IEC 60947-2
  

 
 
   .   This Certificate is valid until January 11, 2027
_________________________________
RINA Services S.p.A.
Giuseppe Russo
This certificate consists of this page and 1 enclosure
**** NOTICE: This is NOT an official certificate ****

TYPE APPROVAL CERTIFICATE
No. ELE331621XG
Enclosure - Page 1 of 1
Series S200 P
Components
  • Circuit breakers S200 P series, B,C,D,K,Z characteristic, 1/1+N/2/3/3+N/4 poles.
S20 a P b c d :
a: number of poles (1,2,3,4)
b: devices with neutral pole (+NA)
c: characteristics (B,C,D,K,Z)
d: rated current (0.2 to 63)
Circuit breaker type

S200 P
Rated Voltage (Ue)
V
230/400 (1 pole); 230 (1+N pole); 400 (2 to 4 poles)
Characteristics

B
C/D
K/Z
B/C/D/K/Z
B/C/D/K/Z
Rated Current (Iu)
A
6-25
0.5-25
0.2-25
32-40
50-63(*)
Ambient Temperature
°C
55
55
25
B/C/D: 55°C
K/Z: 25°C
B/C/D: 55°C
K/Z: 25°C
Rated Frequency
Hz
50-60
50-60
50-60
50-60
50-60
Service short-circuit breaking capacity (Ics)
kA
12.5
12.5
12.5
11.25
7.5
Ultimate short-circuit breaking capacity (Icu)
kA
25
25
25
15
15
Power Factor

0.25
0.25
0.25
0.3
0.3
Utilization Category

A
A
A
A
A
(*) 63 A only for 1; 1+N; 2 poles.

Documents
  • CB Test Reports from n° 70000-4402-0008/38480-1 to n° 70000-4402-0008/38480-33.
  • CB Test Reports from n° 70000-4402-0008/83080-1 to n° 70000-4402-0008/38480-52.
  • CB Test Reports from n° 70000-4402-0009/70366-1 to n° 70000-4402-0009/70366-40.
  • CB Test Report n° 70000-4402-0009/272347-TL3-1.
  • CB Test Certificate DE1-63765
  • Index_CB 34621 + CCA 33216
  • Technisches Datenblatt_S200
  • Testreport-194678-CC2-1




This certificate is the subsequent of N° ELE210716XG.

HAMBURG January 12, 2022
**** NOTICE: This is NOT an official certificate ****