MED418326CSENG- -  -  N- Smoke and Heat detector (A1 Class):,MD9910 with TOD, Integrated Sounder and Obstruction detector,MD9910-LT with Integrated Sounder and not including TOD and Obstruction detector,MD9910-LTNB not including TOD, Integrated Sounder and Obstruction detector,In conjunction with fire detector bases:,MD9900-BS, MD9900-BSI, MD9910-LP, MD9900-BC, MD9900-BCI -N- S- S- -17/07/2026- Marine Equipment- - SN- S- - N-  - 840,487BMarine EquipmentNumero Pratica,Direttiva,Norma,Schema,Richiesta,Validità,EmailR- MED418326CS- N-May 31, 2030840487
 
Form
  Marine Equipment(TO)
Certification N. MED418326CS - (ENG)
Certificate date 17/07/2026
Type Protezione antincendio
Product Fixed fire detection and fire alarm systems components for control stations, service spaces, accommodation spaces, cabin balconies, machinery spaces and unattended machinery spaces: (c) Heat detectors - Point detectors
Item Nº MED/3.51c

Model
Items/Sizes
Smoke and Heat detector (A1 Class):,MD9910 with TOD, Integrated Sounder and Obstruction detector,MD9910-LT with Integrated Sounder and not including TOD and Obstruction detector,MD9910-LTNB not including TOD, Integrated Sounder and Obstruction detector,In conjunction with fire detector bases:,MD9900-BS, MD9900-BSI, MD9910-LP, MD9900-BC, MD9900-BCI
Applicant MICRODATA DUE - SOCIETA' A RESPONSABILITA' LIMITATA
Place of requester VIA GRETI DEL VARA 9  %  19020 Follo (SP)  % ITALY
Tel. N.,Fax, Email 0187 599101, 0187 558983, d.dido@microdatasrl.it
Directive (EU) 2025/1533
Standard EN 54-5:2017 incl. A1:2018, IEC 60092-504:2016, IEC 60533:2015.
Reference Documents SOLAS 74 Reg. II-2/7,SOLAS 74 Reg. X/3,IMO Res. MSC.36(63)-(1994 HSC Code) 7,IMO Res. MSC.97(73)-(2000 HSC code) 7,IMO Res. MSC.98(73)-(FSS Code) 9,IMO Res. MSC391(95)-(IGF Code) 11,IMO MSC.1/Circ 1242,RINA Rules for the certification of Marine Equipment
Validity 31/05/2030
EC TYPE-EXAMINATION (MODULE B) ENG
Vuoto Querysave
S
EC TYPE EXAMINATION (MODULE B)
CERTIFICATE No. MED418326CS
This is to certify that RINA Services S.p.A. (Notified Body No. 0474) did undertake the relevant type approval procedures for the equipment identified below, which was found to be in compliance with the Fire Protection requirements of Marine Equipment Directive (MED) 2014/90/EU, including the requirements and testing standards of Regulation (EU) 2025/1533.

MED Item Nº MED/3.51c
Description Fixed fire detection and fire alarm systems components for control stations, service spaces, accommodation spaces, cabin balconies, machinery spaces and unattended machinery spaces: (c) Heat detectors - Point detectors
Type Smoke and Heat detector (A1 Class): MD9910 with TOD, Integrated Sounder and
Obstruction detector MD9910-LT with Integrated Sounder and not including TOD
and Obstruction detector MD9910-LTNB not including TOD, Integrated Sounder and
Obstruction detector In conjunction with fire detector bases: MD9900-BS,
MD9900-BSI, MD9910-LP, MD9900-BC, MD9900-BCI

Applicant MICRODATA DUE - SOCIETA' A RESPONSABILITA' LIMITATA
Testing standards EN 54-5:2017 incl. A1:2018, IEC 60092-504:2016, IEC 60533:2015.
Reference standards SOLAS 74 Reg. II-2/7; SOLAS 74 Reg. X/3; IMO Res. MSC.36(63)-(1994 HSC Code) 7; IMO Res. MSC.97(73)-(2000 HSC code) 7; IMO Res. MSC.98(73)-(FSS Code) 9; IMO Res. MSC391(95)-(IGF Code) 11; IMO MSC.1/Circ 1242; RINA Rules for the certification of Marine Equipment
  

 
 
The mark of conformity may only be affixed to the above type approved equipment and a Manufacturer's Declaration of Conformity issued when the production control phase module (D, E or F) of Annex II of the Directive is fully complied with a written inspection agreement with a Notified Body
   .   This Certificate is valid until May 31, 2030
_________________________________
RINA Services S.p.A.
Luigi Benedetti
This Certificate consists of this sheet plus an attachment
**** NOTICE: This is NOT an official certificate ****

EC TYPE EXAMINATION (MODULE B)
CERTIFICATE No. MED418326CS
Enclosure - Page 1 of 1
Smoke and Heat detector (A1 Class): MD9910 with TOD, Integrated Sounder and Obstruction detector MD9910-LT with Integrated Sounder and not including TOD and Obstruction detector MD9910-LTNB not including TOD, Integrated Sounder and Obstruction detector In conjunction with fire detector bases: MD9900-BS, MD9900-BSI, MD9910-LP, MD9900-BC, MD9900-BCI
Alternative Manufacturer
UNIPOS LTD

Alternative Place of Manufacturer
47 SAN STEFANO STR
5800 PLEVEN Pleven
BULGARIA


Product information:
Product:
Combined Smoke and Heat detector (MD9910, MD9910-LT, MD9910-LTNB)

Description

MD9910 automatic analogue addressable multi-criteria combined Smoke and Heat Detector suitable for indoor installation.
The detector MD9910 is provided with a new feature named TOD (test on demand) that runs a test procedure on a command received by the Control Unit.
The TOD checks the following circuits:

- Functionality of the IR detection chain: The functionality of the smoke measurement is fully tested. The test result is transmitted to the control panel.
- Functionality of the built in Sounder: The sound pressure level generated by the Sounder is monitored to verify the correct acoustic level. The test result is transmitted to the control panel
- Functionality of the Alarm LEDs: The correct functionality of the alarm LEDs is verified. The test result is transmitted to the control panel.
- Functionality of the temperature detector: The temperature circuit is tested by forcing a thermal alarm. The test result is transmitted to the control panel.
- Functionality detecting obstructions in front of the detector: Sensor enclosure protection is detected as well as any obstacles nearby the sensor preventing the passage of smoke. The test result is transmitted to the control panel.

Note:
It can be assumed that the T.O.D. test procedure provides diagnostic results comparable with the ones obtained by manual test simulation performed locally by the operator.
The MD9910 detector can also be supplied without the TOD (Test On Demand) functionality in two versions that differ in the presence (MD9910-LT) and absence (MD9910-LTNB) of the integrated sounder.















Rating and main characteristics:

Protection Index with base MD9910-LP IP22
Protection Index with base MD9900-BS/BSI IP44
Sounder type Type A
Sound Max output 81dB(A)@1mt
Sound nominal output 75dB(A)@1mt
Frequency 2400 Hz
Weight (detector only) 125 gr
Weight (with LP base) 180 gr
Weight (with BS/BSI base) 280 gr
Material Polycarbonate Flame Retarded CI. UL94V0
Colour White RAL9010
Operating Temperature - 25°C / +75°C
Power Supply 24Vdc (modulated)
Max Current 350 uA
Max Current with Sounder on 550 uA

MD 9910 heat detector according to Class A1 according to EN 54-5:2017

Detector main features:

- provide fire alarm for smoke presence
- provide fire alarm for high temperature
- survey the temperature inside the room where it is installed
- transmit to central Unit the analogue values of temperature and smoke that it measures
- perform, on demand, a test procedure named TOD (Test On Demand)
- notify the alarm state by the activation of the built-in Sounder
- notify the alarm by activation of two high intensity LEDs visible at 360° by means of light guides
- detect the presence of an obstruction that inhibits the revealing of the smoke

The MD9910-LT and MD9910-LTNB versions are derived from the standard MD9910 sensor, from which they differ due to the absence of certain electronic circuits that are not required for the Test On Demand (TOD) function.







Datasheet:

D38823_J - Datasheet detector MD9910
ST38822_F - Technical Specification MD9910 (23.04.2025)
D44604_A - Technical assessment MD9910-LT & MD9910_LTNB (24.04.2025)






Microdata Due Reference documents:


ST38822 Rev. E
Detector Technical specification
D38823 Rev. G
Sensor Data sheet
D40019 Rev. 0
Risk Assessment
SDD MD9910 Rev.1.1
Software description
SDD-39929_Rev.1
Software description doc. SWMD9910
CRISD-39930 Rev. 1
Computer Resource Integrated Support
VDD SW-29741 Rev.1
Version Description Doc. SW-29741 rev.1
IS40015 Rev.0
MD9910 Inspection and functional test
D36618 Rev. B
Detector Bases Short-Circuity Isolator_ Functional test procedure
IS39982 Rev. 0
Smoke Detector- Dust pollution test
ST39940 Rev. B
Low Profile Detector Base – MD9910-LP Technical Specification
D39924 Rev. B
Data sheet LP detector base
CM-29685-40007
Dwg. MD9910 LP
CM-29685-40010
Dwg. MD9910 LP
CM-29655-40006_0
Dwg. MD9910 dimension with bases
CM-29655-40007
Dwg. MD9910 detector assembly
CM-29655-40010
Dwg. MD9910 detector Outline
ME-29737
Dwg. MD9910 ID Label
ME-29806 Rev.A Dwg. MD9910-LP- ID Label
19268/09/S
Certificate ISO 9001:2015 (13/02/2024) Accredia

EVPU a.s. Test Reports:


0-0381B/19
EN54-3:2014+A1:2019
4/12/2019
0-0381B/19
Amendment n. 01
8/01/2020
0-0381B/1/19
EN54-5:2017+A1:2018
4/12/2019
0-0381B/2/19
EN54-7:2018
4/12/2019
0-0381B/3/19
EN54-29:2015, cl 5.5
4/12/2019
0-0381E/19
EN54-3:2014+A1:2019
4/12/2019
EN54-5:2017+A1:2018
4/12/2019
EN54-7:2018; EN55032:2015
4/12/2019
EN50130-4:2011+A1:2014 4/12/2019
EN55032:2015
4/12/2019
0-0381S/19
EN 54-5:2017+A1:2018, cl. 4.27
4/12/2019
0-0381S/1/19
EN 54-7:2018, cl.4.2.8
4/12/2019
0-0381B/4/19
IEC 60092-504:2016, tab. 1
4/12/2019
EN 60529:1991+A1:2000+A2:2013 (IP44 with base MD9900-BS)
4/12/2019
EN60695.11.5:2017
4/12/2019
0-0381E/1/19
IEC60092-504:2017
4/12/2019





EVPU a.s. Statement:

Doc. n. Ny-013/20 (10/03/2019)








TesLab Test Reports:


19A285F
IEC 60092-504:2016 (IP22 with base MD9910-LP)
19/12/2019
19B344A Rev.1
Additional Dust Test
27/02/2020
19A284F
EN 54-17:2005
28/12/2019
19A285F60092-504:2016 (MD9910-LP) 19/12/2019
19A286AEN 60529:1991 + A1:2000 + A2:2013 26/11/2019






Genoa July 17, 2026
**** NOTICE: This is NOT an official certificate ****