ELE037623CS!003ENG- -  -  N- MD9902 IR Tri-Spectrum  -N- S- S- -22/02/2023- Prodotti Elettrici- - SN- N- Luigi Benedetti- N-  - 840,487Luigi BenedettiBbisProdotti ElettriciNumero Pratica,NumDich,Norma,NumBusta,Richiesta,Validità- ELE037623CS/003- N-Feb 21, 2028840487
 
Form
  Prodotti Elettrici(TO)
Certification N. ELE037623CS/003 - (ENG)
Certificate date 22/02/2023
Type Impianti di Automazione
Product Fixed fire detection and fire alarm systems: Flame detectors including Short circuit isolator

Model or Denomin.
Items
MD9902 IR Tri-Spectrum
Applicant MICRODATA DUE SRL
Place of requester Via Greti Del Vara 9 , 19020 Follo, La Spezia % ITALY
Tel. N.,Fax, Email 0187-599101 d.dido@microdatasrl.it
Standards SOLAS 74 as amended: Reg. II-2/7, Reg. X/3,IMO Res.MSC.36(63)-(1994 HSC Code) 7 ,IMO Res.MSC.97(73)-(2000 HSC Code) 7,IMO Res.MSC.98(73)-(FSS Code) 9,IMO Res.MSC 391(95)-(Codice IGF) 11,IMO MSC.1/Circ.1242
Envelope N. 9090 H
Expire date 21/02/2028
Interrut.senza Dettaglio ENG
Vuoto Querysave
S
TYPE APPROVAL CERTIFICATE
No. ELE037623CS003
This is to certify that the product below is found to be in compliance with the applicable requirement of the RINA type approval system.

Description
Type MD9902 IR Tri-Spectrum
Applicant MICRODATA DUE SRL
Via Greti Del Vara 9 , 19020 Follo, La Spezia
ITALY
Reference standards SOLAS 74 as amended: Reg. II-2/7, Reg. X/3,IMO Res.MSC.36(63)-(1994 HSC Code) 7 ,IMO Res.MSC.97(73)-(2000 HSC Code) 7,IMO Res.MSC.98(73)-(FSS Code) 9,IMO Res.MSC 391(95)-(Codice IGF) 11,IMO MSC.1/Circ.1242
  

 
 
   .   This Certificate is valid until February 21, 2028
_________________________________
RINA Services S.p.A.
Luigi Benedetti
This certificate consists of this page and 1 enclosure
**** NOTICE: This is NOT an official certificate ****

TYPE APPROVAL CERTIFICATE
No. ELE037623CS003
Enclosure - Page 1 of 3
MD9902 IR Tri-Spectrum including Short circuit isolators

Product description: 
                                                   
 MD 9902 IR Tri-Spectrum 
 Analogue, Addressable detectors able to provide flame detection and temperature analog value.

The flame is detected by three sensors working simultaneously; one of them is working on the hot carbon dioxide specific flame wavelength, the two other measure the interference radiation on the  near wavelengths.
Sensitivity Class 1, 2 , 3 as defined on the EN 54-10 Requirements is complied with.

In case a failure occurs  in the  fire detection and alarm system (eg. loss of communication with detectors through loop card), the degraded mode is activated and a digital signal is sent to the central unit to activate the relevant loop led on the central unit.

 A signalling LED on the detector housing is also flashing when a fire alarm is detected.
The detector  warns its failure conditions or degradation.
IR sensors is contained in Aluminium chamber. 

Detector housing:  IP 65/67_Poliycarbonate flame retardant
(in connection with approved socket type MD9900-BS or MD9900-BS-PT and MD9900-BSI or MD9900-BSI-PT);

Detector housing: IP 32_Poliycarbonate flame retardant
(in connection with approved socket type MD9900-BC or MD9900-BC-PT and MD9900-BCI or MD9900-BCI-PT);

IP 32 protection with bases MD9900-BC and MD9900-BCI
IP 65 protection with bases MD9900-BS and MD9900-BSI
IP 66/IP67 protection with bases MD9900-XF and MD9900-XFI
IP X7 protection with bases MD9900-BS and MD9900-BSI

Reference documents:
Microdata Due Technical descriptions ST24737 Rev. C  
Microdata Due Data sheets D25795  Rev. H
Microdata Due Software description D25806  Rev. 0
Microdata Due Installation and maintenance manual IS 31219  Rev. A  
Microdata Due Risk Assessment D36685 Rev. 0
Microdata Due Comparing Lexan 920 and Lexan 923 resin D36647 Rev. 0

TYPE APPROVAL CERTIFICATE
No. ELE037623CS003
Enclosure - Page 2 of 3
MD9902 IR Tri-Spectrum including Short circuit isolators


Test reports:
 BRE Laboratory Environmental/ Performance Report n. TE227965, (07/11/06)
 BRE Laboratory Environmental/ Performance Report n. TE227965 -SW  (10/01/07)
Microdata Due Functional tests Report n.1050 annex to IS-26872 Rev. 0, (13/12/06)
 Istituto Giordano Lab IP test Report n. 213254  (30/06/06)
 Istituto Giordano Lab IP test Report n. 225438  (10/05/07)
 Test Lab EMC (EN60092-504)  Report n. 17B302E-c
Test Lab/Microdata Functional tests Report n. 0974-17 (28/11/17)
                      
Fire  detector bases :
The following  detector bases may be used in connection with MD9902 detectors

Models MD9900 BC or MD9900-BC-PT and MD9900 BCI or MD9900-BCI-PT detector bases
(IP 32 in connection with the MD9900 and MD9901 detectors) for false ceiling installation;
Models  MD9900-BCI or MD9900-BCI-PT in addition contain a short circuit isolator.
Models  MD9900-BC-PT and MD9900-BCI-PT are suitable for connection to PTS  Satellite

MD 9900 BS or MD9900-BS-PT and MD 9900-BSI or MD9900-BSI-PT detector bases:
(IP67 in connection with the MD9902  for installation in wet or outdoor areas)
Models MD9900-BSI or MD9900-BSI-PT in addition contain a short circuit isolator
Models MD9900-BS-PT and MD9900-BSI-PT are suitable for connection to PTS Satellite

MD9900-XF or MD9900-XFI detector bases:
(proof base IP66+IP67) particularly suitable for installation in areas exposed to severe environmental conditions.
Model MD9900-XFI in addition contain a short circuit isolator.


Reference documents:
Microdata Due Technical specification n. ST21405 rev. C
Microdata Due Data sheet n. D24729 Rev. F
Microdata Due Data sheet n. D24730 Rev. F
Microdata Due Data sheet n. D37706 rev. A
Microdata Due Functional Test Procedure n. D36618 Rev.0




TYPE APPROVAL CERTIFICATE
No. ELE037623CS003
Enclosure - Page 3 of 3
MD9902 IR Tri-Spectrum including Short circuit isolators


Test reports:
BRE Laboratory Report   n.TE213449/A, (03/10/2007)_Environmental / Performance
Microdata Due Test procedure  n.IS34434_report 822/14 testing on 16/05/2014
Microdata Due Test procedure n.D36618 Rev.0 (13/07/16)_report 656/16 (2/08/16) Functional Test Procedure
Microdata Due Test Report n.172048F-b_UNI-EN 54-17 for MD9900BSI
Microdata Due Test Report n.172048F-d UNI-EN 54-17 for MD9900-XFI
Microdata Due Report n.1951561A, degrees of protection test for MD99002 with MD9900-XF base
RINA Report n° 2006CS014611 for MD9902


Genoa February 22, 2023
**** NOTICE: This is NOT an official certificate ****