MED130526WSENG- -  -  N- SF-AFFF6% -N- S- S- -19/04/2026- Marine Equipment- - SN- S- - N-  - 908,651B2bisMarine EquipmentNumero Pratica,Direttiva,Norma,Schema,Richiesta,Validità,EmailR- MED130526WS- N-Apr 18, 2031908651
 
Form
  Marine Equipment(TO)
Certification N. MED130526WS - (ENG)
Certificate date 19/04/2026
Type Protezione antincendio
Product Fixed low expansion foam fire extinguishing systems components for machinery spaces and tanker deck protection
Item Nº MED/3.58

Model or Denomin.
Items
SF-AFFF6%
Applicant JIANGSU SUOLONG FIRE SCIENCE AND TECHNOLOGY CO., LTD
Place of requester NO.643 YINGWU SOUTH ROAD, XINGHUA CITY % JIANGSU PROVINCE  % CHINA
Tel. N.,Fax, Email 0086 523 82300896
Directive (EU) 2025/1533
Standards IMO MSC.1/Circ.1312,IMO MSC.1/Circ.1312/Corr.1
Reference Documents SOLAS 74 Reg.II-2/10, IMO Res.MSC.98(73)-(FSS Code) 6, IMO Res.MSC.98(73)-(FSS Code) 14, IMO MSC/Circ.1239, IMO MSC.1/Circ.1276.
Request 2025-02-10
Expire date 18/04/2031
Head Office SHANGHAI
EC TYPE-EXAMINATION (MODULE B) ENG
Vuoto Querysave
Zhi Yuan Tan S

EC TYPE EXAMINATION (MODULE B)
CERTIFICATE No. MED130526WS

This is to certify that RINA Services S.p.A. (Notified Body No. 0474) did undertake the relevant type approval procedures for the equipment identified below, which was found to be in compliance with the Fire Protection requirements of Marine Equipment Directive (MED) 2014/90/EU, including the requirements and testing standards of Regulation (EU) 2025/1533.
MED Item Nº MED/3.58
Description Fixed low expansion foam fire extinguishing systems components for machinery spaces and tanker deck protection
Type SF-AFFF6%
Applicant JIANGSU SUOLONG FIRE SCIENCE AND TECHNOLOGY CO., LTD
NO.643 YINGWU SOUTH ROAD, XINGHUA CITY,JIANGSU PROVINCE,CHINA
Testing standards IMO MSC.1/Circ.1312,IMO MSC.1/Circ.1312/Corr.1
Reference standards SOLAS 74 Reg.II-2/10, IMO Res.MSC.98(73)-(FSS Code) 6, IMO Res.MSC.98(73)-(FSS Code) 14, IMO MSC/Circ.1239, IMO MSC.1/Circ.1276.
Issued in SHANGHAI on
This Certificate is valid until
April 19, 2026
April 18, 2031
This Certificate consists of this sheet plus an attachment

________________________________________
Hai Wen Zhang
RINA Services S.p.A.
**** NOTICE: This is NOT an official certificate ****

ATTACHMENT TO
CERTIFICATE No.  MED130526WS
Page 1 of 3

Technical Characteristics

FOAM CONCENTRATE SF-AFFF6%
Type of Foam Concentrate
Aqueous film - forming foam concentrate - Hydrocarbon B Fire
Mixture Ratio
6% *
Density at 20ºC
1.00 ~ 1.10 g/cm3 *
1.03 g/cm3 **
Kinematic Viscosity at 20ºC
≤ 200 mm2/s *
4.0 mm2/s**
PH at 20ºC
6.5 ~ 8.5 *
7.2 **
Freezing Point
≤ -15 ºC *
-15 ºC **
Minimum temperature for use
- 10 ºC *
Maximum temperature for use
+ 60 ºC *
Expansion Ratio at 20ºC
≥ 7.0 *
7.5 **
*) Data from Product Data Sheet Ref. RINA filed No.: SHFP-17819.
**) Data from Initial Test Report, when tested according to IMO MSC.1/Circ.1312 & MSC.1/Circ.1312/Corr.1.
Field of Application

This approval does not address the foam generating equipment, only the foam concentrate.

Foam concentrate SF-AFFF6% is with no intentionally added PFOS (perfluorooctane sulfonic acid).

Fixed foam fire extinguishing systems using low expansion foam concentrate for extinguishing fires of following products at ambient temperature and pressure:


- Chemical Products as per list of Chapter 17, International Bulk Chemical Code (Column L - Letters A, B and D);
- Chemicals to which the IBC Code nor the BCH Code apply as per list set out in IMO Circular MSC/Circ. 553.

Technical Documentation

Product Data Sheet reviewed and filed by RINA with No.: SHFP-17819.

ATTACHMENT TO
CERTIFICATE No. MED130526WS
Page 2 of 3

Continued:

Tests Carried Out

According to IMO MSC.1/Circ.1312 & MSC.1/Circ.1312/Corr.1- "Revised guidelines for the performance and testing criteria, and surveys of foam concentrates for fixed fire-extinguishing systems", test report (Ref. No.: SL-2020-0618-3) issued by JIANGSU SUOLONG FIRE SCIENCE AND TECHNOLOGY CO.,LTD, witnessed and filed by RINA with No.: SHFP-17820.

Test Report (PFOS) issued by SGS-CSTC Standards Technical Services (Qingdao) Co., Ltd, and filed by RINA with No.: SHFP-36339.

Notes

The foam concentrate should be delivered with a declaration (i.e., Batch Certificate) of the main characteristics (sedimentation, pH value, expansion ratio, drainage time and volumetric mass).

The declaration will be the basis for the annual condition test.

Previous issued MED Module B certificate (Ref. No.: MED143120WS) was renewed without modification.





ATTACHMENT TO
CERTIFICATE No. MED130526WS
Pages 3 of 3
The mark of conformity may only be affixed to the above type approved equipment and a Manufacturer's Declaration of Conformity issued when the production control phase module (D, E or F) of Annex II of the Directive is fully complied with a written inspection agreement with a Notified Body
XXXX/YY
"WHEELMARK FORMAT"

XXXX
Notified Body number undertaking surveillance module
YY
Last two digits of year mark affixed
     
______________________________________________
General conditions for the approval
a) The initial conditions verified by RINA at the time of the approval are to be maintained
b) Any changes to the initial conditions are to be promptly communicated to RINA, which reserves the right to repeat the relevant assessment
c) This certificate will no be valid if the manufacturer makes any changes or modifications to the approved equipment, which have not been notified to, and agreed with RINA
d) RINA personnel are to be allowed to witness during the performances of activities, upon their request
e) The activities are to be carried out in compliance with the RINA Rules and/or other applicable Rules

f) Should the specified regulations or standards be amended during the validity of this certificate, the product is to be reapproved prior to it being placed on board vessels to which the amended regulations or standards apply. 


__________________________________________
Hai Wen Zhang
**** NOTICE: This is NOT an official certificate ****