Product description
Transits of electric cables, having maximum diameter of 99 mm, installed in A-Class aluminium bulkheads. The transits are composed of an aluminium frame having thickness of 10 mm and depth of 60 mm fillet welded, on both sides, to the bulkhead plate and filled with EPDM modules; on the upper part it is installed one module fitted with a screw expander. The interstices between the cables and the modules and between the modules are lubricated by means of product named WallMax Lubricant. The transits are insulated, on both sides with two layers of mineral wool type SeaRox SL 620, having density of 100 kg/m3 and, each, thickness of 60 mm; the mineral wool panels, having dimensions of 400x600 mm and 300x300 mm (transits WRF 60), are fixed to the bulkhead by means of steel pins and washers welded with pitch ranging from 120 up to 200 mm. The certification is valid also for transit types WRF2, WRFD and for type WRFO composed of a three-side frame with the fourth side welded afterwards.
Reference documents
WallMax drawing No. 5500001031 Rev. 00 dated 14 November 2017 approved on 23 January 2018 with endorsement Nos. LABS-1602.
Tests carried out
Tests as per RINA Test Laboratory Reports No. 2017CS013522/4 issued on 23 January 2018 according to Appendix 1 of IMO 2010 FTPC Part 3 - A.IV Cable Transits.
|
ATTACHMENT TO
CERTIFICATE Nr. MED025623CS
Page 2 of 3 |
Field of application
Fire resistant A-60 Class cable transits through aluminium bulkheads as per following tables:
WRF TYPE
Transit dimensions (mm) | Minimum fill
% | Maximum fill
% | Cables - Maximum diameter (mm) |
140x118 | 0.08 | 37.5 | 53 |
140x298 | 0.03 | 49.5 | 99 |
WRFR6 TYPE
Transit dimensions (mm) | Minimum fill
% | Maximum fill
% | Cables - Maximum diameter (mm) |
140x298 | 0.05 | 37.4 | 99 |
|