Product description:
Analogue and addressable Fire detection and fire alarm system consisting of:
Fire alarm control panel | MD2020-CU (P/N-30103) |
Power supply module | MD2020-PSU (P/N-30378) |
Interface Module | MD2020-CTB (P/N-30377) |
Branch control unit | MD2020-BCU (P/N-30287) |
Loop control unit | MD2020-LCU (P/N-30284) |
Remote node | MD2020-RN (P/N-30513) |
Fire Alarm Central Unit is able to work in the following configurations:
a) for the management of Centralized Systems (Only one Central Unit) or distributed system
(several central unit net connected) ; detectors are connected in a Loop configuration.
b) for the management of Distributed System, detectors are connected on open electric lines
named Branch
Main features:
Up to 40 detection Branches/Loops are managed through Branch control Unit BCU and Loop Control Unit LCU card.
An additional 40 units can be added using MD2020-RN.
Up to 127 devices may be connected to each Loop
Up to 180 devices may be connected to each Branch
The central units are able to detect any fault occurring on the system (eg. Loop/ Branch cable break, detector failure, etc.)
The central units provides the following additional functions:
- Alarm, Failure, Delayed alarm, System, Alarm sounder, Failure Sounder relay
The MD2020-CU can be connected to the Alarm Repeater Unit MD9860
The MD2020-CTB also implements additional Input/Output features. These extra I/O capabilities are managed by the CTB's internal microprocessor, which communicates with the CU via a dedicated serial line:
- n° 18 programmable outputs – 4 relay / 14 static
- n° 04 monitored inputs – 2 isolated / 2 non isolated
- n° 01 thermistor input – for connecting external thermistor
Microdata Due Software description:
doc. n. D44507 Rev. 0: Fire Alarm Central Unit MD2020-CU Software Requirements (08/01/2022)
doc. n. IRS 40109 Rev. L: Fire Alarm Central Unit MD2020-CU External Communication Interface Specification
Microdata Due Reference documents:
Technical specification doc. n. ST44513 Rev. 0 (04/09/2023)
User Manual: D44490 Rev. 0 (02/05/2024) ;
Layout: 30148-16; 52933_1; 30039-02, 30410-02, 30412-02, 30288-02, 30285-02, 30375-02;
Risk Assessment: doc. D44517 rev. 0 (22/04/2024)
FMEA Microdata Due doc. n. D42343 Rev. 0 (13/05/2024)
doc. n.ST 43415 Rev. 0: Fire Alarm Central Unit MD2020-CU Technical Specification (04/09/2023)
doc. n.D 43427 Rev. A: Fire Alarm Central Unit MD2020-CU - Data Sheet
Test reports :
Doc. Microdata Due IS44476 rev.C, Annex A, B, C, and D(Conformity to EN 54-2, EN 54-4 and FSS code as amended., RINA Rules part C, Ch, 3, Sec. 3, EN IEC 62923-1:2018, EN IEC 62923-2:2018)
Microdata Due IS 43423 Demo for Rina Certification (02/05/2024)
TesLab/ Environmental report doc. n.245168N-a (31/05/24)
TesLab/ Environmental report doc. n.245168N-b (31/05/24)
TesLab/ Environmental report doc. n.243078F-a (15/05/24)
TesLab/ Environmental report doc. n.243078F-b (15/05/24)
TYPE APPROVAL CERTIFICATE No. ELE274624CS001Enclosure - Page 2 of 2
MD2020
The complete sets of documents related to:
- Software
- Demo System for Environmental and functional Tests
- General Specification about MD2020 CU (Control Unit), PSU (Power Supply Unit),
BCU (Branch Control Unit), LCU (Loop Control Unit), CTB (Control Terminal Board),
RN (Remote Node)
have been archived in the Leonardo Draw Plus portal under the project:
https://leodrawplus.rina.org/projects/50876/detail
Reference documents
TAO-APP dated 26/10/2023.
Offer N° 2024/16581 dated 06/06/2024
|
|