General Description:
The air cooled Green Orca Battery System comprises of up to eighteen battery modules utilizing Lithium-Ion NMC battery cells. The modules are connected in series to form a string to achieve the required system voltage. Strings are connected in parallel to provide the required current.
The batteries are quipped with over-pressure relief valves and the racks have an integrated runaway exhaust duct. Between each pack (module) is a thermal barrier installed.
Ratings:
Module/Pack EST50-1050 EST
Chemistry: Lithium Ion NMC
Cell configuration: 1P14S
Max voltage: 58.1 V
Min voltage: 44.8 V
Capacity: 200 Ah
Energy: 10.5 kWh
String
Max no. of modules in series: 18
Max voltage: 1045 V
Max energy: 209 kWh
Software:
BMS: V1.3.xxx
BCU: V1.3.xxx
BCU monitor: V4.0.xxx
Battery Management System (BMS)
The status of each module is monitored by the BMS:
- individual cell voltage
- battery current
- cell temperatures
- perform active balancing between individual cells
- perform active balancing between individual packs
- perform safe guard functions (e.g. over/under voltage, over/under temperatures, ...)
Battery Control Unit (BCU)
The Battery Control Unit connects (switch ON/OFF) the modules the system DC-bus. The BCU measures string current, string voltage and DC bus voltage.
BCU monitor
- user interface
- communication with BCUs and external systems
- interface to peripheral devices and sensors
TYPE APPROVAL CERTIFICATE
No. ELE053123XG/001
Enclosure - Page 2 of 2
Battery System
Green Orca
Remarks:
- Each particular application and installation such as electric propulsion and essential services, or for the charging/discharging of battery systems of a capacity of 50 kWh or above are to be specifically approved.
- Batteries are to be subject to functional and safety tests according to IEC Publication 62620 or in accordance with other equivalent national or international standards recognized by RINA.
- Performance tests (Factory Acceptance Test) are to be carried out on the battery system (BMS and Battery Cells) according to a test program and which is to include functional tests (alarm system, safety system, control system, etc.) and further tests resulting from the Risk Assessment at the presence of a RINA Surveyor.
- The battery system is to be used in connection with an appropriate Power Management System (PMS) able to shut down the battery pack in case of an identified failure.
- Installation of the battery system is to be in accordance with RINA Rules for the Certification, Installation and Testing of Lithium Based Storage Batteries.
- The battery system is not to be installed on the bridge or deck zone.
- This Type Approval Certificate does not cover any Flag Administration requirements.
Documents:
(I030) Green Orca Battery System Block Diagrams ; (I080) GOA,20200227,DAT,000,Environmental specifications; 11 - Green Orca Battery System Specification; Communication Reference Manual Green Orca Systems V2.14; 28 - GOA,20190424,MAN,000,Thermal,Runaway,Guide,GO,Systems; GOA,20180112,lis,012,List of Controlled and Monitored items; GOA,20180111,REP,023,FMEA EST Battery System rev2.3; GOA,20180110,MAN,070,Safety Description Document; GOA,20180111,MAN,034,BMS Description v3.4; GOA,20180123,MAN,012 Operation and Installation Manual GO Systems; GOA,20200430,rep,004,Software Quality Document;
Test Reports:
- 2224238.51, DEKRA -Environmental, dated 2018-02-09;
- 2224238.60, DEKRA – IP test, dated 2018-02-09;
- 2224893.0501, DEKRA – EMC test, dated 2018-02-08;
- GOA,20180125,000, GO1050, THALES - Vibration test, dated 12-12-2017;
- Propagation test report GO1050 ALU 20170512 revD, - EST Floattech, dated 20170712; |
|