MED037623CS!003ENGF- -  -  N- MD9902 IR Tri-Spectrum -N- S- S- -22/02/2023- Marine Equipment- - SN- S- - N-  - 840,487B2bisMarine EquipmentNumero Pratica,Direttiva,Norma,Schema,Richiesta,Validità- MED037623CS/003- N-Feb 21, 2028840487
 
Form
  Marine Equipment(TO)
Certification N. MED037623CS/003 - (ENG)
Certificate date 22/02/2023
Description
Fixed fire detection and fire alarm systems components for control stations, service spaces, accommodation spaces, cabin balconies, machinery spaces and unattended machinery spaces,(g) Short circuit isolators,(e) Flame detectors: Point detectors
Type Protezione antincendio
Product Fixed fire detection and fire alarm systems components for control stations, service spaces, accommodation spaces, cabin balconies, machinery spaces and unattended machinery spaces: (g) Short circuit isolators,Fixed fire detection and fire alarm systems components for control stations, service spaces, accommodation spaces, cabin balconies, machinery spaces and unattended machinery spaces: (e) Flame detectors: Point detectors
Item Nº MED/3.51g,MED/3.51e

Model
Items/Sizes
MD9902 IR Tri-Spectrum
Applicant MICRODATA DUE - SOCIETA' A RESPONSABILITA' LIMITATA
Place of requester VIA GRETI DEL VARA 9  %  19020 Follo (SP)  % ITALY
Tel. N.,Fax, Email 0187 599101, 0187 558983, d.dido@microdatasrl.it
Directive (EU) 2022/1157
Standard EN 54-10 (2002) incl. A1 (2005) ,EN 54-17 (2007) incl. AC (2007),IEC 60092-504 (2016),IEC 60533 (2015),RINA Rules for the certification of Marine Equipment.
Reference Documents SOLAS 74 Reg. II-2/7,SOLAS 74 Reg. X/3,IMO Res. MSC.36(63)-(1994 HSC Code) 7,IMO Res. MSC.97(73)-(2000 HSC code) 7,IMO Res. MSC.98(73)-(FSS Code) 9,IMO Res. MSC.391(95)-(IGF Code) 11,IMO MSC.1/Circ 1242,RINA Rules for the certification of Marine Equipment
Validity 21/02/2028
EC TYPE-EXAMINATION (MODULE B) ENG
Vuoto Querysave
Lucia Lorenzi S

EC TYPE EXAMINATION (MODULE B)
CERTIFICATE No. MED037623CS/003

This is to certify that RINA Services S.p.A. (Notified Body No. 0474) did undertake the relevant type approval procedures for the equipment identified below, which was found to be in compliance with the Fire Protection requirements of Marine Equipment Directive (MED) 2014/90/EU, including the requirements and testing standards of Regulation (EU) 2022/1157.
MED Item Nº MED/3.51g,MED/3.51e
Description Fixed fire detection and fire alarm systems components for control stations, service spaces, accommodation spaces, cabin balconies, machinery spaces and unattended machinery spaces,(g) Short circuit isolators,(e) Flame detectors: Point detectors
Type MD9902 IR Tri-Spectrum
Applicant MICRODATA DUE - SOCIETA' A RESPONSABILITA' LIMITATA
VIA GRETI DEL VARA 9,19020 Follo (SP),ITALY
Testing standards EN 54-10 (2002) incl. A1 (2005) ,EN 54-17 (2007) incl. AC (2007),IEC 60092-504 (2016),IEC 60533 (2015),RINA Rules for the certification of Marine Equipment.
Reference standards SOLAS 74 Reg. II-2/7; SOLAS 74 Reg. X/3; IMO Res. MSC.36(63)-(1994 HSC Code) 7; IMO Res. MSC.97(73)-(2000 HSC code) 7; IMO Res. MSC.98(73)-(FSS Code) 9; IMO Res. MSC.391(95)-(IGF Code) 11; IMO MSC.1/Circ 1242; RINA Rules for the certification of Marine Equipment
Issued in Genoa on
This Certificate is valid until
February 22, 2023
February 21, 2028
This Certificate consists of this sheet plus an attachment

________________________________________
Luigi Benedetti
RINA Services S.p.A.
**** NOTICE: This is NOT an official certificate ****

ATTACHMENT TO
CERTIFICATE No.  MED037623CS/003
Page 1 of 4
Product description:

MD 9902 IR Tri-Spectrum


Analogue, Addressable detectors able to provide flame detection and temperature analog value.

The flame is detected by three sensors working simultaneously; one of them is working on the hot carbon dioxide specific flame wavelength , the two other measure the interference radiation on the near wavelengths.
Sensitivity Class 1, 2 , 3 as defined on the EN 54-10 Requirements is complied with.

In case a failure occurs in the fire detection and alarm system (eg. loss of communication with detectors through loop card), the degraded mode is activated and a digital signal is sent to the central unit to activate the relevant loop led on the central unit.

A signalling LED on the detector housing is also flashing when a fire alarm is detected.
The detector warns its failure conditions or degradation.
IR sensors is contained in Aluminium chamber.

Detector housing: IP 65/ 67 _Poliycarbonate flame retardant
(in connection with approved socket type MD9900-BS or MD9900-BS-PT and MD9900-BSI or MD9900-BSI-PT);

Detector housing : IP 32 _ Poliycarbonate flame retardant


(in connection with approved socket type MD9900-BC or MD9900-BC-PT and MD9900-BCI or MD9900-BCI-PT);

IP 32 protection with bases MD9900-BC and MD9900-BCI
IP 65 protection with bases MD9900-BS and MD9900-BSI
IP 66/IP67 protection with bases MD9900-XF and MD9900-XFI
IP X7 protection with bases MD9900-BS and MD9900-BSI

Reference documents:
Microdata Due Technical descriptions:ST24737 Rev. C
Microdata Due Data sheets:D25795 Rev. H
Microdata Due Software description:D25806 Rev. 0
Microdata Due Installation and maintenance manualIS 31219 Rev. A
Microdata Due Risk Assessment:D36685 Rev. 0
Microdata Due Comparing Lexan 920 and Lexan 923 resinD36647 Rev. 0
Test reports:
BRE Laboratory Environmental / Performance Report n. TE227965, (07/11/2006)
BRE Laboratory Environmental / Performance Report n. TE227965 -SW (10/01/2007)
Microdata Due Functional tests Report n. 1050 annex to IS-26872 Rev. 0, (13/12/2006)
Istituto Giordano Lab IP test Report n. 213254 (30/06/2006)
Istituto Giordano Lab IP test Report n. 225438 (10/05/2007)
Test Lab EMC (EN60092-504) Report n. 17B302E-c
Test Lab/Microdata Due Functional tests Report n. 0974-17 (28/11/2017)

Fire detector bases
The following detector bases may be used in connection with MD9902 detectors

Models MD9900 BC or MD9900-BC-PT and MD9900 BCI or MD9900-BCI-PT detector bases
(IP 32 in connection with the MD9900 and MD9901 detectors) for false ceiling installation;
Models MD9900-BCI or MD9900-BCI-PT in addition contain a short circuit isolator.
Models MD9900-BC-PT and MD9900-BCI-PT are suitable for connection to PTS Satellite


MD 9900 BS or MD9900-BS-PT and MD 9900-BSI or MD9900-BSI-PT detector bases:
(IP67 in connection with the MD9902 for installation in wet or outdoor areas)
Models MD9900-BSI or MD9900-BSI-PT in addition contain a short circuit isolator
Models MD9900-BS-PT and MD9900-BSI-PT are suitable for connection to PTS Satellite

MD9900-XF or MD9900-XFI detector bases:
(proof base IP66+IP67) particularly suitable for installation in areas exposed to severe environmental conditions.
Model MD9900-XFI in addition contain a short circuit isolator.

Reference documents:
Microdata Due Technical specification n. ST21405 rev. C
Microdata Due Data sheet n. D24729 Rev. F
Microdata Due Data sheet n. D24730 Rev. F
Microdata Due Data sheet n. D37706 rev. A
Microdata Due Functional Test Procedure n. D36618 Rev.0

Test reports:
BRE Laboratory Report n. TE213449/A, (03/10/2007)_Environmental / Performance
Microdata Due Test procedure n° IS 34434_report 822/14 testing on 16/05/2014
Microdata Due Test procedure n. D36618 Rev.0 (13/07/16)_report 656/16 (2/08/16) - Functional Test Procedure
Microdata Due Test Report n° 172048F-b_UNI-EN 54-17 for MD9900BSI
Microdata Due Test Report n° 172048F-d UNI-EN 54-17 for MD9900-XFI
Microdata Due Test Report n° 1951561A, degrees of protection test for MD99002 with MD9900-XF base
RINA Report n° 2006CS014611 for MD9902




ATTACHMENT TO
CERTIFICATE No. MED037623CS/003
Pages 4 of 4
The mark of conformity may only be affixed to the above type approved equipment and a Manufacturer's Declaration of Conformity issued when the production control phase module (D, E or F) of Annex II of the Directive is fully complied with a written inspection agreement with a Notified Body
XXXX/YY
"WHEELMARK FORMAT"

XXXX
Notified Body number undertaking surveillance module
YY
Last two digits of year mark affixed
     
______________________________________________
General conditions for the approval
a) The initial conditions verified by RINA at the time of the approval are to be maintained
b) Any changes to the initial conditions are to be promptly communicated to RINA, which reserves the right to repeat the relevant assessment
c) This certificate will no be valid if the manufacturer makes any changes or modifications to the approved equipment, which have not been notified to, and agreed with RINA
d) RINA personnel are to be allowed to witness during the performances of activities, upon their request
e) The activities are to be carried out in compliance with the RINA Rules and/or other applicable Rules

f) Should the specified regulations or standards be amended during the validity of this certificate, the product is to be reapproved prior to it being placed on board vessels to which the amended regulations or standards apply. 


__________________________________________
Luigi Benedetti
**** NOTICE: This is NOT an official certificate ****