Product description:
MD 9902 IR Tri-Spectrum
Analogue, Addressable detectors able to provide flame detection and temperature analog value.
The flame is detected by three sensors working simultaneously; one of them is working on the hot carbon dioxide specific flame wavelength , the two other measure the interference radiation on the near wavelengths.
Sensitivity Class 1, 2 , 3 as defined on the EN 54-10 Requirements is complied with.
In case a failure occurs in the fire detection and alarm system (eg. loss of communication with detectors through loop card), the degraded mode is activated and a digital signal is sent to the central unit to activate the relevant loop led on the central unit.
A signalling LED on the detector housing is also flashing when a fire alarm is detected.
The detector warns its failure conditions or degradation.
IR sensors is contained in Aluminium chamber.
Detector housing: IP 65/ 67 _Poliycarbonate flame retardant
(in connection with approved socket type MD9900-BS or MD9900-BS-PT and MD9900-BSI or MD9900-BSI-PT);
Detector housing : IP 32 _ Poliycarbonate flame retardant
(in connection with approved socket type MD9900-BC or MD9900-BC-PT and MD9900-BCI or MD9900-BCI-PT);
IP 32 protection with bases MD9900-BC and MD9900-BCI
IP 65 protection with bases MD9900-BS and MD9900-BSI
IP 66/IP67 protection with bases MD9900-XF and MD9900-XFI
IP X7 protection with bases MD9900-BS and MD9900-BSI
Reference documents:
| Microdata Due | Technical descriptions: | ST24737 Rev. C |
| Microdata Due | Data sheets: | D25795 Rev. H |
| Microdata Due | Software description: | D25806 Rev. 0 |
| Microdata Due | Installation and maintenance manual | IS 31219 Rev. A |
| Microdata Due | Risk Assessment: | D36685 Rev. 0 |
| Microdata Due | Comparing Lexan 920 and Lexan 923 resin | D36647 Rev. 0 |
Test reports:
| BRE Laboratory | Environmental / Performance | Report n. TE227965, (07/11/2006) |
| BRE Laboratory | Environmental / Performance | Report n. TE227965 -SW (10/01/2007) |
| Microdata Due | Functional tests | Report n. 1050 annex to IS-26872 Rev. 0, (13/12/2006) |
| Istituto Giordano Lab | IP test | Report n. 213254 (30/06/2006) |
| Istituto Giordano Lab | IP test | Report n. 225438 (10/05/2007) |
| Test Lab | EMC (EN60092-504) | Report n. 17B302E-c |
| Test Lab/Microdata Due | Functional tests | Report n. 0974-17 (28/11/2017) |
Fire detector bases
The following detector bases may be used in connection with MD9902 detectors
Models MD9900 BC or MD9900-BC-PT and MD9900 BCI or MD9900-BCI-PT detector bases
(IP 32 in connection with the MD9900 and MD9901 detectors) for false ceiling installation;
Models MD9900-BCI or MD9900-BCI-PT in addition contain a short circuit isolator.
Models MD9900-BC-PT and MD9900-BCI-PT are suitable for connection to PTS Satellite
MD 9900 BS or MD9900-BS-PT and MD 9900-BSI or MD9900-BSI-PT detector bases:
(IP67 in connection with the MD9902 for installation in wet or outdoor areas)
Models MD9900-BSI or MD9900-BSI-PT in addition contain a short circuit isolator
Models MD9900-BS-PT and MD9900-BSI-PT are suitable for connection to PTS Satellite
MD9900-XF or MD9900-XFI detector bases:
(proof base IP66+IP67) particularly suitable for installation in areas exposed to severe environmental conditions.
Model MD9900-XFI in addition contain a short circuit isolator.
Reference documents:
| Microdata Due | Technical specification | n. ST21405 rev. C |
| Microdata Due | Data sheet | n. D24729 Rev. F |
| Microdata Due | Data sheet | n. D24730 Rev. F |
| Microdata Due | Data sheet | n. D37706 rev. A |
| Microdata Due | Functional Test Procedure | n. D36618 Rev.0 |
Test reports:
| BRE Laboratory | Report n. TE213449/A, (03/10/2007)_Environmental / Performance |
| Microdata Due | Test procedure n° IS 34434_report 822/14 testing on 16/05/2014 |
| Microdata Due | Test procedure n. D36618 Rev.0 (13/07/16)_report 656/16 (2/08/16) - Functional Test Procedure |
| Microdata Due | Test Report n° 172048F-b_UNI-EN 54-17 for MD9900BSI |
| Microdata Due | Test Report n° 172048F-d UNI-EN 54-17 for MD9900-XFI |
| Microdata Due | Test Report n° 1951561A, degrees of protection test for MD99002 with MD9900-XF base |
| RINA | Report n° 2006CS014611 for MD9902 |