MED453121CSENGD- -  -  N- Explorer 4 -N- S- S- -23/06/2022- Marine Equipment- - SN- S- - N-  - 237,389B2bisMarine EquipmentNumero Pratica,Direttiva,Norma,Schema,Richiesta,Validità- MED453121CS- N-Jun 23, 2027237389
 
Form
  Marine Equipment(TO)
MED041325GE
Certification N. MED453121CS - (ENG)
Certificate date 23/06/2022
Type Protezione antincendio
Product Fixed oxygen analysis and gas detection equipment: (b) category 3 - explosive gas atmospheres
Item Nº MED/3.54b

Model
Items/Sizes
Explorer 4
Applicant RECOM INDUSTRIALE S.R.L.
Place of requester VIA PIETRO CHIESA 25 R  %  16149 GENOVA (GE)  % ITALY
Tel. N.,Fax, Email 010 4695661, 010 6424205, ---
Directive (EU) 2021/1158
Standard EN 50104:2019, EN IEC 60079-0:2018 incl. AC:2020, EN 60079-29-1:2016, IEC 60092-504:2016, IEC 60533:2015, for combined O2/HC systems, additionally: IMO MSC.1/Circ. 1370.
Reference Documents SOLAS Reg. II-2/4,  SOLAS Reg. VI/3, IMO Res. MSC.98(73)-(FSS Code) 15.  For combined O 2/HC systems additionally: IMO MSC.1/Circ.1370.
Request 28/07/2016
Validity 23/06/2027
Head Office GENOVA
EC TYPE-EXAMINATION (MODULE B) ENG
Vuoto Querysave
Luigi Benedetti S

EC TYPE EXAMINATION (MODULE B)
CERTIFICATE No. MED453121CS

This is to certify that RINA Services S.p.A. (Notified Body No. 0474) did undertake the relevant type approval procedures for the equipment identified below, which was found to be in compliance with the Fire Protection requirements of Marine Equipment Directive (MED) 2014/90/EU, including the requirements and testing standards of Regulation (EU) 2021/1158.
MED Item Nº MED/3.54b
Description Fixed oxygen analysis and gas detection equipment: (b) category 3 - explosive gas atmospheres
Type Explorer 4
Applicant RECOM INDUSTRIALE S.R.L.
VIA PIETRO CHIESA 25 R,16149 GENOVA (GE),ITALY
Testing standards EN 50104:2019, EN IEC 60079-0:2018 incl. AC:2020, EN 60079-29-1:2016, IEC 60092-504:2016, IEC 60533:2015, for combined O2/HC systems, additionally: IMO MSC.1/Circ. 1370.
Reference standards SOLAS Reg. II-2/4,  SOLAS Reg. VI/3, IMO Res. MSC.98(73)-(FSS Code) 15.  For combined O 2/HC systems additionally: IMO MSC.1/Circ.1370.
Issued in GENOVA on
This Certificate is valid until
June 23, 2022
June 23, 2027
This Certificate consists of this sheet plus an attachment

________________________________________
Luigi Benedetti
RINA Services S.p.A.
**** NOTICE: This is NOT an official certificate ****

ATTACHMENT TO
CERTIFICATE No.  MED453121CS
Page 1 of  3
Product description:

The Explorer4 analyzer is a multi-channel, microprocessor controlled gas detection
system, designed for the continuous monitoring of gas and other parameters, composed by:

Main features:

Case
Rack for 4 – 8 – 16 channels
Power supply
12 VDC / 110 – 220 VAC with transformer
Display
LCD 2x16 digit
Analog input signals
2 for each channel (0÷10 V / 4÷20 mA)
Digital Input signals
RS 232 / Bus / I/O / PC
Visual alarm
4 LED for each channel (1 fault and 3 alarm levels) + 1 LED for power
Output alarms
4 output for each channel (1 for level)
1 fault relay
Analog input signals
2 for each channel (0÷10 V / 4÷20 mA)
Alarms
3 levels, from 0 to 100% F.S. Fault and alarm disconnection sensor
3 relays for each channel
Measure point range
% or ppm - 8bit configurable
Buzzer Alarm
1 buzzer activated in case of alarm
Key pads
3 multi function keys
Operative Temperature
-20°C to +55°C
Humidity
0% to 95% HR (non-condensate)
Battery
Optional
Programming
Languages menu: English, Italian, French, Spanish, German, Portuguese (others on request)
average of the reading time, sampling time, kind of alarm (beeps or continuous)

Suitable to work in conjunction with:

1001700 102111 RTC 1001 Combustible Gas Sensor Transmitter 0-100%LEL VQ-01 ATEX Z1
1001710 102154 RTC 1002 Combustible Gas Sensor Transmitter 0-100 %LEL VQ-21 PR ATEX Z1
1001760 102302 RTE 1001 Oxigen Sensor Transmitter 0-30%
1001800 102311 RTE 1004 H2S Sensor Transmitter
1001780 102306 RTE 1003 CO Sensor Transmitter

Programming of parameters (gain, offset, full scale, alarm levels (3), fault of the
sensors, etc.) makes it possible to check any measurement detectable with sensors 0÷10 V or 4÷20 mA.






ATTACHMENT TO
CERTIFICATE Nr. MED453121CS
Page 2 of 3



Reference Documents
  • Operation / Installation Manual for EXPLORER 4 Gas Sampling System issued December 2007 rev.1.0
  • former RINA mod. B MED certificate n° MED272113CS dated 02/05/2016


Test reports:

TesLab Test Report n° 222026E dated 01/03/2022




ATTACHMENT TO
CERTIFICATE No. MED453121CS
Pages 3 of  3
The mark of conformity may only be affixed to the above type approved equipment and a Manufacturer's Declaration of Conformity issued when the production control phase module (D, E or F) of Annex II of the Directive is fully complied with a written inspection agreement with a Notified Body
XXXX/YY
"WHEELMARK FORMAT"

XXXX
Notified Body number undertaking surveillance module
YY
Last two digits of year mark affixed
     
______________________________________________
General conditions for the approval
a) The initial conditions verified by RINA at the time of the approval are to be maintained
b) Any changes to the initial conditions are to be promptly communicated to RINA, which reserves the right to repeat the relevant assessment
c) This certificate will no be valid if the manufacturer makes any changes or modifications to the approved equipment, which have not been notified to, and agreed with RINA
d) RINA personnel are to be allowed to witness during the performances of activities, upon their request
e) The activities are to be carried out in compliance with the RINA Rules and/or other applicable Rules

f) Should the specified regulations or standards be amended during the validity of this certificate, the product is to be reapproved prior to it being placed on board vessels to which the amended regulations or standards apply. 


__________________________________________
Luigi Benedetti
**** NOTICE: This is NOT an official certificate ****