Product description
GAS Screen 160 is a Gas analyzer equipped with suction pump, can be connected to sensors that measures the presence of Co, Co2 and N2O into the atmosphere by continuous monitoring with 16 channels 4-20mA and RS485 channels 494 (2x247) for combustible gases (% LEL), oxygen (O2%) and toxic gases (ppm).
Case | Wall mounting IP 65 Case |
Display | COLOUR Touch Screen |
Power supply | 220Vac/24 V DC |
Power consumption | 100 W |
No. of Chanels | 16–4/20 mA 2X247–RS485
16 direct LEL% |
Alarms Levels | 2 levels (High e Low ) 0 to 100 % f.s. |
Alarms Signal | 2 leds A1 and A2 + 1 led fault |
Alarm Relays | 3 Relais per channel |
Working temperature | -20°C to + 55°C |
Humidity | 0% to 95% relative humidity (Non-condensing) |
Programmable Parameter | Language (Italian and English)
Gain, offset, and scale for each channel.
3 levels of alarm per channel; |
- 1000001 integrated gas detection GAS Screen 160 System CO, CO2, N2O
- 1003000 I.R. sensor CO2 0-5000 ppm / Vol 5% / 10% Vol
- 1003500 I.R. sensor N2O 0 ... 2000 ppm
- 1001780 E.C. sensor 0-2000 ppm CO
- 1004010 Diaphragm suction pump 1 L / min
- PFM07 Digital Flowmeter SMC
- 1003610 External optical acoustic alarm
- VAR-AM33 Man-machine interface: VAR-AM33 Custom Board with VAR-SOM-AM33 7 "LCD resistive touch panel
Reference Documents
- Technical specification / Installation Manual for GAS Screen 160 Doc: 1004400M00.1 sa - rev.07 - 27.12.2021
- Environmental Test report TesLab n° 15A201F dated 18-01-2016
- RECOM functional test reports dated 12/07/2016 in compliance with CEI EN 60079-29-1 and CEI EN 50104
Test Carried Out
Simulation of gas detection in compliance with CEI EN60079-29-1 and CEI EN 50104
Note
For each specific installation on board, the system configuration drawings are to be always sent for approval.
The test of the system will be carried out with simulation of functionality in normal, emergency and single failure condition.
Final acceptance of the system is subject to the good result of functional test to be carried out on board - relevant safety certificate shall be provided for each specific installation in hazardous area. |
|