General Description:
The air cooled AYK Battery System is designed to be modular and can be scaled up to 1000 V DC. The smallest
unit of the battery is the module. Battery modules connected in series are forming a string. The maximum number
of modules connected in series are twenty four (24). Strings are isolated by a circuit breaker from a DC busbar.
Strings connected in parallel are forming a battery bank, controlled by a multi string manager unit.
Each string has a single controller unit. The Battery Management System (BMS) at the string level control the
safety funcitons of the battery string and communicate with the Multi String Manager (MSM). The BMS at the Multi
String Manger Level manges all strings connected in parallel within the battery bank.
Ratings:
|
| Battery System |
|
| A-69A | A-88A | A-103A | A-107A | A-176A | A-215A | B-176A |
Cell Level | Rated Capacity [Ah]: | 90 | 230 | 90 | 280 | 230 | 280 | 230 |
Nominal Voltage [V]: | 3.2 |
max Voltage [V]: | 3.65 |
min Voltage [V]: | 2.5 |
Module Level | Cell Arrangement: | 12S2P | 12S1P | 12S3P | 12S1P | 12S2P | 12S2P | 12S2P |
Nominal Voltage [V]: | 38.4 |
Voltage Range [V]: | 36 - 43.2 |
Capacity [Ah]: | 180 | 230 | 270 | 280 | 460 | 560 | 460 |
String Level | Voltage Range [V]: | 400 - 1000 |
Modules in series | 9 - 24 |
Energy [kWh]: | 62.1 - 165.6 | 79.2 - 211.2 | 92.7 - 247.2 | 96.7 -
258 | 158.4 - 422.4 | 193.5 -
516 | 158.4 - 422.4 |
Bank level | Strings | 1 - 10 |
Energy [kWh]: | 62 - 1656 | 79 - 2112 | 93 - 2472 | 96.7 - 2580 | 158 - 4224 | 194 - 5160 | 158 - 4224 |
Software:
Module level BMS: 1.1.9
Smoke detector board: 1.1.9
Valve driver board: 1.1.9
String controller BMS: 1.1.9
Interface board: 1.1.9
TYPE APPROVAL CERTIFICATE
No. ELE124323XG
Enclosure - Page 2 of 3
Battery System
Single String Controller
Power supply: 220 V AC
Max Current: 500 A
Short circuit breaking capability: 40 kA
Multi String Manager
Power supply: 220 V AC
Display: 13,3" touch panel
Data storage: 1 TB HDD
Emergency Stop: Button on enclosure and remotely possible
Remarks:
- Each particular application and installation such as electric propulsion and essential services, or for the charging/discharging of battery systems of a capacity of 50 kWh or above are to be specifically approved.
- Batteries are to be subject to functional and safety tests according to IEC Publication 62620 or in accordance with
other equivalent national or international standards recognized by RINA.
- Performance tests (Factory Acceptance Test) are to be carried out on the battery system (BMS and Battery Cells)
according to a test program and which is to include functional tests (alarm system, safety system, control system,
etc.) and further tests resulting from the Risk Assessment at the presence of a RINA Surveyor.
- The battery system is to be used in connection with an appropriate PMS able to shut down the battery pack in
case of an identified failure.
- Installation of the battery system is to be in accordance with RINA Rules for the Certification, Installation and
Testing of Lithium Based Storage Batteries.
- The battery system is not to be installed on the bridge or deck zone.
- This Type Approval Certificate does not cover any Flag Administration requirements.
Documents:
DOC2021-04 AYK Battery Safety Description; DOC2022-01 AYK Battery HAZID input to system Risk Analysis; DOC2028-02 AYK Battery Operations Manual; DOC2030-02 AYK Battery Maintenance Manual; DOC2031-04 AYK Battery Communication Protocol ModbusTCP; DOC2084-01 AYK Software Quality Plan; DOC2085-04 AYK A-176A Battery System Data Sheet; DOC2115-02 AYK Key Components List; DOC2156-02 AYK A-69A Battery System Data Sheet; DOC2157-02 AYK A-103A Battery System Data Sheet; DOC2158-02 AYK A-88A Battery System Data Sheet; DOC2159-02 AYK B-176A Battery System Data Sheet; DOC2168-02 AYK System Installation Instruction; DOC2175-01 AYK System Block Diagram; DOC2186-01 AYK Battery Design Description (General); DWG2031-01 A-88A Module Design; DWG2033-01 A-69A Module Design; DWG2034-01 B-176A Module Design; DWG2035-01 A-103A Module Design; DWG2041-01 A-176A Module Design; LF90 (3.2V 90Ah) Product Specification(Version E); DOC2160-02 AYK A-215A Battery System Data Sheet;DOC2199-01 AYK A-107A Battery System Data Sheet; DWG2036-01 A-215A Module Design; DWG2058-01 A-107A Module Design; LF280K (3 2V 280Ah) Product Specification(Version B);
TYPE APPROVAL CERTIFICATE
No. ELE124323XG
Enclosure - Page 3 of 3
Battery System
Test Reports:
01052000003024-1(E); Cell Test Report LF90 (Translation); Cell Test Report LF90 Original (CEPRI-SY8-2018-020); DOC2081-03 AYK Battery Module Thermal Runaway Propagation test; DOC2091-01 Independent safety function test; EVE20201225001,English; LF230-S01-LF-EVE; LF90 UN38.3; Test Report A-88A Battery Module Vibration; DOC2198-01 Test Report A-107A Battery Module Thermal Runaway Propagation; 01052100001801-1(E) LF280K-UN38.3; LF280K-CN21LSPD 001-IEC62619-report;