Product description:
The EN60 and EN100 series are miniature circuit breakers for DIN Rail mounting with contact position indication.
Model type: Series: EN60 (B; C, D)
Ratings and principal characteristics:
133/230V AC; 230/400V AC; 440V AC 0,5 -63A
1-; 1+N-; 2-; 3-; 3+N-; 4-pole
Instantaneous tripping current type B; C, D
Icu: 20kA (133/230V); 10kA (230/400V; 440V)
Ics: 15kA (133/230V); 7,5kA (230/400V; 440V)
Frequency: 50/60Hz
Degree of protection: IP 20
Type key: EN6_ _ _ _
A B C D
A: Number of poles: 1; 2; 3; 4
B: –NA: with neutral pole
C: Characteristic: B; C; D
D: Rated current: 0,5A to 63 A for characteristic C; D
6 A to 63 A for characteristic B
---------------------------------------------------------------------------------------------------------------------------
Model type: Series: EN100 (B; C, D)
Ratings and principal characteristics:
133/230V AC; 230/400V AC; 440V AC 0,5 -63A
1-; 1+N-; 2-; 3-; 3+N-; 4-pole
Instantaneous tripping current type B; C, D
Icu: 25kA (133/230V); 15kA (230/400V; 440V)
Ics: 18,75kA (133/230V, 0,5 – 40A); 15kA (133/230V, 50 – 63A
11,25kA (230/400V; 440V, 0,5 – 40A); 7,5kA (230/400V; 440V, 50 – 63A
Frequency: 50/60Hz
Degree of protection: IP 20
Type key: EN1_ _ _ _
A B C D
A: Number of poles: 1; 2; 3; 4
B: –NA: with neutral pole
C: Characteristic: B; C; D
D: Rated current: 0,5A to 63 A for characteristic C; D
6 A to 63 A for characteristic B
Documents:
VDE Testing and Certification Institute:
CB Test Certificates:
- DE1-68102: test report: 310525-TL3-1
- DE1-68103; test report: 310525-TL3-3
Remarks:
- The products fulfill EC-Code: 3a1.