Product Description of Pressure Switch Type KP and KPI
The KP and KPI pressure switches are used for control, monitoring and alarm systems in a wide variety of industry applications.
KP pressure switches are mainly used for gaseous fluid whereas KPI pressure switches are more for liquid and gaseous fluid. The products are available in IP30 enclosure as well as IP55 enclosure.
The KP pressure range include special designed pressure switches and limiters for steam boilers and other heating applications.
For water pump control and protection (dry run) the dual pressure switch KP44 is suitable and secure improved lifetime of the water pump.
Main characteristics of Pressure Switch Type KP and KPI (Single)
Ambient temperature: -40°C - 65°C (80°C for max. 2 hours)
Media temperature: -40°C - 100°C
Contact system: Single-pole, double-throw (SPDT)
Contact load: Alternating cur. AC1&AC3=16 A, 400 V / AC15=10 A, 400 V / AC1=10 A, 440V / AC3=6A, 440 V / AC15=4 A, 440V / Direct cur. DC13: 12 W, 220 V
Enclosure: IP30 / IP44 / IP55
Cable entry: Rubber cable gland entry for 6 – 14 mm diameter cables
Mounted on back plate / wall bracket: Vibration proof in the range 0 – 1000 Hz, 4 g [1g = 9.81 m/s2]
Mounted on angle bracket: Not recommended in areas where vibrations occur
Main characteristics of Pressure Switch and Thermostat Type KP (Dual)
Ambient temperature: -40°C - 65°C (80°C for max. 2 hours)
Media temperature: Max. 100°C
Contact load: Alternating cur. AC1&AC3=16 A, 400 V / AC15=10A, 400 V / Direct cur. DC13: 12 W, 220 V
Enclosure: IP22
Cable entry: Rubber cable gland entry for 6 – 14 mm diameter cables
Mounted on back plate / wall bracket: Vibration proof in the range 0 – 1000 Hz, 4 g [1g = 9.81 m/s2]
Mounted on angle bracket: Not recommended in areas where vibrations occur
Pressure Switch Type KP:
Type | Setting Range | Differential | Permissible Operating Press. | Max. Test Pressure | Pressure Connection |
KP35 | -0.2 - 7.5bar | 0.7 - 4.0bar | 17bar | 22bar | G ¼ A |
KP36 | 2.0 - 14bar | 0.7 - 4.0bar | 17bar | 22bar | G ¼ A |
KP36 | 4.0 - 12bar | 0.5 - 1.6bar | 17bar | 22bar | G ¼ A |
Pressure Switch Type KP (boiler version):
Type | Setting Range | Differential | Reset | Max. Test Pressure | Pressure Connection |
KP34 | 0.1 – 1.0bar | 0.1 – 0.4bar | Automatic | 4bar | G ½ A |
KP34 | 0.1 – 1.0bar | 0.2bar | Manual | 4bar | G ½ A |
KP35 | 0.4 – 3.4bar | 0.4 – 2.2bar | Automatic | 10bar | G ½ A |
KP35 | 0.4 – 3.4bar | 0.5bar | Manual | 10bar | G ½ A |
KP36 | 1.0 – 10bar | 0.7 - 4bar | Automatic | 17bar | G ½ A |
KP36 | 1.0 – 10bar | 0.7bar | Manual | 17bar | G ½ A |
KP37 | 4.0 – 20bar | 1.8 – 3.1bar | Automatic | 28bar | G ½ A |
KP37 | 4.0 – 20bar | 3.0bar | Manual | 28bar | G ½ A |
Pressure Switch Type KPI:
Type | Setting Range | Differential | Permissible Operating Press. | Max. Test Pressure | Pressure Connection |
KPI35 | -0.2 - 8.0bar | 0.4 - 1.5bar | 18bar | 18bar | G ¼ A |
KPI35 | -0.2 - 8.0bar | 0.5 - 2.0bar | 18bar | 18bar | G ¼ A |
KPI36 | 4.0 - 12bar | 0.5 - 1.6bar | 18bar | 18bar | G ¼ A |
KPI36 | 2.0 - 12bar | 0.5 - 1.6bar | 18bar | 18bar | G ¼ A |
KPI38 | 8.0 - 28bar | 1.8 – 6.0bar | 30bar | 30bar | G ¼ A |
Pressure Switch Type KP(Dual):
Type | Pressure Range (bar) | Differential (bar) | Permissible Op. Press. (bar) | Max. Test Press. (bar) | Pressure Connection |
Control | Safety | Control | Safety |
KP44 | 2.0 - 12.0 | 0.5 – 6.0 | 0.7 - 4.0 | 1.0 | L&R:17 | L:25/R:19 | 2xG ¼ A |
Product Description of Pressure Switch Type KP
KP pressure switches are for use in refrigeration and air conditioning systems to give protection against excessively low suction pressure or excessively high discharge pressure.
KP pressure switches are also used for starting and stopping refrigeration compressors and fans on air-cooled condensers.
A KP pressure switch can be connected directly to a single-phase AC motor of up to approx. 2kW or installed in the control circuit of DC motors and large AC motors.
KP pressure switches are fitted with a single-pole double-throw (SPDT) switch. The position of the switch is determined by the pressure switch setting and the pressure at the connector. KP pressure switches are available in IP30, IP44 and IP55 enclosures.
Main characteristics of Pressure Switch Type KP
Ambient temperature: -40°C - 65°C (80°C for max. 2 hours)
Ambient temperature (PED approved units): -25°C - 65°C (80°C for max. 2 hours)
Media temperature: -50°C - 100°C
Max. Working Pressure: LP: PS / MWP = 17 bar
KP 4, KP 47 (LP side): PS / MWP = 21.5 bar
KP17, KP47 and KP7BS (HP side):PS / Mwp=32 bar
KP 6: PS / MWP = 46.5 bar
Max. Test Pressure: LP: Pe = 20 bar
KP 4, KP 47 (LP side): Pe = 24 bar
HP: Pe = 35 bar
KP 6: Pe = 46.5 bar
Contact Load: Alternating cur. AC1&AC3=16 A, 400 V / AC15=10A, 400 V / Direct cur. DC13: 12 W, 220 V
Tightening torque: max. 2 Nm
Rated impulse voltage: 4 kV
Pollution degree: 3
Short circuit protection, fuse: 16 A
Insulation: 400 V
Enclosure: IP30 / IP44 / IP55
NOTE: For technical data on types of pressure switch type KP, please check manufacturer data sheet no. AI213186439478en-001203 dated 2022.09.
Product Description of Pressure Switch KPS
The KPS Series consists of a series of pressure and temperature-controlled switches. In this series, special attention has been given to meeting demands for a high level of enclosure, robust and compact construction, and resistance to shock and vibration.
For KPS pressure switches the position of the contacts depends on the pressure in the inlet connection and the set scale value.
The series covers most outdoor as well as indoor application requirements and is suitable for use in monitoring alarm and control systems in factories, diesel plants, compressors, power stations and on-board ships.
Main characteristics of Pressure Switch KPS
Switch: Single-pole changeover (SPDT)
Contact material: Gold-plated silver contact
Contact load AC: Ohmic=10 A, 440 V, AC-1 / Inductive=6A, 440V, AC-3 & Inductive= 4A, 440V, AC-15
Contact load DC: 12 W, 220 V, DC-13
Ambient temperature: -40°C - 70°C (KPS 31-39)
Ambient temperature: -25°C - 70°C (KPS 43-47)
Temperature of medium: -40°C - 100°C (KPS 31-39)
Temperature of medium: -25°C - 100°C (KPS 43-47)
Vibration resistance: Vibration-stable in the range 2 – 30 Hz, amp. 1.1 mm og 30 – 300 Hz, 4 g.
Enclosure: IP67
Cable entry: Pg 13.5 for cable diameters from 5 – 14 mm.
Identification: The type designation and code no. of the unit is stamped in the side of the housing.
Pressure Switch Type KPS
Type | Setting Range | Adjustable/Fixed Differential | Permissible Op. Pressure | Max. Test Pressure | Pressure Connection |
KPS31 | 0 – 2.5bar | 0.1bar | 6bar | 6bar | G ¼ |
KPS31 | 0 – 2.5bar | 0.1bar | 6bar | 6bar | G ⅜A |
KPS33 | 0 – 3.5bar | 0.2bar | 10bar | 10bar | G ¼ |
KPS33 | 0 – 3.5bar | 0.2bar | 10bar | 10bar | G ⅜A |
KPS35 | 0 – 8bar | 0.4 – 1.5bar | 12bar | 12bar | G ¼ |
KPS35 | 0 – 8bar | 0.4 – 1.5bar | 12bar | 12bar | G ⅜A |
KPS35 | 0 – 8bar | 0.4bar | 12bar | 12bar | G ¼ |
KPS37 | 6 – 18bar | 0.85 – 2.5bar | 22bar | 27bar | G ¼ |
KPS37 | 6 – 18bar | 0.85 – 2.5bar | 22bar | 27bar | G ⅜A |
KPS39 | 10 – 35bar | 2.0 – 6bar | 45bar | 53bar | G ¼ |
KPS39 | 10 – 35bar | 2.0 – 6bar | 45bar | 53bar | G ⅜A |
Pressure Switch Type KPS for High Pressure and Pulsating Media
Type | Setting Range | Adjustable/Fixed Differential | Permissible Overpressure | Max. Test Pressure | Min. Burst Pressure | Pressure Connection |
KPS43 | 1 – 10bar | 0.7 – 2.8bar | 120bar | 180bar | 240bar | G ¼ |
KPS45 | 4 – 40bar | 2.2 – 11bar | 120bar | 180bar | 240bar | G ¼ |
KPS47 | 6 – 60bar | 3.5 – 17bar | 120bar | 180bar | 240bar | G ¼ |
Documents:
Data Sheet of Pressure Switch and Thermostat Type KP and KPI - AI000086439001en-001101 dated 2025.02
Data Sheet of Pressure Switch Type KP - AI213186439478en-001203 dated 2022.09
Data Sheet of Pressure switch and Thermostat KPS - AI227086438792en-001001 dated 2024.07
Declaration of Conformity dated 10.06.2025
This certificate replaces the previous certificate ELE086320XG/003.