Materials/Components
Pumps, piping, tanks, valves, section valves, open nozzles, filters, control and monitoring systems as described in Tema Sistemi Technical Documentation Booklet.
The open type Bronze (Cu Sn 12) nozzle designated as WM 101 is represented in the relevant drawing. The nozzle is also available in nickel coated version.
Fields of application
Local application fire-fighting system for the protection of high fire risk areas in machinery spaces of category A as required by Reg. II-2/10.5.6.2 of SOLAS 74, as amended. The system may also be arranged on high speed crafts in compliance with para. 7.7.3.2 chapter 7 of HSC Code as amended by resolution MSC.97(73).
Nozzles type AQUATECH WM 101 arrangement and main characteristics
K-factor (lpm/bar1/2) | 1.0 |
Nominal operating pressure | 100 bar (nominal); 90-110 bar (min-max) |
Minimum vertical distance to fire source | 2 m |
Maximum vertical distance to fire source | 10 m |
Maximum nozzle spacing | 4 m |
Nozzle arrangement (*) | 3x3 (square arrangement) |
(*) According to Par 3.4.2.2 of Appendix to MSC.1/Circ.1387.
The outer nozzles can be located either at the edge of the protected area or outside of the protected area.
Single row installation: the outer nozzle should be placed at least at the edge of the protected area with max horizontal spacing of 2 m.
Reference documents
Tema Sistemi Technical Documentation Booklet and Enclosures filed by RINA with n. CSST-7039, CSST-7040 and CSST-7041 and CSST-7045.
Tema Sistemi WM 101 nozzle drawing approved by RINA with n. CSST-26432.
TESI Laboratory test report n. 188/C dated 30/06/2010, filed by RINA with n. CSST-7037.
Tema Sistemi Test Report n. TS/WM101/02/07 dated 28/06/2010, filed by RINA with n. CSST-7035.
Test Report n° TS/WM/01/21 issued by Brand technology filed with n° CSST-19035.
|